manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Controllers
  8. •
  9. Siemens DOL Series User manual

Siemens DOL Series User manual

Direct-On-Line and Automatic Star – Delta Starter
Our new series of DOL and ASD starters complies to latest
standard IS/IEC 60947-4-1
Operating Instructions
Selection:
• ReferTable1forrecommended
selectionofDOLStartersand
Table2forASDStarters.
• DOLandASDStartersare
suppliedwithoutrelays.Relays
aretobettedatsite.
• Selectthesuitablerangeof
relayasperrecommendation
giveninTable1and2.
• Selectback-upfuserating
fordifferentstartersfrom
theselectiontables.The
recommendationofthefuses
andfuseswitchesisaccording
toType-2co-ordinationasper
IS/IEC60947-4-1.
Inspection:
• Removethehousingcover.
• Checkthecoilvoltagessothat,
thecoilvoltagecorrespondsto
actualsupplyvoltage.
Fig.2Direct-On-LineStarter(DOL)
Fig.3AutomaticStarDeltaStarter
(ASD)
• Inspectinteriorforbreakage.
• Ifyoundaseriousdefect,do
notusetheproductbuthave
itcheckedbyanauthorized
Siemensdealeroran
electrician.
Installation:
• Assoonasyouopenthe
starter,youwillseeasticker
“K1BIRELAY”showingthe
locationatwhichtherelay
shouldbemounted.Refer
Table5fortheprocedureto
befollowedforfittingthe
relay.
• Completethewiringby
connectingthewireshaving
ferrules‘95’and‘96’.Wiring
shouldbeexactlyasperthe
circuitdiagramlabelshown
oninsideofthefrontcover.
• Backupfuseratingsandcable
sizesarealsorecommended
onthelabel.Alsoforyour
futurereference,spaceis
providedonthelabelinside
thefrontcovertowritethe
coilvoltageandtherelay
rangeselectedbyyou.
• Incaseofstartershaving
resettingcord,attachthe
resettingdeviceontheholes
providedontherelaysurface.
(ref.fig.4)Adjusttheend
oftheresetcordusingthe
adjustmentscrew(fig.4)so
thatclearancebetweenblue
knobandresetcordmetallic
endisabout2mm.
Fig.1NewseriesofStarters
Fordependableservice,itisofutmostimportancethatinstructionsgivenbelowarefollowedfor
selection,inspection,installation,commissioning,operationandmaintenance.
s
Hazardous Voltage can cause
Electric Shock and burns.
DisconnectPowerbeforeproceeding
withanyworkonthisequipment
Warning:
Removerequiredlengthof
insulationandusingthe
hardwareconnectedatthe
contactorterminals,fixthe
incomingandoutgoing
cables.
c. Incase,thepowerandcontrol
circuitsareofdifferent
voltages,connectthedesired
supplytothecontrolcircuit,
usingtheconnector.Follow
theinstructionsgivenon
wiringdiagramlabelstuckon
innersideoffrontcover.
d. Tightenthescrewsfirmly.
e. Checkthatthelineandmotor
connectionsaredoneexactly
asperwiringdiagrampasted
insidethefrontcover.
f. Removeanywirecutting
fallenintothestarter.
• Connectearthingconductorto
terminalsmarked
Commissioning:
Read the caution
note carefully before
commissioning.
• Removethefrontcover.
• BeforeswitchingON,re-check
externalconnections.
• Setoverloadrelayto0.58
timestheratedmotorcurrent.
• Setthedialofthetimer(fig.
7)toanapprox.valueof
startingtimeofyourmotor
(preferablymorethan6sec.).
• Star-DeltaTimersetting(for
ASDonly):
a. Firststartthemotorby
pressingthe‘ON’buttonas
indicatedinfig.8.
b. Measuretimetakenforitto
• Mountstarteronavertical
wall/platefreefrom
vibrations,withpropernuts
andbolts.Referfig.11for
mountingdimensions,and
