
Operating
instructions
NLSW®45-3 Ex SIL2
+49 2058 2044 - info@seikom-electronic.com - www.seikom-electronic.com
b)
Connect the PLC or control unit to relay output A and B (green) using the terminals
supplied. Please note the NO/NC contact assignment and circuit.
c)
Set the "Sensitivity" potentiometer (dark blue) for both channels to the left stop
(insensitive).
d)
Set the "Start-up bypass" potentiometer (orange) to the desired start-up bypass time
approx. 5 s ... 60 s (left stop approx. 5 s/ right stop approx. 60 s) for both sensors.
e)
Apply mains voltage (red); the green LEDs light up. The device is ready for operation
within 2 seconds.
f)
The yellow LEDs light up (briefly) and go out again as soon as the set start-up bridging
time has elapsed. The relays are energized during this time.
g)
Switch on the airflow generator.
h)
Before setting the switching points, the device should run for at least 2 minutes under
operating conditions (with flow). The switching point setting at low flow rates requires a
sensitive setting on the potentiometer.
i)
Slowly turn the "Sensitivity" potentiometer for channel A (dark blue) to the right until the
yellow LED lights up and the output relay is energized. To achieve stable switching
conditions, you should turn slightly beyond the switching point. Set the same switching
ratio for channel B.
Note: Depending on the installation position and air flow situation in the duct, small
switching differences between duct A and duct B are normal.
j)
If the start-up bypass is preset, do not make this sensitivity setting until the start-up
bypass has expired and the yellow LED has gone out.
k)
To check the flow monitoring, reduce or switch off the flow generation. The yellow LEDs
go out and the output relays de-energize.
The device is now set to monitoring function. Preset values of the
NLSW45-3 Ex SIL2:
▪
The switching hysteresis is fixed.
▪
The switching delay is 0.2 s as standard.
▪
The start-up delay is adjustable from 5 s to 60 s as standard.
5.5
Switching point adjustment
The relationship between air velocity and change in resistance is not linear. In the lower range
(small flows), the change in resistance is very large. In the upper range, the change in resistance is
always smaller for the same flow changes. When setting the switching point, it should therefore be
noted which change is to be monitored, as different settings have certain disadvantages. The
following requirements should be observed:
Small flow change in the high flow velocity range: The switching point must be selected very
close to the measured value of the normal flow, as the measured value change is very small when
the flow changes. As the temperature compensation has a certain delay compared to the actual
temperature change, such a switching point setting is only possible for applications with slow
temperature changes.
Small flow change in the low flow velocity range: The switching point can be selected with a
greater distance to the measured value of the normal flow, as the measured value change is large
when the flow changes. A change in temperature has no effect on the switching behavior.