manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Seikom Electronic
  6. •
  7. Measuring Instrument
  8. •
  9. Seikom Electronic NLSW45-6 User guide

Seikom Electronic NLSW45-6 User guide

Setting the switching point
The relationship between air velocity and impedance change is non linear. In the lower range of flow velocity, the change of
impedance is very large. In the upper range of flow velocity, identical changes in flow velocity result in increasingly smaller
impedance changes. If the switching point is set, it is important to note what change is to be monitored because different settings
have certain disadvantages.
Note the following requirements
Small flow change in high flow velocity range: The switching point must be selected very close to the normal flow reading
since flow changes only lead to a very small change in the measured value. Since temperature compensation takes place with certain
delay after the actual temperature change has occurred, this switching point setting is only suitable for the applications which have
slow temperature changes in the medium.
Small flow change in low flow velocity range: The switching point can be selected at a greater interval from the normal flow
reading because a change in flow velocity causes a very large change in the measured value. A temperature change has no effect on
switching behaviour.
Large change in flow rate:
A Yes/NO statement is usually required here (e.g. fan running or fan stationary). You can therefore select a safety clearance which is
so large that neither temperature changes nor turbulence may have an affect on switching behaviour.
Assembly
The NLSW45-6 can be mounted on a top-hat rail to DIN EN 50022-35 using bolts or a quick-release clamp.
If the unit is exposed to major vibrations, it is advisable to mount it on a rubber-metal vibration damper.
Commissioning
Connection and commissioning has to be done by appropriate personnel! Please attend the following steps during assembling and
connecting:
1. Connect the appropriate sensor to the appliance.
2. Set the “Sensitivity" potentiometer to minimum sensitivity.
3. Set the "start-up break“ potentiometer to the needed time (approx. 5-60s)
4. Connect the power supply; the appliance is operational within 2 seconds. The green LED lights up.
5. The yellow LED lights up briefly and turns off after the start-up break time.
6. Switch on the flow generator.
7. Slowly turn the "Sensitivity" potentiometer to maximum until the yellow LED has just lightened up. To attain stable
switching behaviour, turn the potentiometer slightly past this switching point. Do not make this adjustment until the
yellow LED has gone out!
8. To check the monitoring device, turn off the flow. The yellow LED turns off and the relay connects.
Attention: Pay attention to the connection diagram and be aware of using the correct voltage!
What to do if the monitoring device does not work properly
Problem
cause
sollution
device does not work in any way
no or wrong suplly voltage
check supply voltage and connection
device does not recognice flow
sensor is not installed properly
check the sensor's installation
flow is out of range
change the tube's diameter
device reacts in a different way
sensor is highly polluted
maintain the sensor
device reacts in fast media tepmerature
changes
temperature gradient is out
of range
check the temp. Gradient of your
installation
If you have any other questions, feel free to contact us.
Airflow monitoring
Installation and operating instruction
NLSW45-6 and NLSW45-6.1
Our products correspond to the requirements of the European guidelines
WEEE 2012/19/EU - RoHS 2011/65/EU
Mistakes and misprints are not to be excluded. All information „without guarantee“. 03/2022
General Information
The NLSW45-6 monitors gaseous media with tamperatures in the range of -20 to 250°C and up to 400°C with F8/400.
The sensor is watched for short-circuit and loss of connection. The start-up delay and the switching point is settable step-
less. The NLSW45-6 is used in combination with the sensor series F8. The compensation of different temperatures
keeps the switching point constant.
Measuring principal
A temperature-sensitive resistor is heated according to the calorimetric measuring principle. The temperature-sensitive resistor is