alsofig.5forpermissible
displacement.
Fig.5 Maximumpermissible
displacementfromverticalplane
Fig.6Cableconnections
Fig.4ResetCordconnections
'Reset'
Cord
reachnearlyratedspeedor
steadystatecurrent(indicated
whenmotorhumreachesa
steadypitch).
c. Stopthemotor.Settimertothis
measuredvalue,byrotatingthe
dialshowning.7.
• Overloadrelaysetting:
a. Forcloserprotectionsetthe
overloadrelaytoactualline
current(DOL)oractualphase
current(ASD)asmeasuredby
anAmmeter.
• IntheabsenceofanAmmeter,
useprocedureasgivenbelow:
a. Startthemotorandletitrun
for½anhour.Thengradually
reducerelaysettingtillittrips.
Setrelayataslightlyhigher
valueofthissetting.
b.Allowresettimeofapprox.
4min.Presstheblueknobon
therelaycompletelytoreset
therelay.
c.Re-startmotoraftersome
time.Iftherelaydoesnottrip,
considerittobeproperlyset.
Ifittrips,followstepbwith
settingatalittlehighervalue
andrecheck.
d. Overloadrelaycharacteristics
giveninfig.10canbeusedto
estimatetheaveragetripping
timeatdifferentmultiplesof
setcurrent.
Caution:
• Switch off the starter and
disconnect the main supply
by switching off the main
switch before doing any
maintenance.
Screw for
adjustment
2
Fig.7TimerAdjustment
Dial
• Selectcorrectsizesofcableas
specifiedinselectionTable1
and2.
• Dependinguponlocation
ofincomingandoutgoing
cablesremovecorresponding
rubbergrommets.Ensuredust
proofingbyusingpropercable
gland.(fig.6)
a. Forcontactorsupto3TS36,
removeapprox.10mmof
insulationoftheconductor,
loosenterminalscrews
andpushcableendunder
theSIGUTterminalofthe
contactor.
b. Forcontactorsabove
3TS36,selectproperlugs
forconductortermination
dependinguponcablesize
specifiedinTable1and2.
H - Hand Reset
A - Auto Reset
Blue
Reset
Knob
• In case of DOL starters
under no circumstances
should the relay be set
higher than the rated
current on the motor name
plate.
• In case of ASD starters
under no circumstances
should the relay be set
higher than phase current
i.e. 0.58 times the rated
current on the motor
nameplate.
• Iftherelaytripsevenwhen
set at the rated motor
current the suitability of
the starter / relay for the
particular application should
be checked with the nearest
Siemens office.
Operating Characteristics:
Thegivencharacteristics
(fig.10)areaveragevaluesof
allrangesandsizesofbimetal
relaysandaremainlyintendedto
indicatetheinversetimecurrent
characteristicsofthesame.The
trippingtimesshownarefor
relaysstartingfromthecold
state.Atoperatingtemperatures
(heatedatratedcurrent)these
arereducedtoabout25%of
thevaluesobtainedfromthe
characteristics.
Operation:
• Forstartingthemotor,press
greenpushbutton,marked‘I’
(fig.8).
• Forstoppingthemotor,press
redpushbutton,marked‘O’
(fig.8).
• Incaseofhandresettype
overloadrelay,pressblue
pushbutton,marked‘R’(fig.
8)forresetting,aftertherelay
hastrippedduetooverload.
Inthiscaseyoucanrestart
themotoronlyifyouresetit.
• Incaseyouwantthestarter
tobein‘SelfReset’mode,
theblueknobonrelay(fig.
9)istobepressedand
rotatedinanticlockwise
direction;sothatitcomes
inposition‘A’,anditsedge
Fig.8Starterfrontview
Fig.9Relayfrontview
Fig.10Operatingcharacteristicsof3US5/6relays
Maintenance:
• Keeptheinteriordustfree.
• Re-tightenterminalscrews
fromtimetotime.
