Salicru SLC ADAPT User manual

SLC ADAPT
SLC CUBE 3+
SLC TWIN PRO
SLC TWIN PRO 33
SLC X-TRA
MAKE BEFORE BREAK MANUAL BYPASS PANEL FOR UPS (BM*):
USER'S MANUAL

2SALICRU

3
General index
1. INTRODUCTION.
1.1. ACKNOWLEDGEMENT LETTER.
2. INFORMATION FOR SAFETY.
2.1. USING THIS MANUAL.
2.1.1. Conventions and used symbols.
2.2. ADDITIONAL SAFETY NOTICES.
3. QUALITY AND STANDARD GUARANTEE.
3.1. DECLARATION OF THE MANAGEMENT.
3.2. STANDARD.
3.3. ENVIRONMENT.
4. DESCRIPTION.
4.1. TYPES OF MANUAL BYPASS PANELS.
4.2. PRODUCT DEFINITION.
4.2.1. Nomenclature.
5. INSTALLATION.
5.1. TO CONSIDER IN THE INSTALLATION.
5.2. EQUIPMENT RECEPTION.
5.2.1. Unpacking, contents checking and inspection.
5.2.2. Storage.
5.2.3. Unpacking.
5.2.4. Relocation till the installation place.
5.2.5. Location.
5.3. CONNECTION.
5.3.1. Connection of the power supply to the bypass panel. UPS input
line (rectifier).
5.3.2. Connection of the power supply of the bypass panel. Static
bypass line (type of panels -B only).
5.3.3. Connecting the UPS with the bypass panel.
5.3.4. Connection of the loads to the bypass panel.
5.3.5. Connection of the auxiliary contact of the UPS manual bypass,
with the bypass panel (not available in TWIN PRO and PRO 33
panels).
5.3.6. Connection of the auxiliary contact of the UPS output switch,
with the bypass panel (available in CUBE3+ series only).
5.3.7. Systems with «n» equipments in parallel or redundant.
5.3.7.1. Power connections.
5.3.7.2. Connection of the auxiliary contact of the manual bypass
switch of each UPS, with the one in the bypass panel (not
available in panels of TWIN PRO and PRO 33 series).
5.3.7.3. Connection among the auxiliary contact of the output switch
of each UPS, with the ones in the bypass panel (available in
panels of CUBE3+ and X-TRA series).
6. START UP AND SHUTDOWN.
6.1. CONTROLS BEFORE THE START UP.
6.2. OPERATION TO SHIFT FROM «OUT OF SERVICE»(UPS
OR UPS’S TO «OFF») TO «NORMAL OPERATING» (LOADS
SUPPLIED BY THE UPS OR UPS’S).
6.2.1. Manual bypass panel with one UPS only.
6.2.2. Manual bypass panels with two or more UPS’s.
6.3. SHIFTING FROM «NORMAL OPERATING» (LOADS SUPPLIED
BY THE UPS OR UPS’S) TO «MAINTENANCE OPERATING»
(LOADS SUPPLIED THROUGH THE MANUAL BYPASS).
6.3.1. Manual bypass panels with one UPS only.
6.3.2. Manual bypass panel with two or more UPS’s.
6.4. SHIFTING FROM «MAINTENANCE OPERATING» (LOADS
SUPPLIED THROUGH THE MANUAL BYPASS) TO «NORMAL
OPERATING» (LOADS SUPPLIED BY THE UPS OR UPS’S).
6.4.1. Manual bypass panels with one UPS only.
6.4.2. Manual bypass panels with two or more UPS’s.
6.5. DAILY START UP/SHUTDOWN PROCEDURE OF THE UPS OR
UPS'S (INVERTER START UP / SHUTDOWN).
6.6. COMPLETE SHUTDOWN OF THE PANEL-UPS SET.
6.6.1. Manual bypass panel with one UPS only.
6.6.2. Manual bypass panels with two or more UPS’s.
USER'S MANUAL

4SALICRU
SALICRU
1. INTRODUCTION.
1.1. ACKNOWLEDGEMENT LETTER.
We would like to thank you in advance for the trust you have
placed in us by purchasing this product. Read this instruction
manual carefully in order to be familiarized with its contents,
because, as much as you know and understand the equipment
the highest will be your satisfaction and safety levels and their
features will be optimized too.
We remain at you entire disposal for any further information or
any query you should wish to make.
Yours sincerely.
•The equipment here described can cause important
physical damages due to wrong handling. This is why,
the installation, maintenance and/or fixing of itself must
be done by our staff or qualified personnel exclusively.
•Although we have made every effort to guarantee a com-
plete and accurate information in this user’s manual, we
are not responsible for any errors or omissions that may
exist.
The images included in this document are mere illustrations
and they could not represent the part of the equipment ex-
actly, therefore they are not contractual. Nevertheless, dif-
ferences that could exist will be alleviated or solved with
the correct labelling of the equipment.
•According to our policy of constant evolution, we reserve
the right to modify the specifications, operating or
described actions in this document without fore-
warning.
•Any reproduction, copy or third party concession,
modification or partial or in whole translations of this
manual or document, in any format or media, is prohib-
ited without the previous written authorization of our
firm, being reserved the full and exclusive ownership right
over it.