heated by a second resistor. A flow dissipates heat from the measuring resistor, causing the resistor’s temperature to fall and thus a
change of impedance. This temperature change is evaluated. Since both the velocity and the temperature of the flowing medium
affect the dissipated heat, a relationship must be created between flow and temperature. For this purpose, a second temperature-
sensitive resistor is located next to the first one. The second measuring resistor is not heated and is only used for the temperature
measurement.
Airflow > / = switch point Switching output is energised Yellow LED “Airflow“ switch on
Airflow < switch point Switching output isn’t energised Yellow LED “Airflow“ switch off
Technical Data
Type
NLSW45-6 –NLSW45-6.1
NLSW45-6 –NLSW45-6.1
Article-No.
80502 –80502/400°C
81504 –81504/400°C
Operating Voltage
24V AC/DC
230V AC 50/60Hz
Voltage tolerance
± 5%
± 6%
Over voltage category
||
||
Signal lamp, voltage
Green LED
Green LED
Power consumption
3VA/W
4,5VA
Ambient temperature
-20…+50°C
-20…+50°C
Switching output
Relay, 1 change-over contact
Relay, 1 change-over contact
Relay output
Minimum switching load
250VAC, 8A, 2kVA
10mA / 5V DC
250VAC, 8A, 2kVA
10mA / 5V DC
Signal lamp, airflow
Yellow LED
Yellow LED
Atart up delay
selectable, 2s-60s
selectable, 2s-60s
Signal lamp, start up delay
-
-
Media temperature range NLSW45-6
Media temperature range NLSW45-6.1
-20…+250°C
-20…+400°C
-20…+250°C
-20…+400°C
Switching point adjustment
With potentiometer
With potentiometer
Airflow range NLSW45-6
Airflow range NLSW45-6.1
0.1-30m/s
0.1-20m/s
0.1-30m/s
0.1-20m/s
Measuring probes NLSW45-6
Measuring probes NLSW45-6.1
F8, F8.1, F8.2, F8.3
F8/400°C, F8.1/400°C,
F8.2/400°C, F8.3/400°C
F8, F8.1, F8.2, F8.3
F8/400°C, F8.1/400°C
F8.2/400°C, F8.3/400°C
Electrical connection
10 terminals, 2.5mm²
10 terminals, 2.5mm²
protection category, housing
IP40
IP40
protection category, terminals
IP20
IP20
contamiation class
2
2
Housing dimensions
L=120mm, W=45mm, H73mm
L=120mm, W=45mm, H73mm
Prüfzeichen
CE
Installation Instruction
Before setting up the switching point, the device should have been active for at least 2 minutes in normal conditions. To set up the
switching point please attend the following steps:
-The sensors tip should be placed in the duct’s middle and has to be flowed around completely by the medium.
-The flow in vertical-ducts needs to be upwards.
-To assure maximum reliability the sensor needs a length of the inlet path of 5xD (inside pipe diameter) and 3xD (inside
pipe diameter) of the outlet path.
-The sensor is to be mounted only with its own hex-head screw.
-The sensor must be connected to the evaluation unit as described in its manual. Incorrect connection leads to
malfunctioning and can destroy both!
-If the sensor’s cable is laid in a conduit with other live cables (motor-, solenoid valve-cables, …) we recommend
shielding it.
-If the length of the cable needs to be changed it needed to be done with a.w.g. 16 (1.5mm²) and must not be longer than
20m!
Maintenance information
In order to avoid malfunction the sensor should be maintained in regular distances according to its pollution. Cleaning the sensor pay
attention to following steps:
-Dismantle the sensor.
-Insert the sensor in slightly warm and soaped water carefully for about 10 minutes.
-Carefully rinse off the airflow sensor with lukewarm water.
-Assemble the airflow sensor.
Attention: Do not use screwdrivers or equal to clean the sensor!
Attention!!
Connection and commissioning must be performed by properly authorized and qualified personnel!
Connection to mains supply (L, N) must be made by means of a protected isolating switch with the usual fuses.
As a matter of principle, the General VDE Regulations must be complied with (VDE 0100, VDE 0113, VDE 0160). If
the potential-free contact is connected to an extra-low safety voltage, sufficient insulation must be provided for
the connecting cables up to the terminal, since otherwise the double insulation to the mains voltage side may be
impaired. The current load capacity of the potential-free contact is limited to 10 A. Therefore, the electrical
circuit of the potential-free contact must be protected by a 10.3 a fuse.
Electrical connection
Core colours: BN=brown BK=black BU=blue