• Nomaintenanceisrequired
foroverloadrelayandpush
button.Donotopenthem.
• Blackeningofsilvercoated
/alloyedcontactsdoesnot
affectoperationallife.If
necessary,cleanthecontacts
ofcontactorwithCRC2-26.
Removeglobuleswith
scrapperorscrewdriverwith
minimumforce.Underno
circumstancesthecontact
shouldbefiledordressedas
itwillreducetheelectricallife
drastically.
• Ifthecontactorhums,clean
themagnetpolefaceswith
softcloth.
• Replacecontactsofthe
contactoriftheyare
severelypittedorwhen
only40%originalcontact
tipremains.Fordetailsof
contactormaintenancerefer
toour‘GuidetoContactor
Installation&Maintenance’.
'ON'
button
'OFF'
button
'RESET'
button
3
flushwiththerelaysurface.
Inthismodeeveniftherelay
tripsonoverload,itwillbe
automaticallyresetinmax.
4minutes.Themotorcanbe
restartedonlyaftertherelay
isreset.
3 US 5/6 3 US 5/6
Selection Table 1: Direct-On-Line Starters
Motor
Output
at 415V,
3ph, 50Hz
I()
4 Pole
motor
Size
DOL Starters Contactor RecommendedOver-load
Relay 50°C
Recommended Fuse-
Switch Recommended
Cu cable size
Type Reference1) Type Reference1) Type Range Type
Max. Backup
HRC Fuse
Rating
(kW/HP) (A) (A) (A) (mm2)
11/15 20.8 DOL-1 3TW7493-2A.. 3TS3400-0A.. 3US5200-2C8K 16-25 3KL815 50 6
15/20 28 DOL-2 3TW7494-2A.. 3TS3522-0A.. 3US5600-2D8K 20-32 3KL815 50 6
18.5/25 34 3TW7495-2A.. 3TS3622-0A.. 3US5600-2Q8K 25-36 3KL815 63 10
22/30 40
DOL-3
3TW7496-2A.. 3TS4722-0A.. 3US5800-2F8K 32-50 3KL821 80 16
30/40 53 3TW7497-2A.. 3TS4822-0A.. 3US5800-2T8K 40-57 3KL821 100 16
37/50 65 3TW7498-2A.. 3TS4822-0A.. 3US5800-2V8K 57-70 3KL822 125 25
45/60 78 DOL-6 3TW7499-2A.. 3TS5122-0A.. 3US5800-8Y8K 70-95 3KL822 125 35
55/75 96 3TW7590-2A.. 3TS5122-0A.. 3US5800-5C8K 85-105 3KL823 160 35
1)10thand11thplaceinthetypereferenceisforcoilvoltagecode,referTable3.
Selection Table 2: Automatic Star-Delta Starters
Motor
Output
at 415V,
3ph,
50Hz
I()
4 Pole
motor
line
current
I()
4 Pole
motor
phase
current
Size
ASD Starters Contactor
Main
Contactor
Star
Contactor
Delta
Recommended
Over-loadRelay50°C
Recommended
Fuse-Switch
Recommended
Cu cable size
Type
Reference1)
Type
Reference1)
Type
Reference1)
Type
Reference1) Type Range Type
Max.
Backup
HRC Fuse
Rating
Incoming
(from
supply)
Outgoing
(to
motor)
(kW/HP) (A) (A) (A) (mm2)(mm2)
22/30 40 23.2
ASD-2
3TE7493-2A… 3TS3522-0A.. 3TS3511-0A.. 3TS3511-0A.. 3US5600-2C8K 16-25 3KL815 50 16 10
30/40 53 30.6 3TE7494-2A… 3TS3522-0A.. 3TS3511-0A.. 3TS3511-0A.. 3US5600-2D8K 20-32 3KL815 63 16 10
37/50 65 37.5 3TE7495-2A… 3TS3622-0A.. 3TS3511-0A.. 3TS3611-0A.. 3US5600-2R8K 32-40 3KL821 80 16 10
45/60 78 45 ASD-3 3TE7496-2A… 3TS4722-0A.. 3TS3522-0A.. 3TS4722-0A.. 3US5800-2F8K 32-50 3KL821 100 35 16
55/75 96 55.4 3TE7497-2A… 3TS4822-0A.. 3TS3522-0A.. 3TS4822-0A.. 3US5800-2T8K 40-57 3KL821 100 35 25
1)10thand11thplaceinthetypereferenceisforcoilvoltagecode,referTable3.
4
Selection Table 3
Coil Voltage 10th - 11th digit in MLFB
24V B0
110V F0
230V P0
240V U0
415V R0
Allothervoltages Uponenquiry
Selection Table 4
Star-Delta Timer
Input Voltage MLFB
24/100-127V 3RP1576-1NQ308K
200-240V 3RP1576-1NM208K
380-440V 3RP1576-1NM208K
Timer to be selected according to contactor coil voltage.
Spares List
Type of spares MLFB
ON/OFFActuator 3SX155-21YA
