SICK TBS User manual

OPERATING INSTRUCTIONS
TBS
Temperature Switch
Temperaturschalter
Operating instructions
Betriebsanleitung

GB
D
Prior to starting any work, read the operating instructions!
Keep for later use!
Declarations of conformity can be found online at www.sick.com.
Vor Beginn aller Arbeiten Betriebsanleitung lesen!
Zum späteren Gebrauch aufbewahren!
Konformitätserklärungen nden Sie online unter www.sick.de.
Operating instructions model TBS Page 4 - 29
Betriebsanleitung Typ TBS Seite 30 - 55

8014826/19ZH/2020-12-01 © SICK AG • Germany • All rights reserved • Subject to change without notice 3
Operating Instructions TBS
ContentsContents
Contents Page 4-29 GB
1. General information 4
2. Safety 6
3. Specications 9
4. Design and function 15
5. Transport, packaging and storage 16
6. Commissioning, operation 16
7. Maintenance and cleaning 26
8. Faults 27
9. Dismounting, return and disposal 29
Inhalt Seiten 30-55 DE
1. Allgemeines 30
2. Sicherheit 32
3. Technische Daten 35
4. Aufbau und Funktion 41
5. Transport, Verpackung und Lagerung 42
6. Inbetriebnahme, Betrieb 42
7. Wartung und Reinigung 52
8. Störungen 53
9. Demontage, Rücksendung und Entsorgung 55

4 © SICK AG • Germany • All rights reserved • Subject to change without notice 8014826/19ZH/2020-12-01
Operating Instructions TBS
1. General information
The temperature switch described in the operating instructions has been designed and manufactured using
state-of-the-art technology. All components are subject to stringent quality and environmental criteria during
production. Our management systems are certied to ISO 9001 and ISO 14001.
These operating instructions contain important information on handling the instrument. Working safely
requires that all safety instructions and work instructions are observed.
Observe the relevant local accident prevention regulations and general safety regulations for the
instrument's range of use.
The operating instructions are part of the product and must be kept in the immediate vicinity of the instru-
ment and readily accessible to skilled personnel at any time.
Skilled personnel must have carefully read and understood the operating instructions prior to beginning any
work.
The manufacturer's liability is void in the case of any damage caused by using the product contrary to its intended
use, non-compliance with these operating instructions, assignment of insufciently qualied skilled personnel or
unauthorised modications to the instrument.
The general terms and conditions contained in the sales documentation shall apply.
Subject to technical modications.
Further information:
- Internet address: www.sick.com
- Relevant product information: 8014742
1. General information

8014826/19ZH/2020-12-01 © SICK AG • Germany • All rights reserved • Subject to change without notice 5
Operating Instructions TBS
1. General information
The temperature switch described in the operating instructions has been designed and manufactured using
state-of-the-art technology. All components are subject to stringent quality and environmental criteria during
production. Our management systems are certied to ISO 9001 and ISO 14001.
These operating instructions contain important information on handling the instrument. Working safely
requires that all safety instructions and work instructions are observed.
Observe the relevant local accident prevention regulations and general safety regulations for the
instrument's range of use.
The operating instructions are part of the product and must be kept in the immediate vicinity of the instru-
ment and readily accessible to skilled personnel at any time.
Skilled personnel must have carefully read and understood the operating instructions prior to beginning any
work.
The manufacturer's liability is void in the case of any damage caused by using the product contrary to its intended
use, non-compliance with these operating instructions, assignment of insufciently qualied skilled personnel or
unauthorised modications to the instrument.
The general terms and conditions contained in the sales documentation shall apply.
Subject to technical modications.
Further information:
- Internet address: www.sick.com
- Relevant product information: 8014742
Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result in serious injury or death, if not
avoided.
CAUTION!
... indicates a potentially dangerous situation that can result in light injuries or damage to
equipment or the environment, if not avoided.
Information
… points out useful tips, recommendations and information for efcient and trouble-free
operation.
CAUTION!
... indicates a potentially dangerous situation that can result in burns, caused by hot surfaces
or liquids, if not avoided.
Abbreviations
L+Positive power terminal
MNegative power terminal
QAAnalogue output
C/Q1:Switching output 1
For variants with IO-Link: IO-Link communication/switching output 1
Q2Switch point 2
SP1:Switching point 1
SP2: Switching point 2
MBA Start of measuring range
MBE End of measuring range
1. General information