5
2.2. ADDITIONAL SAFETY NOTICES.
•In the point of view of the installation and electrical safety,
bypass panels must be considered as transformers or
power lines of distribution.
•As the equipment has protection against electrical shock of
class I, it is essential to install the protective earth cable (con-
nect the PE cable to the terminal ( )).
•The bypass panel must be installed by qualified per-
sonnel and it can be used by trained personnel
only, just with help of this «User’s manual».
•It is important to meet the safety instructions stated in the
own «User’s, installation and start manual of the UPS».
The instructions that you are reading are referred to the
own manual bypass panel only, and they are complemen-
tary to the «UPS user’s manual».
•The neutral regimes from the input to the output are iden-
tical for the bypass panels «with no galvanic isolation». It is
mandatory to keep the neutral regime the same, for both the
bypass panel and the UPS.
•When a bypass panel has a galvanic isolation trans-
former, as an option and fitted in by the factory or in-
stalled later on by the end user, either in the input or output of
the equipment, protections against indirect contact (RCD) must
be fitted in at the output of each isolation transformer, in order
to avoid the electrical shock risk in the secondary winding
(transformer output), because due to its own nature of iso-
lating will avoid the tripping of the protections fitted in the
primary winding of the transformer.
•As a reminder, all the installed isolation transformers or
those ones supplied from factory, the output neutral (N) is
connected to the PE ( ) through a cable bridge between
the neutral and PE terminals (TT regime). In case, it is re-
quired an isolated output neutral, this cable bridge must be
removed (IT regime), take all the cautions stated in the re-
spective local and/or national low voltage regulations.
•In those installations with IT neutral regime, the switches
and circuit breaker protections must break the NEUTRAL
apart from the three phases.
2. INFORMATION FOR SAFETY.
2.1. USING THIS MANUAL.
The generic documentation of the equipment is supplied in
digital format in a CD-ROM and it includes among other docu-
ments the own user’s manual of the system and the document
EK266*08 concerning the «Safety instructions». Before doing
any action in the equipment as regards to installation or start
up, location change, setting or handling of any nature, read
them carefully.
The purpose of the user’s manual is to provide the information
concerning the safety and the explanations of the procedures to
follow for the installation and operating of the equipment. Read
them carefully and follow the stated steps in the established
order. The identification of all parts linked with the connection
and start up by means of labels with their functionality, is corre-
lated in the instructions of this document, in order to make any
operating easy and reliable.
It is mandatory the compliance with «Safety instruc-
tions», being the legal responsible the end user as re-
gards to its observance and application.
Finally, once the equipment is installed and in operation, it is rec-
ommended to keep the documentation CD-ROM in a safe place
with easy access, for the future consults or doubts that could arise.
The following terms are used in the document indistinctly when
referring to:
•«Bypass,panel, equipment, or unit».- To the manual by-
pass panel.
•«System or set».- Set based on one or more UPS’s and the
manual bypass panel.
•«T.S.S.».- Technical Service & Support.
•«Client, fitter, operator or end user».- They are used indistinctly
and extending to the fitter and/or operator, they will do the cor-
responding actions, being able to revert the responsibility of doing
the respective actions in the same person as they are acting on
behalf of himself.
•In those installations with IT neutral regime, the switches
and circuit breaker protections must break the NEUTRAL
apart from the phase or phases.
2.1.1. Conventions and used symbols.
Some symbols can be used and shown in the equipment and/
or in the context of the user’s manual.
For more information concerning the «Safety instructions»,
see section 1.1.1 of document EK266*08.
USER'S MANUAL

6SALICRU
3. QUALITY AND STANDARD GUARANTEE.
3.1. DECLARATION OF THE MANAGEMENT.
Our target is the client’s satisfaction, therefore this Management
has decided to establish a Quality and Environmental policy, by
means of installation a Quality and Environmental Management
System that becomes us capable to comply the requirements de-
manded by the standard ISO 9001 and ISO 14001 and by our
Clients and concerned parts too.
Likewise, the enterprise Management is committed with the
development and improvement of the Quality and Environ-
mental Management System, by means of:
•The communication to all the company about the impor-
tance of satisfaction both in the client’s requirements and
in the legal and regulations.
•The Quality and Environmental Policy diffusion and the fixa-
tion of the Quality and Environment targets.
•To carry out revisions by the Management.
•To provide the needed resources.
3.2. STANDARD.
The Make Before Break Manual Bypass Panel product
is designed, manufactured and commercialized in accordance
with the standard EN ISO 9001 of Quality Management Sys-
tems and certified by SGS body. The marking shows the
conformity to the EEC Directive by means of the application of
the following standards:
•2014/35/EU. - Low Voltage Directive (LVD).
•2014/30/EU. - Electromagnetic Compatibility (EMC).
•2011/65/EU. - Restriction of Hazardous Substances in elec-
trical and electronic equipment (RoHS).
In case of any modification or intervention over the equip-
ment by the end-user, the manufacturer is not responsible.
Declaration of conformity CE of the product is at the
client disposal under previous request to our headquar-
ters offices.
3.3. ENVIRONMENT.
This product has been designed to respect the Environment and
manufactured in accordance with the ISO 14001 norm.
Equipment recycling at the end of its useful life:
Our company commits to use the services of authorised societies
and according to the regulations, in order to treat the whole recov-
ered product at the end of its useful life (contact your distributor).
Packaging:
To recycle the packaging, follow the legal regulations in force,
in accordance with the particular norm of the country where the
equipment is installed.

7
4. DESCRIPTION.
•The manual bypass is a peripheral option to the UPS, which
allows selecting the power supply source that feeds the
loads, either from the UPS or directly from commercial elec-
trical mains. If the UPS has an isolation transformer at its
output or in the static bypass line, the manual bypass panel
must incorporate it, in order to make euqal both neutral re-
gimes.
The isolation transformer is an option, which provides gal-
vanic isolation between the primary and secondary wind-
ings, in such way that it attenuates the electrical noises
and transients coming from mains largely, and also they are
transferred to the secondary winding in minor extent.
•The type of the manual bypass panel is make before break,
so it doesn’t break the power supply to the loads when
doing the shifting, unless it is operated in different order of
the established one.
•In case the panel incorporates the «Backfeed protection»
contactor, its operating must be considered as automatic
and it doesn’t require any attention unless any of the pro-
tection fuses is blown. Do not handle the fuse holder switch
of the «Backfeed protection», unless it is needed to replace
any of these protection parts.
•These instructions are generic for each one of the stated
series in the nomenclature, regardless of the type of panel.
Omit those terminal connections and manoeuvring of the
switches that your unit doesn’t have.
4.1. TYPES OF MANUAL BYPASS PANELS.
•Structurally, there are two type of manual bypass panels
according to the own structure of the UPS:
Standard or basic (Fig. 1). With common input for the
UPS feeding (rectifier-PFC) and the static bypass line.
UPS
MANUAL BYPASS
PANEL
To loads
Input line
IT -option-
Fig. 1. Standard manual bypass connection with the UPS.
With separate bypass line (Fig. 2). These panels have
separate terminals for input and static bypass lines, so
it makes possible to supply both mains from uneven
sources, like: two companies, one company and one
generator set, etc...
UPS
MANUAL BYPASS
PANEL
To loads
Input line
Static bypass line
input
IT -option-
Fig. 2. Manual bypass panel connection with the UPS with
separate bypass line.
•The auxiliary contacts of the manual bypass and output
switches, are not available in all series.
•For parallel or redundant systems based on «n» UPS’s, the
quantity of switches in the panel will be doubled for each one
of them that it is included, less the own manual bypass switch
that it is always common for the complete parallel system.
•In graphical way, Fig. 2 and 3 the galvanic isolation trans-
former is shown at the output, less those ones which under
request or particular specifications are requested. In the
point of view of taking advantages of the inherent features,
efficiency and price, it is the most recommended electrical
connection.
Nevertheless and depending if the unit has or not separate by-
pass line, the isolation transformer can be placed in one side or
other:
The standard or basic equipment and in case it is used
as input voltage adaptor. So its electrical position will
be at the input necessarily.
Those models with separate bypass line, it will be con-
nected at its input, when input mains of the UPS and
the static bypass line come from two different sources;
in order to avoid the direct connection of the neutral at
the output of the own UPS.
•The manual bypass panel will be connected with the input line,
static bypass line, the UPS and loads, by respecting the
phase or phases rotation, neutral N and the PE cable
stated in the labelling of any of them.
•If case of any discrepancy between the labelling and the in-
structions of this manual, the labelling will always prevail.
USER'S MANUAL

