Call point test
1. Run the test function in the fire alarm control panel (see the control panel manual).
2. Insert the key into the hole on the bottom of the call point. The pane will bend and the
switch will open. The LED will start flashing.
3. Pull out the key to reset the call point.
LED indicator
The red LED is flashing when the call point is activated. The LED stops flashing when the call
point is reset.
3. Installation
Disconnect power before making any electrical connections.
The ROP-110 manual call point is designed for installation indoors, in spaces with normal air
humidity. Select the place of installation so that the manual call point is visible and easily
accessible.
1. Place the mounting box against the wall and mark the location of the mounting holes
(Fig. 2).
The mounting box is sold separately. SATEL offers the ROP-BT and ROP-BS surface
mounting boxes.
Instead the SATEL surface mounting boxes, you can use a flush-mounted box
(Fig. 11).
2. Drill the holes for wall plugs (anchors).
3. Run the cables through the hole in the box (Fig. 2).
4. Use wall plugs (anchors) and screws to secure the mounting box to the wall. Select wall
plugs specifically intended for the mounting surface (different for concrete or brick wall,
different for plaster wall, etc.).
5. Remove the call point cover (Fig. 3).
6. Connect the zone circuit wires to the call point (Fig. 4). If the call point is connected to the
zone circuit at the end of line, screw a 5.6 kΩ resistor to its terminals. Connect the cable
shields to the E terminals.
7. Use screws to secure the call point to the mounting box (Fig. 5-6).
8. Insert the pane (Fig. 7-8).
9. Replace the enclosure cover (Fig. 9-10).
10.Insert the key into the hole on the bottom of the call point, then pull it out to set the pane
in its correct position (Fig. 1).