6 © SICK AG • Germany • All rights reserved • Subject to change without notice 8014826/19ZH/2020-12-01
Operating Instructions TBS
2. Safety
WARNING!
Before installation, commissioning and operation, ensure that the appropriate temperature
switch has been selected in terms of measuring range, design and specic measuring
conditions.
Non-observance can result in serious injury and/or damage to the equipment.
WARNING!
Observe the working conditions in accordance with chapter 3 „Specications".
Further important safety instructions can be found in the individual chapters of these
operating instructions.
2.1 Intended use
The temperature switch is used to convert temperature into an electrical signal indoors and outdoors.
The instrument has been designed and built solely for the intended use described here, and may only be
used accordingly.
The technical specications contained in these operating instructions must be observed. Improper handling
or operation of the temperature switch outside of its technical specications requires the instrument to be
taken out of service immediately and inspected by an authorized SICK service engineer.
The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use.
2. Safety

8014826/19ZH/2020-12-01 © SICK AG • Germany • All rights reserved • Subject to change without notice 7
Operating Instructions TBS
2.2 Personnel qualication
WARNING!
Risk of injury should qualication be insufcient!
Improper handling can result in considerable injury and damage to equipment.
The activities described in these operating instructions may only be carried out by skilled
personnel who have the qualications described below.
Skilled personnel
Skilled personnel are understood to be personnel who, based on their technical training, knowledge of
measurement and control technology and on their experience and knowledge of country-specic regulations,
current standards and directives, are capable of carrying out the work described and independently recogni-
zing potential hazards.
Special operating conditions require further appropriate knowledge, e.g. of aggressive media.
2.3 Special hazards
WARNING!
For hazardous media such as oxygen, acetylene, ammable or toxic gases or liquids,
and refrigeration plants, compressors, etc., in addition to all standard regulations, the
appropriate existing codes or regulations must also be followed.
WARNING!
Residual media in the dismounted temperature switch can result in a risk to persons, the
environment and equipment.
Take sufcient precautionary measures.
2. Safety

8 © SICK AG • Germany • All rights reserved • Subject to change without notice 8014826/19ZH/2020-12-01
Operating Instructions TBS
2.4 Labelling / Safety marks
Product label
If the serial number becomes illegible (e.g. due to mechanical damage or overpainting), traceability will no
longer be possible.
Explanation of symbols
General danger symbol
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant European directives.
Electrical connection
Analog output signal
Supply voltage
Serial number
Part number
Temperature range
Max. process pressure at room temperature
2. Safety

8014826/19ZH/2020-12-01 © SICK AG • Germany • All rights reserved • Subject to change without notice 9
Operating Instructions TBS
3. Specications
Features
Measuring range –20 °C ... + 80 °C (–20 °C ... + 120 °C optional)
Sensor element Pt1000, 2-wire, class A according to IEC 60751
Output signals 2x PNP
1 x PNP + 4...20 mA
1 x PNP + 0...10 V
2 x PNP + 4...20 mA
2 x PNP + 0...10 V
2 x NPN
1 x NPN + 4...20 mA
1 x NPN + 0...10 V
2 x NPN + 4...20 mA
2 x NPN + 0...10 V
IO-Link, revision 1.1 (option) (IO-Link is optionally available for all output signals. With the IO-Link option,
switching output SP1 is always PNP.)
Switching points Type: transistor switching output PNP or NPN
Quantity: 1 or 2
Function: normally open / normally closed; windows- and hysteresis function freely adjustable
Contact rating: supply voltage L+ - 1 V [V DC]
Max. switching current: without IO-Link 250 mA /with IO-Link SP1 max. 100 mA, SP2max. 250 mA
Switching delay: 0 ... 50 s (adjustable)
Individually adjustable via control buttons
Setting accuracy: 0.1 °C
Temperature offset ± 3 °C
Scaling of temperature
range
Zero: max. +25 % of span
Full scale: max. -25 % of span
Display 14-segment LED, blue, 4-digits, height 9 mm
Display electronically turnable by 180°
Update: 200 ms
Rotatable housing Display against housing with electrical connection: 330°
Housing against process connection: 320°
3. Specications