8SALICRU
4.2. PRODUCT DEFINITION.
4.2.1. Nomenclature.
3 BM-CUBE+-P-40-LBT-2/2 EE602322-1.
EE* Particular specifications of the client.
2 First character of the output voltage for single phase or phase
to phase voltage for three phase. Omit for 230V or 3x400V.
2 First character of the input voltage for single phase or phase
to phase voltage for three phase. Omit for 230V or 3x400V.
T Isolation transformer. Located at the output, less those ones
with separate bypass line which comes from a different
source of the UPS input mains.
B Equipment with separate bypass line.
L Single phase in/out configuration.
M Single in / three out configuration.
N Three in / single out configuration.
Three in/out configuration.
40 Power in kVA.
P Manoeuvring mechanisms by means of circuit breakers. In-
distinctly of SLC CUBE3 + parallel UPS systems, the output
mechanism is always a disconnect switch, never a circuit
breaker.
ADAPT
CUBE3+
X-TRA Series of the equipment, which is destined the panel.
TWIN PRO
TWIN PRO 33
M Make before break.
B Manual bypass.
C Exclusive protection panel with no manual bypass.
3 Quantity of equipments in parallel. Omitted for single units.

9
5. INSTALLATION.
•Read and respect any information as regards to Safety,
which is described in section 2 of this document. To ob-
viate any of the described indications, can cause serious or very
serious injuries to persons with direct contact or accidents in the
vicinity, as well as failures in the own bypass panel, equipment or
equipments and/or loads connected to the system.
•Check that the data in the nameplate is the required one by
the installation.
•A wrong connection or manoeuvring, can cause failures in
the panel, equipment or equipments and/or loads connected
to the system. Read the instructions of this manual carefully
and follow the stated steps in the established order.
•The connection will only be done, if the switches of
the equipment or equipments are in off position and
with no mains (switch or switches of the power supply line
or lines of the panel must be turned «Off»).
•Any connection of the bypass panel described in this docu-
ment will be done according to both the labelling of the
unit and the single line diagrams. Structurally, there are six
types of panels, regardless of their possible configurations
(L, M, N,...):
Generic manual bypass panel for a standard UPS (Fig. 3).
Generic manual bypass panel for a standard UPS with
separate bypass line (Fig. 4).
Manual bypass panel for «n» standard parallel or re-
dundant UPS’s (Fig. 5). For UPS of CUBE3+, TWIN PRO and
TWIN PRO 33 series.
Manual bypass panel for «n» standard parallel or redun-
dant UPS’s (Fig. 6), for UPS of ADAPT and X-TRA series.
Manual bypass panel for «n» parallel or redundant UPS’s
with separate bypass line (Fig. 7), for UPS of CUBE3+,
TWIN PRO and TWIN PRO 33 series.
Manual bypass panel for «n» parallel or redundant UPS’s
with separate bypass line (Fig. 8), for UPS of ADAPT and
X-TRA series.
Apart from the stated structures, there are several aspects re-
garding the connection of the control wiring of each UPS series,
which are explained later on in this section.
•The reproduced illustrations in this document are mere
examples, and they are intended to show the lineal order
layout of the manoeuvring mechanisms, without taking ac-
count of the physical format of them due to the power rate
of the equipment. Another factor to consider, it is that all
figures show the circuit breaker switch option “P” of the
manoeuvring mechanisms.
•According to the model of the panel, the enclosure can differ
(plastic, metallic case or metallic cabinet), so the aspect of
them could be affected, but the order would be the same.
•Depending on the power of the bypass panel and requested
version, the manoeuvring mechanisms can differ in quantity
(parallel systems), quantity of poles (depending on the configura-
tion), format, size and type (switch or circuit breaker), but they
will always be identified through the labelling.
Pay attention to the stated steps to change the oper-
ating mode, attending the labelling over the manoeu-
vring mechanisms.
•The manual bypass panel version with separate bypass line (-B),
has additional parts of connection and control, which can only
be found in this type of panel. Omit, any reference to them in the
standard or basic version.
5.1. TO CONSIDER IN THE INSTALLATION.
•These instructions are generic for any manual bypass panel
of this series. Omit those not available terminal connections.
•All connections in the panel are done through terminals.
Nevertheless in some models and due to their high power or
current, the connection of the cables can be done directly to
the copper rods of the own switches.
•Regarding the main PE cable and earth bonding cable con-
nections, the panels usually have two points located on op-
posite ends, generally by threaded stud.
•In the documentation supplied in the CD-ROM to-
gether with each UPS, it is available the information
regarding the «Recommended installation» for each one of
the input and output configurations. In this document, it is
shown the circuit diagrams, the size of the protections and
minimum cross cable section of the cables that join the
equipment with the panel according to the nominal oper-
ating voltage. All figures are calculated for a maximum
cable length of 30 m between the distribution panel,
equipment and loads.
For higher lengths correct the cross cable sections in
order to avoid dropping voltages, by respecting the
Regulations or Standards corresponding to the country.
In the same documentation and for each configuration, it
is available the information for «N» units in parallel, as
well as the features of the own «Backfeed protection».
It is mandatory to respect all the indications stated in
the UPS user’s manual as regards to the «Backfeed pro-
tection», considering the possibility of having or not the
separate bypass line and the corresponding actions to
make in each case.
•In parallel systems, the length and cross cable sec-
tion, which goes from the panel till each UPS and vice
versa, will be the same for all of them with no exception.
•Cross cable section must be always considered according
to the size of the own terminals of the switches, in order
to clamp them properly and to give an optimal contact be-
tween both parts.
USER'S MANUAL

