
Installation
Wall Mounting. Usingthe eightscrewsprovided,attach
the two foot brackets to the sides of the enclosure.Then
attachthe unit toany securesurfacebyinserting screws
through the mounting holes in the foot brackets.
Panel Mounting. Followthe dimensionsgivenfor“Panel
Cutout”.Be sure to include the four corner screw holes.
Aftercutting anddrilling,place the frontplate onthe front
side of the panel with its gasket against the panel, and
the remainder of the square housing on the back side.
Slide the screws through the four holes drilled in the
panel,andintothethreaded holesinthe housing.Tighten
until the gasket is firmly compressed against the panel.
ExposeTerminals. Removethefourscrewswhich hold
the front plate to its flange.Remove the front plate.The
display board is attached to this front plate. It is also
connected to the power board by a ribbon cable. For
convenience, this cable can be disconnected, or the
display board can be allowed to dangle while making
connections. Connections can be made inside the
enclosure, or the terminals can be unplugged for easier
access, by gently tugging on them.
Sensor Connection. Followthe“Connections”diagram
to connect either two or three wires from the flow meter
or flow sensor.
Monitor Alarm Connection.Connect thealarm devices
to the appropriate relay terminals. Note that the relays
haveboth normally-open (NO)andnormally-closed(NC)
contacts.
Power Connection. Connect AC or DC power as
desired to the appropriate terminals. For safety, if using
AC power, be sure to connect the ground terminal
provided to a good earth ground.
Replace the front panel, taking care to reconnect the
ribbon cable if it has been disconnected.When power is
switched on,the displayshould light upimmediately with
meaningful letters or digits.
Settings
Set Units. Use to select volume units. Use to
select the particular unit desired (gallons, liters, etc.).
Then use to switch to time units. Again, select the
one desired.
Set Time Period. This is the monitoring period at the
endof which theunit willalarm iftotal flowhas exceeded
its setting.To set this monitoring period in hours, use the
and keys.The digit which is underlined is the one
being set. Use the to increase it.The moves one
digit to the left. Note that if the digit to the right is set to
“9”, the digit to the left will only go to“3”.This is because
48 is the maximum setting allowed.
Set Alarm Point. This is the maximum total flow al-
lowed in the time period set above.Use the same proce-
dure as above to set this value, up to nine digits. The
units are as shown (previously chosen).
Set K-Factor. The unit will not function properly until
this number is entered.It is simply the number of pulses
which the flow meter or flow sensor puts out per gallon
of liquid. It is marked on the Model/Serial tag of
SeaMetrics flow meters and flow sensor fittings. On
Caution: When the control is
powered up,relay or analog out-
puts may be present. If this
could be a hazard, wait to make
external connections until pro-
gramming is complete.
2 of 4
!
SETTINGSOPERATION MODE
SET
SET
SET
SET
SET
SET
SET
SET
Time Period:
12 HOURS
Alarm Point:
1234 GAL
TO CLEAR TOTAL
PRESS UP & LEFT
SET 20mA RATE
0.00 GPM
return to
operation mode
Flow
Monitor
SET PULSE OUT
123 GAL
SET K-FACTOR
123.456
GAL
MINUTE
Units
0:00:00
0 GAL
ELAPSED
0 GPM
0 GAL
Displays