10 © SICK AG • Germany • All rights reserved • Subject to change without notice 8014826/19ZH/2020-12-01
Operating Instructions TBS
3. Specications
Performance
Accuracy of sensor element ≤ ± (0.15 °C + 0.002 |t|) 1)
Accuracy of switching output ≤ ± 0.8 % of span
Display accuracy ≤ ± 0.8 % of span ± 1 digit
Accuracy of optional analog output ≤ ± 0.5 % of span
Response time t50 ≤ 5 s
Response time t90 ≤ 10 s
1) |t| is the absolute value of the temperature in °C
2) Depending on sensor conguration, according to IEC 60751
Mechanics/electronics
Process connection G 1/4 A according to DIN 3852-E
G 1/2 A according to DIN 3852-E
Compression tting, G 1/2 A (for measuring range –20 °C ... + 120 °C)
Compression tting, G 1/4 A (for measuring range –20 °C ... + 120 °C)
1/4’’ NPT
1/2’’ NPT
Insertion lengths/diameter of probe 25 mm / 6 mm (not suitable for measuring range –20 °C ... + 120 °C)
50 mm / 6 mm (not suitable for measuring range –20 °C ... + 120 °C)
100 mm / 6 mm
150 mm / 6 mm
250 mm / 6 mm
350 mm / 6 mm
Wetted parts Stainless steel 1.4571 (AISI 316Ti)
Maximum process pressure 1) 150 bar
Compression tting mx. 50 bar, at 120 °C
Housing material Lower body: stainless steel 1.4301 (AISI 304)
Plastic head: PC + ABS
Buttons: TPE-E
Display window: PC
Enclosure rating 2) IP 65 and IP 67
Maximum ohmic load RA< 0.5 kΩ for output signal 4 mA ... 20 mA
> 10 kΩ for output signal 0 V ... 10 V
≤ 100 kΩ (switching outputs)

8014826/19ZH/2020-12-01 © SICK AG • Germany • All rights reserved • Subject to change without notice 11
Operating Instructions TBS
3. Specications
Electrical connection Round connector M12 x 1, 4-pin
Round connector M12 x 1, 5-pin (only for variants with two switching outputs
and one analog output)
Supply voltage 15 V DC ... 35 V DC
Maximum current consumption 45 mA (for congurations without analog signal output)
70 mA (for congurations with analog signal output)
IO-Link option causes a deviating current consumption.
Total current consumption without IO-Link max. 600 mA / with IO-Link 450 mA (incl. switching current)
Electrical safety Protection class: III
Isolation voltage: 500 V DC
Overvoltage protection: 40 V DC
Short-circuit protection: QA, Q1, Q2towards M
Reverse polarity protection: L+towards M
RoHS l
1) At room temperature and when connected through thread.
2) Enclosure rating IP per IEC 60529. The enclosure rating classes specied only apply while the thermometer is connected with female
connectors that provide the corresponding enclosure rating.

12 © SICK AG • Germany • All rights reserved • Subject to change without notice 8014826/19ZH/2020-12-01
Operating Instructions TBS
3. Specications
Ambient data
Ambient temperature –20 °C ... + 80 °C
Storage temperature –20 °C ... + 80 °C
Relative humidity 45 % ... 75 %
Dimensional Drawings
84
(3.31)
35
(
1.38)
12
(0.47)
DIN 3852-E
G 1/4 A
insertion length L
6
(
0.24)
38
(
1.50)
36
(1.42)
37
(1.46)
M
12
x 1
(1.16)
29.5
27
(1.06)
All dimensions in mm (inch)
TBS with connection G 1/4 A according to
DIN 3852-E
38
(
1.50)
82
(3.23)
35
(
1.38)
DIN 3852-E
G 1/2 A
14
(0.55)
insertion length L
6
(
0.24)
36
(1.42)
35
(1.38)
M
12
x 1
(1.16)
29.5
27
(1.06)
All dimensions in mm (inch)
TBS with connection G 1/2 A according to
DIN 3852-E
3. Specications