10 SALICRU
•The data in the nameplate of the equipment shows the
nominal currents only as the safety standard EN-IEC
62040-1 states. The overload conditions are considered as
a nonpermanent and exceptional operating mode.
•If peripheral elements are going to be added at the input, output
or bypass of the UPS or parallel systems like transformers or auto-
transformers, the stated currents in the nameplates of those parts
must be considered in order to use the appropriate cross cable
section, by respecting the Local and/or National Low Voltage Elec-
trotechnical Regulation.
•Once the installation is finished, do not forget that the by-
pass panel is connected to a UPS or UPS set. Starting from
the concept that the UPS is an electrical generator, the end
user will take the needed cautions against the direct or in-
direct contact.
5.2. EQUIPMENT RECEPTION.
5.2.1. Unpacking, contents checking and inspection.
•To unpack it, see section 5.2.3.
•When receiving the equipment, check that no damages
have occurred during transport (impacts, falls, ...) and the
features of the equipment corresponds with the stated in
the purchase order, so it is recommended to unpack the
equipment for an initial visual inspection.
•In case of observing damage, make the appropriate claims
to your supplier or in lack of it to our firm.
Do not start up any equipment when external dam-
ages have been observed.
•Also check that the data in the nameplate sticked in the
packaging and the equipment, correspond to the one stated
in the purchase order, so it will be needed to unpack it (see
section 5.2.3). Otherwise, make the nonconformity as soon as
possible, quoting the serial number of the equipment and the
reference in the delivery note.
•Check the contents in the packaging:
The own bypass panel.
The user’s manual in electronic format (CD-ROM).
Those panels supplied in wall mounting format, the ac-
cessories to fix it to the wall (bolts and nuts and sup-
ports) and the whole layout diagram.
•Once the reception is finished, it is better to pack the panel again
till its commissioning, in order to protect it against mechanical
impacts, dust, dirt, etc...
5.2.2. Storage.
•The equipment storage, will be done in a dry and cool place,
protected from rain, dust and water jets or chemical agents. It
is advisable to keep the equipment inside its original packaging
because it has been designed to guarantee the maximum pro-
tection during transport and storage.
5.2.3. Unpacking.
•The equipment unpacking can have wooden pallet, card-
board or wooden box depending on the case, expanded pol-
ystyrene corners (EPS) or polyethylene foam (EPE), plastic
bag and polyethylene bands. All materials are recyclable;
so if they are going to be disposed, do it in accordance with
the regulations in force. It is recommended to keep the
packaging, in case it was needed in future.
•Proceed to the equipment unpacking.
To do it, cut the bands of the cardboard enclosure and/or the
sealing adhesive tape. Those panels with wooden packaging,
open it with the appropriate means available.
Remove the equipment out from the cardboard or wooden en-
closure.
5.2.4. Relocation till the installation place.
•If the reception area is far from the installation place, it is
recommended to move the equipment by means of a pallet
jack or the most suitable transport means, keeping in mind
the remoteness between both points.
If the distance is important, it is recommended to move the
equipment completely packed till the installation place and
later on unpack it.
5.2.5. Location.
•Locate the equipment paying attention to the indications
and recommendations stated in the safety instructions
EK266*08.
•The equipment will be located close to the UPS or parallel
system based on «n» equipments.
•The manual bypass panels are supplied in wall mounting
cases, less those exception cases assembled in floor
standing cabinets.
For the first option, make the wholes in the wall according
to the diagram, supplied in paper together with the fixing
accessories, and proceed to fix it.
5.3. CONNECTION.
•Wall mounting cases are supplied with the cable glands al-
ready assembled, of the suitable size for the foreseen cables.
•Depending on the input, bypass and/or output typology
(single phase or three phase), the quantity of terminals of
each strip can differ. Connect the corresponding cables ac-
cording to each case, by respecting the phase (R) or phases
(R-S-T) and neutral (N) rotation.

11
•When discrepancies between the labelling of the
equipment and the instructions of this user’s manual
exist, the labelling in the equipment will always prevail.
•The references in bold between brackets, which are shown
in the different points of this section, correspond to the UPS
elements identified in their own user’s manual. For more infor-
mation consult that document.
5.3.1. Connection of the power supply to the bypass panel.
UPS input line (rectifier).
•It is mandatory to connect the main protection earth
cable to the terminal labelled as ( ), being sure that
it is done before supplying voltage to the bypass panel.
•Connect the power supply cables of the input line to tto the termi-
nals labelled as «INPUT LINE» of the bypass panel, by respecting
the phase (R) or phases (R-S-T) and neutral (N) rotation, stated in
the equipment labelling and this manual.
It is essential to have neutral (N).
5.3.2. Connection of the power supply of the bypass panel.
Static bypass line (type of panels -B only).
•It is mandatory to connect the main protection earth
cable to the terminal labelled as ( ), being sure that
it is done before supplying voltage to the bypass panel.
•Connect the power supply cables of the bypass line to the by-
pass panel, to the terminals labelled as «STATIC BYPASS INPUT
LINE», by respecting the phase (R) or phases (R-S-T) and neutral
(N) rotation, stated in the equipment labelling and this manual.
It is essential to have neutral (N).
5.3.3. Connecting the UPS with the bypass panel.
•Connect a cable bundle between the terminal strip of the
bypass panel labelled as «UPS INPUT» and the UPS input
terminals labelled as «INPUT», by respecting the phase (R) or
phases (R-S-T) and neutral (N) rotation, stated in the equipment
labelling and this manual.
•Those equipments with separate static bypass line, connect
a cable bundle between the terminal strip of the bypass
panel labelled as «STATIC BYPASS INPUT» and the UPS
input terminals labelled as «STATIC BYPASS», by respecting
the phase (R) or phases (R-S-T) and neutral (N) rotation, stated in
the equipment labelling and this manual.
•Connect the cable bundle between the terminal strip of
the bypass panel labelled as «UPS OUTPUT» and the UPS
output terminals labelled as «OUTPUT», by respecting the
phase (R) or phases (R-S-T) and neutral (N) rotation, stated in the
equipment labelling and this manual.
5.3.4. Connection of the loads to the bypass panel.
•It is mandatory to connect the main protection earth
cable to the terminal labelled as ( ), being sure that
it is done before supplying voltage to the bypass panel.
•Connect the loads to the terminal strip of the bypass panel
labelled as «LOADS OUTPUT», by respecting the phase (R) or
phases (R-S-T) and neutral (N) rotation, stated in the equipment
labelling and this manual.
5.3.5. Connection of the auxiliary contact of the UPS manual
bypass, with the bypass panel (not available in TWIN
PRO and PRO 33 panels).
•By means of control wiring (minimum 1 mm2and
maximum 2,5 mm2 ), it is mandatory to connect the
terminal strip labelled as «BYPASS AUXILIARY CONTACT» of
the UPS with the ones in the bypass panel. These signal ter-
minals are the extension of the normally opened auxiliary
contact, of its respective internal manual bypass.
The UPS auxiliary terminals are labelled as follows, de-
pending on the product series:
ADAPT, pins 1 and 2 of (JP5).
CUBE3+, two terminal strip (X51).
X-TRA, terminals (MBY1) and (MBY2).
•This connection is a safety lock against wrong manoeuvring,
which otherwise would involve damages in the UPS and/or
supplied loads, because it switches the inverter «Off» when
turning any of the manual bypass switches «On».
5.3.6. Connection of the auxiliary contact of the UPS output
switch, with the bypass panel (available in CUBE3+
series only).
•The UPS output switch has a normally opened auxiliary con-
tact, with a cable as bridge (PT) which is closing the circuit
in the terminal strip (X45).
•Remove it and by means of control wiring (minimum 1 mm2
and maximum 2,5 mm2 ) connect the terminal strip labelled
as «OUTPUT AUXILIARY CONTACT» of the UPS (X45) with
the ones in the bypass panel. These signal terminals are the
extension of the normally opened auxiliary contact, of its re-
spective internal output switch.
The purpose of this connection is to trigger an alarm in the
control panel due to the trip or turning any of the output
switches to «Off» (both UPS and/or panel).
USER'S MANUAL

