P:\INST INSTRUCTIONS\DELAYED EGRESS\INST-1581S REV F2 12-22 Page 1
1581S
MINI EXIT CHECK® DELAYED EGRESS EMLOCK®
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
California Building
Code Compliant
KEEP PUSHING. THIS DOOR WILL OPEN
IN 15 SECONDS. ALARM WILL SOUND.
Application
When unauthorized egress is initiated, the Exit Check® delays egress through the door for a period of 15 seconds.
Meanwhile, the person exiting must wait allowing personnel or security respond. The door unlocks after the 15 second
delay period has elapsed, permitting egress. A signal from the fire/life safety system will release the lock immediately
for uninhibited egress in an emergency.
Exit Check® applications include:
Restricting the egress of patients for their own safety.
Restricting the egress of commercial center patrons for minimum security application needs.
Standard Features
Small & Compact Size
650 lbs. Holding Force
15 Second Exit Delay when activated.
1 Second Nuisance Delay
Subdued Alarm with 2 Distinct Tones:
- Alarm Activation Intermittent
- Door Release – Continuous
Choice of Activation Trigger:
- Door Movement
- Exit Device w/ REX Switch
- Touch Sense Bar w/REX Switch
Instant Reset from Bypass mode for interfacing
with Patient Monitoring Systems.
Vandal resistant Proximity Sensor Trigger
Auto Sensing 12/24VDC input power
Low Power Consumption
5 foot Power Cable
Connection for Tandem Option (Pairs of Doors)
Optional Features
30 Second Exit Delay
DPS Door Position Switch Output
BAS Bond Alert Sensor Switch Output
Tandem / Auxiliary Cable
3' Cable – 1581S-TC3
10' Cable – 1581S-TC10
Building & Fire Life Safety Code Compliant
1581SND,NA,NH,NC
IBC International Building Code
IFC International Fire Code
NFPA 101 Life Safety Code
NFPA 1, UFC, Uniform Fire Code
UBC Uniform Building Code
CBC California Building Code
SBC Standard Building Code
1581SBD,BH,BC
BOCA National Building Code compliant
Chicago Building Code compliant
Selectable Automatic & Manual Power-Up
Auto Power-Up – Occurs when power is restored and/or
the fire panel is restored (Not available on California
Versions).
Manual Power-Up – This is a UBC & California Building
Code Compliant Feature – Only after power restoration
and fire panel reset may the lock be reset manually at the
opening. A power-up reset key switch or keypad is
required adjacent to the door.
GWXT/GWXT7 Auxiliary Locks
FWAX Special Locking Arrangements
California State
Fire Marshal Listed
CSFM #3774-0324:103
LISTED
CANADA
LISTED
USA
Only the 1581S and the 1581T have been UL listed as “Special Locking
Arrangements” to UL standard 294 and NFPA 101.
Any suggestions or comments to this instruction or
product are welcome. Please contact us through
our website or email engineer@sdcsecurity.com
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011
INSTALLATION INSTRUCTIONS

P:\INST INSTRUCTIONS\DELAYED EGRESS\INST-1581S REV F2 12-22 Page 2
1581S Operational Description
The door is closed and secured by latching hardware. The model 1581S Exit Check locks the door in the secured
position, and the status LED is solid green.
Activation / Alarmed Release :
Activation of the 1581S Exit Check’s 15 second unlock cycle is started by releasing the door latch and applying up to 15
lbs. of pressure to the door causing slight door movement. A short nuisance delay period is then initiated, a pre-
activation warning tone is sounded . To prevent false alarms, re-latching the door during the nuisance delay period will
silence the pre-activation warning tone and keep the door locked.
Once the nuisance delay period has been exceeded, the Exit Check continues with an irreversible door release cycle.
The integral digital countdown display and voice commands continue to inform the person intending to exit of the
seconds remaining until unlock and an alarm output is activated to alert personnel of an unauthorized exit. After the 15
second delay cycle has expired, the Exit Check will release the door allowing free egress.
Reset / Relock:
The Exit Check can be manually reset by authorized personnel by closing the door and activating the Reset input.
Request to Exit / Authorized Bypass:
Momentarily actuating the Request to Exit / Bypass input will initiate the request to exit cycle and unlock the 1581S Exit
Check allowing free egress. After the request to exit cycle has expired or the door closes, the Exit Check will
automatically relock.
By keeping the Request to Exit input continuously activated, the 1581S will remain unlocked for extended periods of
time. Releasing the Request to Exit input will restart the request to exit cycle and will relock the door after the request to
exit time has expired.