8014826/19ZH/2020-12-01 © SICK AG • Germany • All rights reserved • Subject to change without notice 13
Operating Instructions TBS
3. Specications
82
(3.23)
13
(0.51)
35
(
1.38)
6
(
0.24)
38
(
1.50)
36
(1.42)
35
(1.38)
1/4" NPT
insertion length L
M
12
x 1
(1.16)
29.5
27
(1.06)
All dimensions in mm (inch)
TBS with connection 1/4’’ NPT
35
(
1.38)
19
(0.75)
insertion length L
6
(
0.24)
36
(1.42)
1/2" NPT
35
(1.38)
82
(3.23)
38
(
1.50)
M
12
x 1
(1.16)
29.5
27
(1.06)
All dimensions in mm (inch)
TBS with connection 1/2’’ NPT

14 © SICK AG • Germany • All rights reserved • Subject to change without notice 8014826/19ZH/2020-12-01
Operating Instructions TBS
3. Specications
29,5
(1.16)
M12x1
14
(0.55)
27
(1.06)
27
(1.06)
35
(
1.38)
36
(1.42)
82
(3.23)
Einbaulänge L
44
(1.73)
14
(0.55)
6
(0.24)
G 1/2 A
DIN 3852-A
35
(1.38)
38
(
1.50)
All dimensions in mm (inch)
TBS with compression tting, G1/2 A
M12 x 1
29.5
(1.16)
27
(1.06)
14
(0.55)
19
(0.75)
35
(
1.38)
38
(
1.50)
36
(1.42)
6
(
0.24)
82
(3.23)
insertion length L
G 1/4 A
DIN 3852-A
04
)75.1(
12
(0.47)
35
(1.38)
All dimensions in mm (inch)
TBS with compression tting, G 1/4 A

8014826/19ZH/2020-12-01 © SICK AG • Germany • All rights reserved • Subject to change without notice 15
Operating Instructions TBS
4. Design and function
4.1 Description
By means of a measuring element (Pt1000) and by supplying power, the prevailing temperature is conver-
ted into a switching signal or an amplied standardized electrical signal via the change in resistance of the
measuring element. This electrical signal varies in proportion to the temperature and can be evaluated
accordingly.
4.2 Scope of delivery
Cross-check scope of delivery with the delivery note.
4. Design and function

16 © SICK AG • Germany • All rights reserved • Subject to change without notice 8014826/19ZH/2020-12-01
Operating Instructions TBS
5. Transport, packaging and storage
5.1 Transport
Check the temperature switch for any damage that may have been caused by transport.
Obvious damage must be reported immediately.
5.2 Packaging
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport (e.g. change in installation site,
sending for repair).
5.3 Storage
Permissible conditions at the place of storage:
Storage temperature: -20 ... +80 °C
Humidity: 45 ... 75 % relative humidity
WARNING!
Before storing the instrument (following operation), remove any residual media. This is of
particular importance if the medium is hazardous to health, e.g. caustic, toxic, carcinogenic,
radioactive, etc.
6. Commissioning, operation
6.1 Mounting
Required tool: Open-ended spanner (spanner width 27)
The sealing faces at the temperature switch and the measuring point always have to be clean.
Only ever screw in, or unscrew, the instrument via the spanner ats. Never use the case as a working
surface.
5. Transport, packaging and storage / 6. Commissioning, ...