12 SALICRU
INPUT LINE
LOADS OUPUT
UPS
INPUT
OUTPUT
Aux. cont. output
Aux. cont. manual bypass
UPS INPUT
MANUAL
BYPASS
UPS OUTPUT
UPS INPUT
UPS OUTPUT
(*) Aux. cont.
Manual Bypass (1)
Output (2)
MANUAL BYPASS
PANEL
(*) Aux. cont.
(1) Available in manual bypass panel for UPS's of ADAPT, CUBE3+ and X-TRA series.
(2) Available in manual bypass panel for UPS's of CUBE3+ series only.
(1) and (2) Not available in manual bypass panels for UPSs of TWIN PRO and PRO 33 series.
Fig. 3. Generic manual bypass panel for standard UPS.
INPUT LINE
STATIC BYPASS
INPUT LINE
LOADS OUPUT
UPS OUTPUT
UPS INPUT
UPS STATIC
BYPASS
STATIC BYPASS
MANUAL
BYPASS
UPS OUTPUT
(*) Aux. cont.
Manual Bypass (1)
Output (2)
UPS INPUT
INPUT
STATIC BYPASS
OUTPUT
Aux. cont. output
Aux. cont. manual bypass
MANUAL BYPASS
PANEL
UPS
(*) Aux. cont.
(1) Available in manual bypass panel for UPS's of ADAPT, CUBE3+ and X-TRA series.
(2) Available in manual bypass panel for UPS's of CUBE3+ series only.
(1) and (2) Not available in manual bypass panels for UPS's of TWIN PRO and PRO 33 series.
Fig. 4. Generic manual bypass panel for a UPS with
separate bypass line.
5.3.7. Systems with «n»equipments in parallel or
redundant.
5.3.7.1. Power connections.
•Make the connections stated in sections 5.3.1 and 5.3.2.
•Make and repeat for each equipment that makes the
system, the connections stated in section 5.3.3.
5.3.7.2. Connection of the auxiliary contact of the manual bypass
switch of each UPS, with the one in the bypass panel (not
available in panels of TWIN PRO and PRO 33 series).
•By means of control wiring (minimum 1 mm2and
maximum 2,5 mm2 ), it is mandatory to connect the
terminal strip labelled as «BYPASS AUXILIARY CONTACT» of
the UPS with the ones in the bypass panel. These signal ter-
minals are the extension of the normally opened auxiliary
contact, of its respective internal manual bypass.

13
The UPS auxiliary terminals are labelled as follows, de-
pending on the product series:
ADAPT, pins 1 and 2 of (JP5).
CUBE3+, two terminal strip (X51).
X-TRA, terminals (MBY1) and (MBY2).
•The way of connecting the control cables of the UPS’s with
the panel will differ depending on the UPS series, as well
as the quantity of available terminals in the control strip:
CUBE3+.
Make the parallel connection among the auxiliary con-
tacts of the manual bypass switch of each equipment
and the ones in the bypass panel (see Fig. 5 and 7).
ADAPT and X-TRA.
The manual bypass switch of the panel will have as
many extended auxiliary contacts of the control strip
as quantity of UPS’s to connect in parallel (see Fig. 6
and 8).
Connect the terminal strip of the panel with each UPS
of the parallel system respectively. Never joint these
connections, because each UPS has internal different
grounds.
As it has been stated previously, this connection is a safety lock
against wrong manoeuvring.
5.3.7.3. Connection among the auxiliary contact of the output
switch of each UPS, with the ones in the bypass panel
(available in panels of CUBE3+ and X-TRA series).
•The output switch of each UPS has a normally opened
auxiliary contact , with a cable as a bridge mode (PT),
which closes the circuit in the terminal strip (X45) in
CUBE3+ series or in terminal strip (OAC-1) and (OAC-2)
in X-TRA series.
•Remove it and by means of control wiring (minimum 1 mm2
and maximum 2,5 mm2 ) connect the terminal strip labelled
as «OUTPUT AUXILIARY CONTACT» of the UPS (X45) or
(OAC-1) and (OAC-2) with the ones in the bypass panel,
keeping in mind the correlative order of each one of them.
So, the «OUTPUT AUXILIARY CONTACT» terminals (X45) or
(OAC-1) and (OAC-2) of UPS nr 1 to the auxiliary terminal
strip «OUTPUT 1 UPS», the terminals «OUTPUT AUXILIARY
CONTACT» (X45) or (OAC-1) and (OAC-2) of UPS nr 2 to
the auxiliary terminal strip «OUTPUT 2 UPS» and so on,
according to the quantity of equipments that makes the
system.
INPUT LINE
LOADS OUPUT
MANUAL
BYPASS
(*) Aux. cont.
Manual Bypass (1)
UPS 1 Output (2)
•••
UPS «N» Output (2)
UPS 1 INPUT
INPUT
OUTPUT
Aux. cont. output
Aux. cont. manual bypass
MANUAL BYPASS
PANEL
UPS «N»
UPS «N»INPUT
UPS 1 OUTPUT
UPS «N»OUTPUT
•••
UPS 1
UPS 1 INPUT
UPS «N»INPUT
INPUT
OUTPUT
Aux. cont. output
Aux. cont. manual bypass
•••
•••
UPS «N»OUTPUT
UPS 1 OUTPUT
•••
•••
(*) Aux. cont.
(1) and (2) Not available in manual bypass panels for UPS's of TWIN PRO and PRO 33 series.
Fig. 5. Manual bypass panel for «n» standard UPS’s in
parallel or redundant, of CUBE3+ , TWIN PRO and PRO
33 series .
USER'S MANUAL