(BOCA/Chicago)
The 1581S operation complies with
BOCA National Building Code and
the Chicago Building Code: UL
Listed, Special Locking
Arrangements and Auxiliary Locks.
Per BOCA compliance, the Exit Check is manually reset by authorized personnel after an alarm by closing the door and
actuating the integral reset key switch or by momentarily closing a contact connected to the remote reset terminals. In
addition, reset will be automatically initiated once the door has been opened, then closed and remains closed for 30
consecutive seconds.
(NFPA-101)
The 1581S operation complies with
the following building and fire codes:
NFPA 101; NFPA 1-UFC; UBC; IBC;
IFC; SBC; California Building Code.
Listings: UL Listed: Special Locking
Arrangements and Auxiliary Locks;
California State Fire Marshal
(CSFM) Listed.
Option
Code
Delay Release
Time
Nusiance
Time
Reset after
Alarm
Lock Status on
Power-Up
Manual
ND 15 sec
Fixed
1 sec
Fixed
Locked or Unlocked
Selectable
Manual
NH 30 sec
Fixed
1 sec
Fixed
Locked or Unlocked
Selectable
Manual 15 sec
Fixed
1 sec
Fixed
Unlocked
Fixed
NC
(CBC Compliant)
Option
Code
Delay Release
Time
Nusiance
Time
Reset after
Alarm
Lock Status on
Power-Up
Auto/Manual
BD 15 sec
Fixed
1 sec
Fixed
Locked or Unlocked
Selectable
Auto/Manual
BH 30 sec
Fixed
1 sec
Fixed
Locked or Unlocked
Selectable
Auto/Manual
BC 15 sec
Fixed
0 sec
Fixed
Locked or Unlocked
Selectable
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

Included in Package
ARMATURE
SCREW PACK
1580S-101-C
1581S Specifications
Interior Applications Only
Size: 10"L x 2-1/8"H x 2-3/8"D
Power/Current Requirements:
- 12 - 24VDC Auto-sensing
- 320 mA @ 24VDC
- 600 mA @ 12VDC
Lock Status Relay Rating: 1 amp @ 30V resistive
DPS Rating: 250 mA @ 30V resistive
BAS Option: 250 mA @ 30V resistive
ARMATURE PLATE
1581S-10T
EMLOCK
SCREW PACK
C-1500-RF
TEMPLATE
TEMP-1581S
CONTROLLER
CABLE ASSEMBLY
CA-1581S
1581S EMLOCK
HOUSING ASSY. &
MOUNTING PLATE
TRIGGER BLOCK
ASSY 1580S-11
Note:
A remote key switch, keypad, or push
button (see models below) MUST be
provided and purchased separately to
operate the Reset and REX Functions.
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011
918 Digital Keypad
Two relay outputs:
Relay 1 -Reset;
Relay 2 – Choice of
momentary or
sustained bypass.
Digital Entry
P:\INST INSTRUCTIONS\DELAYED EGRESS\INST-1581S REV F2 12-22 Page 3
728RU
Single station two
function key switch
control for alarm
reset and access or
sustained bypass.
101-4AM
Provides visual &
audible annunciation
with audible mute for
up to four openings.
728RUL3
Single station two
function key switch
control for alarm reset
and access with a tri-
colored LED showing
door condition.
702RU
Single station one
function key switch
control for alarm reset.
101-1A
The single station
annunciator is
equipped with a tri-
colored LED and
audible alarm.
101-1AK
Visual & audible
annunciation and a
two function key
switch for alarm reset
and access or
sustained bypass.
101-PAM
Visual & audible
annunciation, timed
access, sustained
bypass and audible
mute.
Suggested Optional Equipment
Power Supply
Station Controls, Annunciator Panels, and Consoles
600 Series Power Supply
Field Selectable 12 or 24VDC modular Power Supplies with
Fire/Life Safety Emergency Release. Tri-colored LED,
separate PTC protected battery charger, and Class 2 Outputs.
602RF 1 Amp
631RF 1.5 Amp
632RF 2 Amp
634RF 4 Amp
636RF 6 Amp
PSB560
Request-to-exit touch
sense non-latching bar
that will activate the
Exit Check® when
slight pressure is
applied to the bar. For
doors without latching.
707RU
Single station two function key switch
control for alarm reset and momentary
authorized access.
708RU
Single station two function key switch
control for alarm reset and sustained
bypass.