ON/OFFContact(DOL2&ASD2) 3SX155-11YA
ResetcordforASD3 3UX1015
Accessoryfor3US58independent
mounting
3UX1421
ContactBlock(1NO) 3SB5420-0B
ContactBlock(1NC) 3SB5420-0C
ContactorSpareContactKit ReferSiemensPriceList
ElectronicStar-DeltaTimer ReferTable4
Relay ReferTable1&2
Contactor ReferTable1&2
Aux.contactblockfor3TS34 3TX4010-2A
Tightening Torque
DOL
& ASD
Starter
Incoming
terminal
Tightening
Torque
Outgoing
Terminal
Tightening
Torque
DOL1 M4 1.0-1.5Nm M4 1.0-1.5Nm
DOL2 M4 1.0-1.5Nm M5 2.5-3.0Nm
DOL3 M6 3.0-4.0Nm M5 2.5-3.0Nm
DOL6 M6 3.0-4.0Nm M5 2.5-3.0Nm
ASD2 M4 1.0-1.5Nm M4 1.0-1.5Nm
ASD3 M6 3.0-4.0Nm M6 3.0-4.0Nm
Cover xing torque 1.5-2.1Nm.
40
Table 5: Installation
Starter MLFB Mode of Relay
mounting Procedure
DOL1/2
3TW7493-2A..
Directmountingon
contactor
1. Unscrewcontactorterminalsandputtherelayterminalsundercontactorterminals.
3TW7494-2A.. 2. Engagetherelayhookincontactorslot.
3TW7495-2A.. 3. Pushtherelaytowardscontactorasmuchaspossible,sothattherelayedgeisush
withthecontactorribs.
ASD2
3TE7493-2A.. 4. Tightenthecontactorterminalscrews.
3TE7494-2A..
3TE7495-2A..
DOL3
3TW7496-2A..
Ontheterminal
carrier
1. Replacetheterminalsofrelaybythoseprovidedinthehardwarekitalongwiththe
starter.
3TW7497-2A.. 2. SeethediagramgivenintheOperatingInstructionsofaccessoryforindependent
mounting.
3TW7498-2A.. 3. Loosenthescrewsofaccessoryforindependentmounting.
ASD3
3TE7497-2A.. 4. Puttherelayterminalsbelowthepintypelugsofthecableterminations.
5. HoldtherelaythewayitisshownintheOperatingInstructionsofterminalcarrier
andengagetherelayhookintheslotoftheterminalcarrier.
6. Whentherelayedgeisushwithterminalcarrieredge,clamptherelaywithtermi-
nalcarrierusingtheclampsinthehardwarekit.
7. Tightentheterminalcarrierscrews.
DOL6
3TW7499-2A..
Directmountingon
contactor
1. Engagetherelayhookincontactorslot.
3TW7590-2A.. 2. Alignthecontactorterminalholestorelayterminalholes.
3. Fixtherelaytothecontactorusingthehardwarealreadyttedatthecontactor
terminals.
4. Fixtheterminalsprovidedalongwiththerelaytotheotherside(outgoingside)of
therelayandusethehardwareprovidedforcableconnections.
5
DOL 1/2
3TW7493-2A..
3TW7494-2A..
3TW7495-2A..
DOL 3
3TW7496-2A..
3TW7497-2A..
3TW7498-2A..
DOL 6
3TW7499-2A..
3TW7590-2A..
s
Fig. 11: Dimensional Details
6
ASD 2
3TE7493-2A..
3TE7494-2A..
3TE7495-2A..
ASD 3
3TE7496-2A..
3TE7497-2A..
7
Siemens Ltd.
XXX-XX-XXX-XXX
This replaces SGR-01-115-029
'Productdevelopmentisacontinuousprocess.Consequently
thedataindicatedinthisleaetissubjecttochangewithout
priornotice.ForlatestissuecontactourSalesOfce.'
A5E45312503A/AA
CustomerCareTollfreeno.1800220987Email:adscs.india@siemens.com
PLASTICS:Segregateaspermaterialtypeforrecycling
throughauthoriseddealer.
BecauseofthelonglifetimeofSiemensproductsthe
disposalguidelinesmaybereplacedbyothernational
regulationswhentakingtheproductoutofservice.
Thelocalcustomercareserviceisavailableatanytime
toanswerdisposal-relatedquestions
SiemensProductsareenvironmentfriendly,which
predominantlyconsistofrecyclablematerials.
Fordisposalwerecommenddisassemblingand
separationintofollowingmaterials:
METALS:SegregateintoFerrous&NonFerroustypesfor
recyclingthroughauthoriseddealer.
Disposal
AB