14 SALICRU
INPUT LINE
LOADS OUPUT
MANUAL BYPASS
Aux. cont.
UPS 1 Manual Bypass (1)
•••
UPS «N» Manual Bypass (1)
UPS 1 Output (2)
•••
UPS «N» Output (2)
UPS 1 INPUT
INPUT
OUTPUT
Aux. cont. output
Aux. cont. bypass manual
MANUAL BYPASS
PANEL
UPS «N»
UPS «N»INPUT
UPS 1 OUTPUT
UPS «N»OUTPUT
•••
UPS 1
UPS 1 INPUT
UPS «N»INPUT
INPUT
OUTPUT
Aux. cont. output
Aux. cont. bypass manual
•••
•••
UPS «N»OUTPUT
UPS 1 OUTPUT
•••
•••
(*) Aux. cont.
(2) Not available in manual bypass panels for UPS's of ADAPT series.
Fig. 6. Manual bypass panel for «n» standard UPS’s in par-
allel or redundant from ADAPT and X-TRA series.
INPUT LINE
LOADS OUPUT
MANUAL
BYPASS
Aux. cont.
Manual Bypass
UPS 1 Output
•••
UPS «N» Output
UPS 1 INPUT
INPUT
STATIC BYPASS
OUTPUT
Aux. cont. output
Aux. cont. manual bypass
MANUAL BYPASS
PANEL
UPS «N»
UPS «N»INPUT
UPS 1 OUTPUT
UPS «N»OUTPUT
•••
UPS 1
UPS 1 INPUT
UPS «N»INPUT
INPUT
STATIC BYPASS
OUTPUT
Aux. cont. output
Aux. cont. manual bypass
STATIC BYPASS
INPUT LINE
UPS «N»STATIC BYPASS
UPS 1 STATIC BYPASS
•••
•••
•••
UPS «N»OUTPUT
UPS 1 OUTPUT
•••
UPS 1 STATIC BYPASS
UPS «N»STATIC BYPASS
•••
•••
(*) Aux. cont.
(1) and (2) Not available in manual bypass panels for UPS's of TWIN PRO and PRO 33 series.
Fig. 7. Manual bypass panel for «n» UPS’s with separate
bypass line in parallel or redundant from CUBE3+,
TWIN PRO and PRO 33 series.

15
INPUT LINE
LOADS OUPUT
INPUT
STATIC BYPASS
OUTPUT
Aux. cont. output
Aux. cont. bypass manual
MANUAL BYPASS
PANEL
UPS «N»
UPS 1 OUTPUT
UPS «N»OUTPUT
UPS 1
UPS 1 INPUT
UPS «N»INPUT
INPUT
STATIC BYPASS
OUTPUT
Aux. cont. output
Aux. cont. bypass manual
•••
•••
•••
MANUAL BYPASS
Aux. cont.
UPS 1 Manual Bypass (1)
•••
UPS «N» Manual Bypass (1)
UPS 1 Output (2)
•••
UPS «N» Output (2)
STATIC BYPASS
INPUT LINE
UPS «N»STATIC BYPASS
UPS 1 STATIC BYPASS
•••
UPS «N»OUTPUT
UPS 1 OUTPUT
•••
UPS 1 STATIC BYPASS
UPS «N»STATIC BYPASS
•••
(*) Aux. cont.
(2) Not available in manual bypass panels for UPS's of ADAPT series.
UPS 1 INPUT
UPS «N»INPUT
•••
Fig. 8. Manual bypass panel for «n» UPS’s with separate
bypass line in parallel or redundant from ADAPT and
X-TRA series.
USER'S MANUAL

16 SALICRU
6. START UP AND SHUTDOWN.
•These instructions are generic for any manual bypass panel
of this series, parallel and redundant equipments included.
Omit those manoeuvring of the switches that your unit
doesn’t have.
•The references in bold between brackets, which are shown
in the different points of this section, correspond to the UPS
elements identified in their own user’s manual. For more infor-
mation consult that document.
•The shown illustrations in this section are mere examples and
they are with four poles switches of DIN rail type, but in practice
they can differ in one or more aspects like: type of panel configu-
ration, format, size or protection type. Nevertheless, in any case
the order will not be different from the stated in them.
Also, in the manual bypass panels in parallel or redundant
equipments, the illustrations do not match with any preset
system, so they are generic for any panel regardless of the
quantity of equipments in parallel or redundant that belong
to.
6.1. CONTROLS BEFORE THE START UP.
•Check that all connections have done properly, by re-
specting the labelling of the equipment and the instructions
in section «INSTALLATION». If phase or phases and neu-
tral rotation is not respected, important damages can be
caused to the panel, UPS or UPS’s and/or connected loads.
•In order to avoid bad electrical contacts, check the connec-
tions screws are firmly tighten.
•Check all switches coming from the power supply which
feeds the bypass panel, the own ones in the panel (see Fig.
9 or 10 depending on the case) and the ones in the UPS or
UPS’s are turned «Off».
UPS INPUT STATIC BYPASS MANUAL BYPASS UPS OUTPUT
Off Off Off + Off
Fig. 9. Position of the manual bypass switches «Out of
service» (with one UPS only).
UPS 1 INPUT UPS 1 STATIC BYPASS MANUAL BYPASS UPS 1 OUTPUT
Off Off Off + Off
•••
UPS N INPUT
Off
•••
UPS N STATIC BYPASS
Off
UPS N OUTPUT
Off
•••
Fig. 10. Position of the manual bypass switches «Out of
service» (with several UPS’s).
•Make sure that all the loads are shutdown (start up
switches turned «Off»).
•Proceed in the established order of this document. Any
wrong manoeuvring over the stated switches of the by-
pass panel, or the ones in the UPS or UPS’s, can cause a break or
short-circuits in the power supply to the loads, with the unin-
tended and unexpected consequences for any part of the set.
•In the installation section, for single and parallel equipments,
it is stated the need of connecting the auxiliary contact of
the manual bypass with the one in the manual bypass panel.
Thanks to this auxiliary safety contact, in case of wrong or
different manoeuvring than the stated in this section, it is
avoided to overlap the inverter output with the UPS input
power supply.
For any change in the operating mode, respect the steps
stated in the instructions of this section strictly, and in par-
ticular ,those ones for TWIN PRO and TWIN PRO 33 series,
which do not have this auxiliary contact, but they have the
needed protections, in order to make the steps in the es-
tablished order.
Before starting the equipment up, check that the
manual bypass switch of the equipment or equip-
ments and the one in the manual bypass panel are in the
same position (UPS and Off or BYPASS and On).
6.2. OPERATION TO SHIFT FROM «OUT OF SERVICE»(UPS
OR UPS’S TO «OFF») TO «NORMAL OPERATING» (LOADS
SUPPLIED BY THE UPS OR UPS’S).
•Turn the external protections of the bypass panel «On» (RCD and/
or circuit breaker switches), they will supply energy to the termi-
nals labelled as «INPUT LINE».
•In panels with separate bypass line (-B), turn the external
protections of the bypass panel «On» (RCD and/or circuit breaker
switches) «On», they will supply energy to the terminals labelled
as «STATIC BYPASS INPUT LINE».
6.2.1. Manual bypass panel with one UPS only.
•Turn the «UPS INPUT» and «UPS OUTPUT» switches of the
bypass panel to «On». In case of including the separate by-
pass line (-B), turn the «STATIC BYPASS» switch of the bypass
panel «On» too. In the illustration of Fig. 11, it is shown the
position of switches once the manoeuvring has been done.