NOTES:
- #10 self drill/tap screws provided for up to 1/8" thick metal applications
- For applications with heavier gauge material, drill (#21) and tap for #10-32 machine screws.
Door and Frame reference dimensions
IMPORTANT! – IT IS HIGHLY RECOMMENDED THAT YOU FIRST INSTALL THE MOUNTING PLATE AT TWO SLOT LOCATIONS ONLY.
THIS WILL ALLOW YOU TO MAKE PROPER ADJUSTMENTS OF THE LOCK’S POSITION PRIOR TO MARKING, DRILLING AND TAPPING
THE FOUR PERMANENT MOUNTING PLATE HOLES.
HINGE SIDE OF FRAME
(OPPOSITE FROM LOCK)
PAPER TEMPLATE
1 ⅞"
2 ⅜"
9 15/16"
2 ⅛"
SLOT LOCATIONS
PLACE AGAINST DOOR
PLACE AGAINST
DOOR JAMB
FOR R.H. DOOR
PLACE AGAINST
DOOR JAMB
FOR L.H. DOOR
DRILL ¼” DIAMETER HOLE X 9/16" DEEP
CENTER PUNCH ON
MARK & REFER TO
INSTRUCTION SHEET
FOR HOLE SIZE.
PLACE AGAINST HEADER
½” DIA. HOLE Mark location four places.
FOLD ON DOTTED LINE
05/04
DWG #4770 TEMP-1581S
1 3/16”1 ½”
SLOT LOCATIONS
P:\INST INSTRUCTIONS\DELAYED EGRESS\INST-1581S REV F2 12-22 Page 4
Door and Frame Preparation Instructions
STEP 1. Locate the paper template and fold
along the dotted line. Place the folded edge of
the template against the door stop and door at
the header while against the vertical stop,
opposite the hinge side of the door. Tape in
place at this position.
STEP 2. As indicated on the paper template,
punch the designated hole locations on the
frame and armature mounting holes on the door.
(NOTE: PRIOR TO DRILLING, INSPECT TO SEE IF
ANY OF THE HOLES CANNOT BE DRILLED DUE
TO THE FRAME OR DOOR CONFIGURATION. A
FILLER PLATE OR ANGLE BRACKET MAY BE
REQUIRED. SEE PAGE 5.)
STEP 3. Drill and tap the two 1581S mounting
holes as indicated on the paper template.
(NOTE: READ NOTE ON TEMPLATE WITH
REGARD TO SELECTING THE PROPER HOLE
SIZE FOR ARMATURE MOUNTING BOLT.)
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

Figure 2B – HOLLOW METAL DOOR
From sexnut side of door, drill exactly 1/2" hole through one metal thickness
only. From armature side of door, drill 5/8" hole to insert reinforcement tube.
Press in sexnut & reinforcement tube all the way and mount armature to door
using hardware provided per Figure 2B.
Figure 2A – SOLID DOOR
Drill exactly 3/8" through the door. From sexnut side of door, drill ½”
diameter hole 1-3/8" deep. Mount armature to door with hardware
provided per Figure 2A.
Figure 2C – REINFORCED ALUMINUM OR
HOLLOW METAL DOOR
Use letter “F” drill and tap for 5/16-18 machine screw. Mount
armature to door with hardware provided per Figure 2C.
REGULAR, FILLER PLATE & ANGLE BRACKET DETAILS
Figure 1A
REGULAR
Figure 1B
WITH FILLER PLATE
FILLER PLATE
Figure 1C
WITH ANGLE BRACKET
ANGLE BRACKET
ARMATURE HOLDER
ARMATURE
DOOR
REINFORCEMENT
BY OTHERS
LETTER “F”
DRILL & TAP 5/16-18
5/16-18 SOC HD
SCREW
WITH 3/16 (5MM)
ALLEN HEX
5/8" DRILL
ARMATURE HOLDER
ARMATURE
1/2" DRILL
REINFORCEMENT TUBE
1 – ¾” HOLLOW
METAL DOOR
5/16-18 SOC HD
SCREW
WITH 3/16 (5MM)
ALLEN HEX
ARMATURE HOLDER
ARMATURE
1/2”
SEX NUT
21/64" DRILL
DOOR
1–3/8"
5/16-18 SOC HD
SCREW
WITH 3/16 (5MM)
ALLEN HEX
P:\INST INSTRUCTIONS\DELAYED EGRESS\INST-1581S REV F2 12-22 Page 5
STEP 1. Mount armature to door. (See figures
2A, 2B & 2C.)