8014826/19ZH/2020-12-01 © SICK AG • Germany • All rights reserved • Subject to change without notice 17
Operating Instructions TBS
6. Commissioning, operation
The correct torque depends on the dimensions of the process connection and the sealing used
(form/material).
When screwing in, do not cross the threads.
The instrument must be grounded via the process connection.
Attach the electrical connector and screw it in hand-tight.
For high process or ambient temperatures appropriate care must be taken
to ensure that the housing temperature of the device (taken at the hexa-
gonal ats of the process connection) during permanent operation does
not exceed 80 °C.
The plastics housing of the TBS can be rotated against the stainless steel housing with the electrical connec-
tion. There is a perceptible stop/end position (in both directions). Under all circumstances the head must
not be rotated beyond these stops/end positions.
Seal
Correct sealing of the process connections with straight threads must be made using
suitable at gaskets, sealing rings or prole sealings.The sealing of tapered threads
(e.g. NPT threads) is made by providing the thread with additional sealing material such
as, for example, PTFE tape (EN 837-2).

18 © SICK AG • Germany • All rights reserved • Subject to change without notice 8014826/19ZH/2020-12-01
Operating Instructions TBS
Compression tting
1. Screw the compression tting (1) into the process connection and tighten.
2. Insert the tapered side of the ferrule (2) into the tting and screw on the
union nut (3) hand-tight.
3. Insert the temperature switch into the tting and maintain it at the
required immersion depth. Tighten the union nut (3) with approx. 50 Nm.
4. Optional
Check the assembly: Loosen the union nut. The ferrule is rmly connected
to the sensor tube.
6. Commissioning, operation

8014826/19ZH/2020-12-01 © SICK AG • Germany • All rights reserved • Subject to change without notice 19
Operating Instructions TBS
Making the electrical connection
The instrument must be earthed via the process connection.
The power supply for the temperature switch must be made via an energy-limited electrical circuit in
accordance with section 9.3 of UL/EN/IEC 61010-1 or an LPS to UL/EN/IEC 60950-1 or class 2 in
accordance with UL1310/UL1585 (NEC or CEC).
The power supply must be suitable for operation above 2,000 m should the temperature switch be
used at this altitude.
For cable outlets, make sure that no moisture enters at the cable end.
Connection diagrams
Round connector M 12 x 1, 4-pin
Assignment
L+M QAC/Q1 Q2
13242
Round connector M 12 x 1, 5-pin
Assignment
L+M QAC/Q1Q2
13542
6. Commissioning, operation

20 © SICK AG • Germany • All rights reserved • Subject to change without notice 8014826/19ZH/2020-12-01
Operating Instructions TBS
6. Commissioning, operation
6.2 Operating modes
System start
Display is fully activated for 2 seconds.
When the temperature switch is powered up within the range of the hysteresis, the output switch is set
to "not active" by default.
Display mode
Normal operation, display temperature value
Programming mode
Setting the parameters
6.3 Keys and functions
The temperature switch has two operating modes, the display mode and the programming mode. The selected
operating mode determines the respective function of the key.
Jumping in the programming mode
Keep the "MENU" key pressed for approx. 5 seconds. If the password is set to
≠
0000
, a
password will be requested rst-hand.
If authentication is successful, then it enters the
programming mode, otherwise it reverts to display mode.
Returning to the display mode
Simultaneous pressing of both keys.
MENU
INFO MENU
Table of contents
Languages:
Other SICK Switch manuals

SICK
SICK L25 User manual

SICK
SICK T4000 Direct Unicode User manual

SICK
SICK WSU 26/2 Parts list manual

SICK
SICK IN4000 Direct User manual

SICK
SICK PBS Series User manual

SICK
SICK ES11 User manual

SICK
SICK ES21 M12 contact User manual

SICK
SICK MLP1 User manual

SICK
SICK i17S User manual

SICK
SICK i12S User manual
Popular Switch manuals by other brands

Panasonic
Panasonic AV-UHS500P operating instructions

Quirky
Quirky R-INS-TAPT-WH02 installation instructions

Compex
Compex SAS2224 Quick install guide

Dell EMC
Dell EMC S4148U-ON Configuration and deployment guide

Leviton
Leviton 47611-8PT Instructions for use

ZyXEL Communications
ZyXEL Communications ONU-6100B-22 Specifications