17
•Start up the UPS according to the procedure stated in the
«User’s, installation and start up manual» of the equipment.
The bypass panel supplies voltage to the terminals labelled
as «LOADS OUTPUT».
UPS INPUT STATIC BYPASS MANUAL BYPASS UPS OUTPUT
On On Off + On
Fig. 11. Position of the bypass panel switches in «Normal
operating»(with one UPS only).
•Start up the loads, they are supplied from the output termi-
nals of the panel, through the UPS.
6.2.2. Manual bypass panels with two or more UPS’s.
UPS 1 INPUT UPS 1 STATIC BYPASS MANUAL BYPASS UPS 1 OUTPUT
On On Off + On
•••
UPS N INPUT
On
•••
UPS N STATIC BYPASS
On
UPS N OUTPUT
On
•••
Fig. 12. Position of the bypass panel switches in «Normal
operating» (with several UPS’s).
•Turn the bypass panel switches «UPS 1 INPUT» to «UPS
N INPUT» and «UPS 1 OUTPUT» to «UPS N OUTPUT» to
«On». If the separate bypass line is also available (-B), turn
the «UPS 1 STATIC BYPASS» to «UPS N STATIC BYPASS»
switches from panel to «On» too. In the illustration of Fig.
12, it is shown the position of switches once the manoeu-
vring has been done.
•Start up all the UPS’s according to the procedure stated in
the «User’s, installation and start up manual» of the equip-
ment. The bypass panel supplies voltage to the terminals
labelled as «LOADS OUTPUT».
•Start up the loads, they are supplied from the output termi-
nals of the panel, through the UPS’s.
6.3. SHIFTING FROM «NORMAL OPERATING» (LOADS
SUPPLIED BY THE UPS OR UPS’S) TO «MAINTENANCE
OPERATING» (LOADS SUPPLIED THROUGH THE
MANUAL BYPASS).
6.3.1. Manual bypass panels with one UPS only.
•Put the UPS on bypass (inverter «Off»), according to the
procedure stated in the «User’s, installation and start up
manual» of the UPS.
It is essential to shutdown the inverter of the UPS
before proceeding, otherwise a short-circuit at its
output will be made with unexpected and unintended out-
comes for any part of the set (UPS, panel and loads).
•Remove the mechanical lock from the switch labelled as
«MANUAL BYPASS» in the bypass panel and turn it «On».
Keep the mechanical lock in a safe place, because it will
have to put it back, once the maintenance or fixing tasks
have been finished.
•Manual bypass panels with isolation transformer, the loads
will be supplied with a clean and/or attenuated voltage
from electrical noises.
•Turn «UPS INPUT» and «UPS OUTPUT» switches from bypass
panel to «Off». In case the separate bypass line (-B) was avail-
able, turn the «STATIC BYPASS» switch of the bypass panel to
«Off» too. In the illustration of Fig. 13, it is shown the position
of the switches once the manoeuvring has been finished.
•Loads are supplied by mains directly through the manual
bypass panel and UPS is completely shutdown, so it is
ready to be serviced for a preventive maintenance, fixing
or replacement for another equipment with the same speci-
fications.
UPS INPUT STATIC BYPASS MANUAL BYPASS UPS OUTPUT
Off Off On + Off
Fig. 13. Position of the bypass panel switches in «mainte-
nance operating» (with one UPS only).
•In case of faulty UPS, it can also be removed and sent to the
factory for its fixing. Nevertheless it is better not do it, because
loads would be connected to mains directly and so exposed to
mains fluctuations.
Even, if this alternative is going to be done, it is manda-
tory to remove any cable bundle connected to the
panel, which has at its opposite end the cables bare from
isolation, resulting in a risk of electrocution or short-circuit in
case of turning on any of the panel switches.
USER'S MANUAL