STEP 2. Install the mounting plate (filler plate
and/or angle bracket if needed – see figures 1A,
1B & 1C) to header with only the two screws at
the slotted hole locations at this time. Snug the
screws down lightly (do not torque) so the
mounting plate & lock can be repositioned later.
STEP 3. Temporarily install the lock to the
mounting plate with the 1/4-20 socket head
screws encased in the lock.
STEP 4. With the lock mounted, close the door
so the armature just comes into contact with the
face of the lock. If the door is not completely
closed as the lock & armature touch, open the
door and reposition the lock away from the door
as described in step 2. (THIS IS TO PREVENT
THE DOOR FROM USING THE LOCK AS THE
DOOR STOP.)
STEP 5. Remove the lock from the mounting
plate, mark & punch all remaining screw and
wiring holes. Drill & tap holes as indicated on the
paper template and install all screws.
STEP 6. Reinstall the lock to the mounting
plate. At this point, if there is no need to remove
the lock for painting or any other reason, install
the anti-tamper plugs over the socket head
mounting screws, using a soft hammer to avoid
damage to the lock case.
ARMATURE MOUNTING INSTRUCTIONS
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

WIRING DETAILS & FUNCTIONS (ALL OPTIONS SHOWN)
ROCKER SWITCH SETTINGS
CONNECTOR INPUT / OUTPUT
GREEN REMOTE TRIGGER INPUT MOM GROUND TO (-) POWER USING DRY CONTACT
BROWN RELAY – COMMON OUTPUT
ORANGE RELAY – CLOSED WHEN IN ALARM OUTPUT
YELLOW RELAY – CLOSED WHEN SECURE OUTPUT
BLACK POWER (-) INPUT REGULATED 12/24 VDC (-) POWER
RED POWER (+) INPUT REGULATED 12/24 VDC (+) POWER
BLUE RESET/REQUEST TO EXIT(REX)*INPUT MOM GROUND TO (-) POWER - DRY CONTACT
WHITE REX & MAINTAINED BYPASS INPUT (REX) MOM GROUND TO (-) POWER - DRY CONTACT
(CONT. BYPASS) AA GROUND TO (-) POWER – DRY CONTACT
RED
GREEN
WHITE
BLACK
(2) SPST DRY CONTACT OUTPUTS TO REMOTE
CONTROL ANNUNCIATOR, LED OR ALARM SYSTEM
MONITOR – RATING: 1 Amp @ 30 VOLTS RESISTIVE
DESCRIPTIONCONTROL / FUNCTION
MAIN
CONNECTOR
J1B
MAIN
CONNECTOR
J1A
WIRE
M/SL
CONNECTOR
J3
CABLE FOR TANDEM LOCK
CONNECTION
(OPTIONAL)
INTERCONNECT
INTERCONNECT CABLE INTERFACING TWO
1581S UNITS (MASTER & AUXILIARY) FOR
PAIRS OF DOORS. (CABLE MUST BE
ORDERED SEPARATELY).
DPS OPTION
CONNECTOR
WHITE
RED
BLACK
SWITCH – COMMON OUTPUT
SWITCH – DOOR OPEN OUTPUT
SWITCH – DOOR CLOSED OUTPUT
BAS OPTION
CONNECTOR
WHITE
RED
BLACK
SWITCH – COMMON OUTPUT
SWITCH – N/C OUTPUT
SWITCH – N/O OUTPUT
RATING: .250 mA @ 30 VOLTS RESISTIVE
POLARITY SHOWN WITH THE DOOR UNSECURE
** Power up lock option not available on some versions
* REX on blue reset wire when enabled by DIP switch
* UL 294 Listed, power
limited, Class 2, power
supply must be used
P:\INST INSTRUCTIONS\DELAYED EGRESS\INST-1581S REV F2 12-22 Page 6
USE ONLY SHIELDED CABLE FOR ALL SIGNAL WIRES, WITH
SHIELD GROUNDED AT ONE END
J1B
J1A
DIP SWITCHES
TRIGGER SENSOR
LOCK COIL CONNECTOR
(J4)
TANDEM CABLE (OPTIONAL)
CONNECTOR
(J1B)
CONNECTOR
(J1A)
MASTER/AUXILIARY
CONNECTOR
(J3)
TO MASTER/AUXILIARY
CONNECTOR ON
SECOND 1581S
GREEN
BROWN
ORANGE
YELLOW
BLACK
RED
BLUE
WHITE
DPS
DPS CONNECTOR
BLACK
WHITE
RED
DPS SENSOR (OPTIONAL)
DPS
OPTION
CABLE
MAIN
CABLE
DIP SWITCH DETAIL
ON
OFF
SHOWN SWITCHED TO
OFF CONDITION
Master/SlaveCoil
BAS
1
2
3
4
5
6
BAS
OPTION
CABLE
BLACK
WHITE
RED
BAS CONNECTOR
}
}
SWITCH # FUNCTION OFF ON DESCRIPTION
1 REX Time 1 Second 10 Seconds Internal relock time delay when using REX input controls
2 Power-up Option** Disabled Enabled Manual reset on power-up required when disabled; Auto reset on power-up when enabled
3 Remote Trigger Disabled Enabled When enabled, remote trigger input is used for external activation; Internal sensor disabled
4 Master/Slave Master Slave Designates lock as master or slave for tandem application (tandem cable required)
5 Door Prop Disabled Enabled
When disabled, the lock will enter alarm mode if the door is held open past the REX period.