This manual suits for next models

1

Other Seikom Electronic Measuring Instrument manuals

Seikom Electronic NLSW45-5 User manual

Seikom Electronic

Seikom Electronic NLSW45-5 User manual

Seikom Electronic NLSW 2a User manual

Seikom Electronic

Seikom Electronic NLSW 2a User manual

Seikom Electronic 77029 User guide

Seikom Electronic

Seikom Electronic 77029 User guide

Seikom Electronic NLSW 45-4 User manual

Seikom Electronic

Seikom Electronic NLSW 45-4 User manual

Seikom Electronic NLSW45-6 User manual

Seikom Electronic

Seikom Electronic NLSW45-6 User manual

Seikom Electronic F3 Ex SIL1 Series User manual

Seikom Electronic

Seikom Electronic F3 Ex SIL1 Series User manual

Seikom Electronic NLSW2aS3 User manual

Seikom Electronic

Seikom Electronic NLSW2aS3 User manual

Seikom Electronic NLSW45-4 User guide

Seikom Electronic

Seikom Electronic NLSW45-4 User guide

Seikom Electronic RLSW 7 User manual

Seikom Electronic

Seikom Electronic RLSW 7 User manual

Seikom Electronic RLSW 8 LCD User manual

Seikom Electronic

Seikom Electronic RLSW 8 LCD User manual

Seikom Electronic NLSW2aAEG User manual

Seikom Electronic

Seikom Electronic NLSW2aAEG User manual

Seikom Electronic RLSW 5A User manual

Seikom Electronic

Seikom Electronic RLSW 5A User manual

Seikom Electronic F3.xEx Series User manual

Seikom Electronic

Seikom Electronic F3.xEx Series User manual

Seikom Electronic RLSW4 User manual

Seikom Electronic

Seikom Electronic RLSW4 User manual

Seikom Electronic NLSW75-AEx (Gg) User manual

Seikom Electronic

Seikom Electronic NLSW75-AEx (Gg) User manual

Seikom Electronic NLSW45-3Ex User guide

Seikom Electronic

Seikom Electronic NLSW45-3Ex User guide

Seikom Electronic RLSW4 User manual

Seikom Electronic

Seikom Electronic RLSW4 User manual

Seikom Electronic NLSW 45-3 SIL2 User manual

Seikom Electronic

Seikom Electronic NLSW 45-3 SIL2 User manual

Seikom Electronic NLSW 45-3 Ex SIL2 User manual

Seikom Electronic

Seikom Electronic NLSW 45-3 Ex SIL2 User manual

Seikom Electronic NLSW45-3Ex User manual

Seikom Electronic

Seikom Electronic NLSW45-3Ex User manual

Seikom Electronic NLSW 45-3 SIL1 User manual

Seikom Electronic

Seikom Electronic NLSW 45-3 SIL1 User manual

Popular Measuring Instrument manuals by other brands

entegris InVue NT4400 user guide

entegris

entegris InVue NT4400 user guide

MTE HYDROCAL 1001 Plus Installation and operation manual

MTE

MTE HYDROCAL 1001 Plus Installation and operation manual

Akai X-V Service manual

Akai

Akai X-V Service manual

Siemens LDS 6 Compact operating instructions

Siemens

Siemens LDS 6 Compact operating instructions

Truvelo ProLaser 4 Operator's manual

Truvelo

Truvelo ProLaser 4 Operator's manual

Stanley TLM160 user manual

Stanley

Stanley TLM160 user manual

Casella USA CEL 240 Series Operator's manual

Casella USA

Casella USA CEL 240 Series Operator's manual

Weidmann InsuLogix T product manual

Weidmann

Weidmann InsuLogix T product manual

Apera Instruments SX811-SS instruction manual

Apera Instruments

Apera Instruments SX811-SS instruction manual

SRM B38 technical information

SRM

SRM B38 technical information

F&F LE-03 quick start guide

F&F

F&F LE-03 quick start guide

Bosch Denoxtronic Set PC-LD Original instructions

Bosch

Bosch Denoxtronic Set PC-LD Original instructions

Prodigit 3270 Series Operation manual

Prodigit

Prodigit 3270 Series Operation manual

Associated 12-1015 rev-B user manual

Associated

Associated 12-1015 rev-B user manual

GE DINAMAP ProCare Service manual

GE

GE DINAMAP ProCare Service manual

PTC Instruments 511A-Type A manual

PTC Instruments

PTC Instruments 511A-Type A manual

Magnetrol VIZUAL Installation and operating manual

Magnetrol

Magnetrol VIZUAL Installation and operating manual

SICK FLOWSIC30 operating instructions

SICK

SICK FLOWSIC30 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.