18 SALICRU
6.3.2. Manual bypass panel with two or more UPS’s.
•Put all the UPS’s on bypass (inverters «Off»), according
to the procedure stated in the «User’s, installation and start
up manual» of the UPS.
It is essential to shutdown the inverters of the
UPS’s before proceeding, otherwise a short-circuit at
its output will be made with unexpected and unintended out-
comes for any part of the set (UPS’s, panel and loads).
•Remove the mechanical lock from the switch labelled as
«MANUAL BYPASS» in the bypass panel and turn it «On».
Keep the mechanical lock in a safe place, because it will
have to put it back, once the maintenance or fixing tasks
have been finished.
•Manual bypass panels with isolation transformer, the loads
will be supplied with a clean and/or attenuated voltage
from electrical noises.
•Turn the «UPS 1 INPUT» to «UPS N INPUT» and «UPS
1 OUTPUT» to «UPS N OUTPUT» switches of the bypass
panel to «Off». In case of including the separate bypass line
(-B), turn the «UPS 1 STATIC BYPASS» to «UPS N STATIC
BYPASS» switches of the bypass panel «Off» too. In the
illustration of Fig. 14, it is shown the position of switches
once the manoeuvring has been done.
UPS 1 INPUT UPS 1 STATIC BYPASS MANUAL BYPASS UPS 1 OUTPUT
Off Off On + Off
•••
UPS N INPUT
Off
•••
UPS N STATIC BYPASS
Off
UPS N OUTPUT
Off
•••
Fig. 14. Position of the bypass panel switches in «Mainte-
nance operating» (with several UPS’s).
•Loads are supplied by mains directly through the manual
bypass panel and UPS’s are completely shutdown, so they
are ready to be serviced for a preventive maintenance,
fixing or replacement for another equipment with the same
specifications.
•In case of faulty UPS, it can also be removed and sent to the
factory for its fixing. This option is valid when the power of the
equipments, which are still installed is enough to supply the
loads. Even it is unlikely but not impossible, any new fault in any
of the remaining equipments and the possible consequences
that could happen will be assumed.
Even, if this alternative is going to be done, it is man-
datory to remove any cable bundle connected to the
panel, which has at its opposite end the cables bare from
isolation, resulting in a risk of electrocution or short-circuit in
case of turning on any of the panel switches.
6.4. SHIFTING FROM «MAINTENANCE OPERATING» (LOADS
SUPPLIED THROUGH THE MANUAL BYPASS) TO
«NORMAL OPERATING» (LOADS SUPPLIED BY THE UPS
OR UPS’S).
6.4.1. Manual bypass panels with one UPS only.
•Once the preventive maintenance, fixing or UPS replacing
tasks have been finished, loads must be shifted to UPS, but
checking the following points previously:
UPS switches are turned «Off».
Bypass panel switches, less the «MANUAL BYPASS»
switch are turned «Off».
•Turn the «UPS INPUT» and «UPS OUTPUT» switches of the
bypass panel to «On». In case of including the separate
bypass line (-B), turn the «STATIC BYPASS» switch of the
bypass panel «On» too.
•Turn the «MANUAL BYPASS» switch of panel bypass to
«Off» and put the mechanical lock back.
For safety it is mandatory to put back the mechanical
lock before proceeding with the operating.
•In the illustration of Fig. 15 it is shown the position of the
panel switches after doing the manoeuvring of this point.
•Start the UPS up according to the procedure stated in the
«User’s, installation and start up manual» of the equipment.
The bypass panel supplies voltage to the terminals labelled
as «LOADS OUTPUT» to the loads from UPS.
UPS INPUT STATIC BYPASS MANUAL BYPASS UPS OUTPUT
On On Off + On
Fig. 15. Position of the bypass panel switches in «Normal
operating» (with one UPS only).

19
6.4.2. Manual bypass panels with two or more UPS’s.
•Once the preventive maintenance, fixing or UPS or UPS’s
replacing tasks have been finished, loads must be shifted to
them, but checking the following points previously:
UPS’s switches are turned «Off».
Bypass panel switches, less the «MANUAL BYPASS»
switch are turned «Off».
•Turn the «UPS 1 INPUT» to «UPS N INPUT» and «UPS 1
OUTPUT» to «UPS N OUTPUT» switches of the bypass panel
to «On». In case of including the separate bypass line (-B),
turn the «UPS 1 STATIC BYPASS» to «UPS N STATIC BY-
PASS» switches of the bypass panel «On» too.
•Turn the «MANUAL BYPASS» switch of panel bypass to
«Off» and put the mechanical lock back.
For safety it is mandatory to put back the mechanical
lock before proceeding with the operating.
UPS 1 INPUT UPS 1 STATIC BYPASS MANUAL BYPASS UPS 1 OUTPUT
On On Off + On
•••
UPS N INPUT
On
•••
UPS N STATIC BYPASS
On
UPS N OUTPUT
On
•••
Fig. 16. Position of the bypass panel switches in «Normal
operating» (with one UPS only).
•In the illustration of Fig. 16 it is shown the position of the
panel switches after doing the manoeuvring of this point
•Start the UPS’s up according to the procedure stated in the
«User’s, installation and start up manual» of the equipment.
The bypass panel supplies voltage to the terminals labelled
as «LOADS OUTPUT» to the loads from UPS’s.
6.5. DAILY START UP/SHUTDOWN PROCEDURE OF THE
UPS OR UPS'S (INVERTER START UP / SHUTDOWN).
•In case of need it, see the procedure stated in the «User’s,
installation and start up manual» of the equipment.
6.6. COMPLETE SHUTDOWN OF THE PANEL-UPS SET.
6.6.1. Manual bypass panel with one UPS only.
•Shutdown the load or loads.
•Shutdown the UPS according to the procedure stated in the
«User’s, installation and start up manual» of the equipment.
•Turn the «UPS INPUT» and «UPS OUTPUT» switches of the
bypass panel to «Off». In case of including the separate by-
pass line (-B), turn the «STATIC BYPASS» switch of the bypass
panel «Off» too. In the illustration of Fig. 9, it is shown the
position of switches once the manoeuvring has been done.
•Turn «Off» the external protections of the bypass panel (RCD
and/or circuit breaker switches), which are supplying the energy
to the terminals labelled as «INPUT LINE».
•Those panels with separate static bypass line (-B), turn
«Off» the external protections of the bypass panel (RCD
and/or circuit breaker switches), which are supplying the energy
to the terminals labelled as «STATIC BYPASS INPUT LINE».
•The set is out of service completely and with no power supply.
6.6.2. Manual bypass panels with two or more UPS’s.
•Shutdown the load or loads.
•Shutdown the UPS’s according to the procedure stated in
the «User’s, installation and start up manual» of the equip-
ment.
•Turn the «UPS 1 INPUT» to «UPS N INPUT» and «UPS 1
OUTPUT» to «UPS N OUTPUT» switches of the bypass
panel to «Off». In case of including the separate bypass line
(-B), turn the «UPS 1 STATIC BYPASS» to «UPS N STATIC
BYPASS» switches of the bypass panel «Off» too. In the
illustration of Fig. 10, it is shown the position of switches
once the manoeuvring has been done.
•Turn «Off» the external protections of the bypass panel (RCD
and/or circuit breaker switches), which are supplying the energy
to the terminals labelled as «INPUT LINE».
•Those panels with separate static bypass line (-B), turn
«Off» the external protections of the bypass panel (RCD
and/or circuit breaker switches), which are supplying the energy
to the terminals labelled as «STATIC BYPASS INPUT LINE».
•The set is out of service completely and with no power supply.
USER'S MANUAL

Avda. de la Serra 100
08460 Palautordera
BARCELONA
Tel. +34 93 848 24 00
Fax +34 93 848 22 05
SALICRU.COM
www.linkedin.com/company/salicru
@salicru_SA
Product Range
Uninterruptible Power Supplies (UPS)
Lighting Flow Dimmer-Stabilisers
DC Power Systems
Static Inverters
Photovoltaic Inverters
Voltage stabilisers
The Technical Service and Support (T.S.S.) network, Com-
mercial network and warranty information are available in
website:
www.salicru.com
REF. EL043C01 REV. C CODE 401*
Other manuals for SLC ADAPT
1
This manual suits for next models
4
Table of contents
Other Salicru Protection Device manuals