When enabled, no alarm will sound if the door is held open past the REX period following an
authorized REX signal. Lock will relock and rearm upon closure of the door.
6 REX on Reset Input Disabled Enabled
When disabled, the blue reset will only function as a reset wire after an alarmed release.
When enabled and the lock is secure, momentarily shorting the blue reset wire to ground will
initiate a REX period.
Shunt

P:\INST INSTRUCTIONS\DELAYED EGRESS\INST-1581S REV F2 12-22 Page 7
RED
BLK
GRN
BLU
BRN
WHT
ORG
YEL
RED
BLK
GRN
BLU
BRN
WHT
ORG
YEL
POWER -
POWER +
COM
NO
NC
COM
NO
NC
600 Series
Power Supply
1581S Mini Delayed Egress
Locking Magnet
PSB560 Request-To-Exit
Touch Sense Bar
(Remote Trigger Option)
RED
BLK
WHT
BLU
RESET
BYPASS
OR
ACCESS
728RU or 728RUL3
Key Switch
Reset Station
RED
BLK
GRN LED (+)
LED (+)
LED (-)
L3
OPTION
System Wiring – Single Door
+
(-)
8 conductors 3 or 5 conductors
8 conductors
Power
Supply
To Fire Panel – Dry, Closed Contact
AC Mains
2 conductors
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
WARNING:
APPLICATION OF VOLTAGE TO THE DRY CONTACT INPUTS OF THIS UNIT
WILL CAUSE PERMANENT DAMAGE AND VOID THE WARRANTY
To Smoke Detection System – Dry, Closed Contact
S
Smoke Detection System
Dry, Closed Contact
Patient Monitoring System
To Patient Monitoring System – Dry, Open Contact
Connection to a Infant/Patient Monitoring,
Optional Equipment and Smoke Detection
System has not been investigated by UL.
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

P:\INST INSTRUCTIONS\DELAYED EGRESS\INST-1581S REV F2 12-22 Page 8
RED
BLK
GRN
BLU
BRN
WHT
ORG
YEL
RED
BLK
GRN
BLU
BRN
WHT
ORG
YEL
POWER -
POWER +
COM
NO
NC
COM
NO
NC
+
-
1581S Mini Delayed Egress
Magnet
(Set DIP switch to Auxiliary)
PSB560 Request-To-Exit
Touch Sense Bar
(Remote Trigger Option)
1581S Mini Delayed Egress
Magnet
(Set DIP switch to MASTER)
PSB560 Request-To-Exit
Touch Sense Bar
(Remote Trigger Option)
RED
BLK
WHT
BLU
RESET
BYPASS
OR
ACCESS
600 Series
Power Supply
728RU or 728RUL3
Key Switch
Reset Station
COM
NO
NC
WHT
ORG
YEL
RED
BLK
GRN LED (+)
LED (+)
LED (-)
L3
OPTION
1581S-TC3 Tandem Cable
System Wiring – Pair of Doors
3 or 5
conductors
8 conductors
Power
Supply
To Fire Panel – Dry, Closed Contact
AC Mains
2 conductors
8 conductors
8 conductors
4 conductors
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
WARNING:
APPLICATION OF VOLTAGE TO THE DRY CONTACT INPUTS OF THIS UNIT
WILL CAUSE PERMANENT DAMAGE AND VOID THE WARRANTY
Smoke Detection System
Dry, Closed Contact S
To Smoke Detection System – Dry, Closed Contact
Patient Monitoring System
To Patient Monitoring System – Dry, Open Contact
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

TRIGGER SENSOR
TRIGGER
HORIZONTAL
ALIGNMENT
VERTICAL
ALIGNMENT
1581S LOCK BODY
1581S ARMATURE
1581S ARMATURE
P:\INST INSTRUCTIONS\DELAYED EGRESS\INST-1581S REV F2 12-22 Page 9
STEP 1. After the lock has been mounted to the door and frame per the provided template, make all wiring
connections to the lock. At a minimum, this will be the power and reset inputs (black, red & blue conductors). It is
important that the reset input (blue conductor) be connected to a normally open momentary, dry contact switch (i.e.