This manual suits for next models

7

Other Siemens Controllers manuals

Siemens SIRIUS 3RW30 User manual

Siemens

Siemens SIRIUS 3RW30 User manual

Siemens SQL36E series User manual

Siemens

Siemens SQL36E series User manual

Siemens ST950 User manual

Siemens

Siemens ST950 User manual

Siemens SIRIUS 3RW30 User manual

Siemens

Siemens SIRIUS 3RW30 User manual

Siemens GEB-1E Series User manual

Siemens

Siemens GEB-1E Series User manual

Siemens OZS164 series User manual

Siemens

Siemens OZS164 series User manual

Siemens AEROGYR RWI65.02 User manual

Siemens

Siemens AEROGYR RWI65.02 User manual

Siemens SIRIUS 3RA2110 Series User manual

Siemens

Siemens SIRIUS 3RA2110 Series User manual

Siemens 540-716 Service manual

Siemens

Siemens 540-716 Service manual

Siemens IQHeat User manual

Siemens

Siemens IQHeat User manual

Siemens i-3 User manual

Siemens

Siemens i-3 User manual

Siemens G2257 User manual

Siemens

Siemens G2257 User manual

Siemens 5WG1 536-1DB51 User manual

Siemens

Siemens 5WG1 536-1DB51 User manual

Siemens SITRANS VP300 User manual

Siemens

Siemens SITRANS VP300 User manual

Siemens SINAMICS G120 User manual

Siemens

Siemens SINAMICS G120 User manual

Siemens SIMATIC NET CP 1613 A2 User manual

Siemens

Siemens SIMATIC NET CP 1613 A2 User manual

Siemens RMU7 B Series User manual

Siemens

Siemens RMU7 B Series User manual

Siemens RVL481 User manual

Siemens

Siemens RVL481 User manual

Siemens PS 307 6ES7307-1BA01-0AA0 User manual

Siemens

Siemens PS 307 6ES7307-1BA01-0AA0 User manual

Siemens Delta Series User manual

Siemens

Siemens Delta Series User manual

Siemens SIMATIC EM 300 User manual

Siemens

Siemens SIMATIC EM 300 User manual

Siemens SITOP UPS1600 under STEP 7 V12 User manual

Siemens

Siemens SITOP UPS1600 under STEP 7 V12 User manual

Siemens SQK349.00/209 User manual

Siemens

Siemens SQK349.00/209 User manual

Siemens SIMATIC S7-1500T User manual

Siemens

Siemens SIMATIC S7-1500T User manual

Popular Controllers manuals by other brands

Victron energy BlueSolar MPPT 150/35 manual

Victron energy

Victron energy BlueSolar MPPT 150/35 manual

dbx ZC-9 How to use

dbx

dbx ZC-9 How to use

Toss ROPEX RESISTRON RES-407 operating instructions

Toss

Toss ROPEX RESISTRON RES-407 operating instructions

Elan OLE Specifications

Elan

Elan OLE Specifications

Niobrara QUCM Installation and programming manual

Niobrara

Niobrara QUCM Installation and programming manual

Parker R34 Installation & service instructions

Parker

Parker R34 Installation & service instructions

HomeMatic HM-LC-Sw1-PI-DN-R1 operating manual

HomeMatic

HomeMatic HM-LC-Sw1-PI-DN-R1 operating manual

Emerson Bettis RP3E Installation, operation and maintenance manual

Emerson

Emerson Bettis RP3E Installation, operation and maintenance manual

Eaton MMX11 Series installation instructions

Eaton

Eaton MMX11 Series installation instructions

Watts WFC-03 10Z HC RF 24 Quick installation guide

Watts

Watts WFC-03 10Z HC RF 24 Quick installation guide

TimeTec Security BLE-16 installation guide

TimeTec Security

TimeTec Security BLE-16 installation guide

Evco EV3802 quick start guide

Evco

Evco EV3802 quick start guide

Mitsubishi Electric Melservo MR-J3-10B instruction manual

Mitsubishi Electric

Mitsubishi Electric Melservo MR-J3-10B instruction manual

Ekinex KNX EK-FB1-TP quick start guide

Ekinex

Ekinex KNX EK-FB1-TP quick start guide

WEG PFW03-M08 user manual

WEG

WEG PFW03-M08 user manual

Vetus SENSORD Operation manual and installation instructions

Vetus

Vetus SENSORD Operation manual and installation instructions

Elko DIM-15 manual

Elko

Elko DIM-15 manual

Welger E-LINK RP 235 operating manual

Welger

Welger E-LINK RP 235 operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.