928 Digital Keypad or 728 Key Switch) for initial setup adjustments as well as to reset the lock to a secure status
after it has been activated.
STEP 2. With all wiring connections completed, re-install the lock cover onto the lock. Ensure that the trigger
sensor is aligned with the hole in the cover. The sensor is preset at the factory to slightly project through the cover.
WARNING: DO NOT ATTEMPT TO ADJUST THE TRIGGER SENSOR LENGTH. AS THIS WILL RESULT IN DAMAGE TO
THE SENSOR AND VOID THE WARRANTY.
STEP 3. Slowly swing the door closed and visually observe the position of the armature trigger as it approaches
the trigger sensor on the lock. If the provided mounting template was used during the lock and armature installation,
the trigger & sensor should align with one another both horizontally and vertically. IMPORTANT: CORRECT
OPERATION OF THIS LOCK DEPENDS ON THE TRIGGER SENSOR BEING ABLE TO DETECT THE TRIGGER WHEN THE
DOOR IS CLOSED. A PROXIMITY ADJUSTMENT CAN BE MADE TO THE TRIGGER FOR FINE TUNING. THIS IS
EXPLAINED IN STEP 4.
STEP 4. NOTE: BEFORE STARTING THIS NEXT STEP, YOU WILL NEED TO BE ABLE TO ACTIVATE THE ALARM
RESET INPUT. After alignment has been verified, close the door and ensure DIP switch #2 is OFF. Apply power to
the lock. Push on the door. The LED should be flashing green, indicating that the lock is in the Manual Power Up
mode. Reset the lock at this time. The lock should now secure the door and the LED should be steady green. You
may change the mode to Auto Power Up by setting the #2 dipswitch to the ON position. Now when you first apply
power, you will see a solid green light and the door will be secure without having to reset the lock.
STEP 5. Activation of the 1581S can be made by door movement or an external trigger. When using the door
movement method, activation is achieved through the way the armature hardware is designed. When someone
unlatches the door and applies up to 15 lbs. pressure, the lock will hold onto the armature while simultaneously
letting the trigger/door move away from the lock/trigger sensor. Sensitivity in the detection of the trigger movement
can be adjusted for optimum sensitivity & performance. This adjustment can be made by using the 5mm hex
wrench provided with the lock. The center of the trigger or “target” is spring loaded and can be screwed in and out
of the armature thus either decreasing or increasing the space between itself and the sensor. The “spring” feature
of the target is to prevent damage from direct contact with the trigger sensor. Depending on the accuracy of the
alignment, the trigger does not have to physically touch the sensor to operate correctly.
Lock Operation and Adjustment Instructions
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

P:\INST INSTRUCTIONS\DELAYED EGRESS\INST-1581S REV F2 12-22 Page 10
Sense Bar Trigger Non-Latching
PSB560, MSB550
Power
PT-2
PT-3
Wall Mount Reset Station or Keypad
Required with 1581S
728RU
918U
702RU
101-1AK
Power
Latch Monitoring Strike Trigger
For Mortise Exit Devices
MS-16
Latch Trigger
Power
Remote Annuciators
101-1A
101-4AM
101-PAM
Power
Pair of doors with two locks and required
TC-3 cable for power and Auxiliary operation
Power
Pair of doors with two locks and required
TC-10 cable for power and Auxiliary operation
Power J-Box
Pushing either door triggers
the delayed release of both doors. Pushing either door triggers
the delayed release of both doors.
Reset Reset
Reset
Reset
Latching Exit Device with
Built-in Switch Kit Trigger
Power
PT-2
PT-3
PTH-4
Hinge
Switch
Kit
Reset
Systems Applications Reference
Activation by applying pressure to doors with latching hardware:
Pair of doors with two locks and required
TC-3 cable for power and Auxiliary operation
Power
Sense Bar Trigger Non-Latching
Reset
PSB560, MSB550
Activation by a remote trigger for doors with or without latching hardware: