manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Controllers
  8. •
  9. Siemens RDE-MZ6 User manual

Siemens RDE-MZ6 User manual

Other Siemens Controllers manuals

Siemens SIRIUS M200D User manual

Siemens

Siemens SIRIUS M200D User manual

Siemens Synco 700 Series Operator's manual

Siemens

Siemens Synco 700 Series Operator's manual

Siemens SIMATIC S7-400H User manual

Siemens

Siemens SIMATIC S7-400H User manual

Siemens RLU2 Series User manual

Siemens

Siemens RLU2 Series User manual

Siemens SITOP PSU8600 User manual

Siemens

Siemens SITOP PSU8600 User manual

Siemens GCA 1 Series User manual

Siemens

Siemens GCA 1 Series User manual

Siemens SEZ50MB User manual

Siemens

Siemens SEZ50MB User manual

Siemens SIMATIC ET 200S User manual

Siemens

Siemens SIMATIC ET 200S User manual

Siemens SIPART DR24 User manual

Siemens

Siemens SIPART DR24 User manual

Siemens SIMATIC S7-200 User guide

Siemens

Siemens SIMATIC S7-200 User guide

Siemens GDB 1 Series User manual

Siemens

Siemens GDB 1 Series User manual

Siemens GD Series User manual

Siemens

Siemens GD Series User manual

Siemens instabus JB520C23 User manual

Siemens

Siemens instabus JB520C23 User manual

Siemens Simatic S7-1500 Technical Document

Siemens

Siemens Simatic S7-1500 Technical Document

Siemens SIRIUS S0 User manual

Siemens

Siemens SIRIUS S0 User manual

Siemens FT2001-A1 User manual

Siemens

Siemens FT2001-A1 User manual

Siemens Desigo PXC5.E003 User manual

Siemens

Siemens Desigo PXC5.E003 User manual

Siemens SSA Series User manual

Siemens

Siemens SSA Series User manual

Siemens SIMATIC ET 200SP User manual

Siemens

Siemens SIMATIC ET 200SP User manual

Siemens SIMATIC S7 User guide

Siemens

Siemens SIMATIC S7 User guide

Siemens SQM50.484R8A Owner's manual

Siemens

Siemens SQM50.484R8A Owner's manual

Siemens 125-1957 User manual

Siemens

Siemens 125-1957 User manual

Siemens Simatic S7-1500 User manual

Siemens

Siemens Simatic S7-1500 User manual

Siemens scalance WLC711 Administrator guide

Siemens

Siemens scalance WLC711 Administrator guide

Popular Controllers manuals by other brands

Digiplex DGP-848 Programming guide

Digiplex

Digiplex DGP-848 Programming guide

YASKAWA SGM series user manual

YASKAWA

YASKAWA SGM series user manual

Sinope Calypso RM3500ZB installation guide

Sinope

Sinope Calypso RM3500ZB installation guide

Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

Isimet

Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

LSIS sv-ip5a user manual

LSIS

LSIS sv-ip5a user manual

Airflow Uno hab Installation and operating instructions

Airflow

Airflow Uno hab Installation and operating instructions

ABB ACS580-01 drives Hardware manual

ABB

ABB ACS580-01 drives Hardware manual

Panasonic GM1 Series Reference manual

Panasonic

Panasonic GM1 Series Reference manual

Emerson SW93 owner's manual

Emerson

Emerson SW93 owner's manual

AutoAqua Smart ATO micro SATO-120P manual

AutoAqua

AutoAqua Smart ATO micro SATO-120P manual

Panasonic FP? Positioning Unit RTEX Technical manual

Panasonic

Panasonic FP? Positioning Unit RTEX Technical manual

Alpha IP MIOB 21001 manual

Alpha IP

Alpha IP MIOB 21001 manual

Surecom SR-629 user manual

Surecom

Surecom SR-629 user manual

Regulus SRS1 T Installation and operation manual

Regulus

Regulus SRS1 T Installation and operation manual

3M MicroTouch EX113 reference guide

3M

3M MicroTouch EX113 reference guide

KUHN TKS user manual

KUHN

KUHN TKS user manual

S&C PMH Instructions for operation

S&C

S&C PMH Instructions for operation

Regin CORRIGO L10 manual

Regin

Regin CORRIGO L10 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

1/3 Operating Instructions CB1B1428en_02 / 2018-03-21 Siemens Building Technologies
s
Operating Instructions
RDE-MZ6
The RDE-MZ6 is a multizone controller and is typically used for floor and zone heating applications.
It should only be used in conjunction with RDD100.1RF* or RDE100.1RF* room thermostats/
transmitters.
The multizone controller receives wireless signals from the configured RDD100.1RF or
RDE100.1RF and then controls the selected zone(s). Each zone can be controlled individually,
either without time program (via RDD100.1RF) or with time program (via RDE100.1RF). The
controller can handle up to 6 zones (1 to 6). One thermostat can also be paired to multiple zones.
Alternatively, the multizone controller (zone number 6 only output) can be reconfigured for an
application using a circulating pump or boiler. This means that the remaining zones 1 to 5 are free
to drive the valves and actuators. An internal DIP switch must be operated to activate this feature.
The multizone receiver is equipped with a built-in antenna and operates at a frequency of 433 MHz.
* To be ordered separately (S55770-T319 = RDD100.1RF, S55770-T320 = RDE100.1RF)
1 Indication of data transmission and operating state (LED)
2 Initialization of wireless communication with transmitter
(LEARN button)
3 RESET button
2/3 Operating Instructions CB1B1428en_02 / 2018-03-21 Siemens Building Technologies
How to pair transmitter and RDE-MZ6
Make sure RDD100.1RF or RDE100.1RF (thermostat(s)/
transmitter(s)) are on your hands.
Option 1: One transmitter for one zone on RDE-MZ6
Learn
Mode
+
–
!
To pair one transmitter to one zone, proceed as
follows:
Transmitter setting:
1) On the transmitter, enter the parameter
settings (refer to section "Do youwant to
change parameters?"in RDE100.1RFS or
RDD100.1RFS Operating Instructions).
2) Assign the transmitter to the following specific
zone and ensure the parameter number is set
as follows:
Zone no. 1 on transmitter, adjust P19=1
Zone no. 2 on transmitter, adjust P19=2
Zone no. 3 on transmitter, adjust P19=3
Zone no. 4 on transmitter, adjust P19=4
Zone no. 5 on transmitter, adjust P19=5
Zone no. 6 on transmitter, adjust P19=6
RDE-MZ6 receiver setting:
3) Power on the receiver.
4) Press and hold the LEARN button of the
respective channel/zone you want to learn on
RDE-MZ6 for at least 3 seconds, then
release it.
5) The red and green LEDs flash alternately on
the respective channel/zone to indicate this
channel is in learning mode.
Initiate learning:
6) On the transmitter, enter the parameter
settings once again.
7) Proceed to parameter P20. Adjust the value
to P20=1 (ON), then confirm.
8) During wireless learning, the LCD displays
"rF" and "Lrn". Wait for time out and the
transmitter exits the parameter settings.
Successful wireless learning:
9) The greenLED flashes for 10 minutes to
indicate that the paired channel has
successfully completed wireless learning.
Recommendation:
10) Additional test to ensure the wireless signal
is fine:
On the transmitter, change the operating
mode by pressing Mode or change the
setpoint by pressing +or –. On the paired
channel, the green LED should flash for 3
seconds before changing to constantly
green. At the same time, observe your
radiator, boiler or heater indication (if it has
one) to ensure that it changed the operating
mode.
11) If step 9 or 10 is working fine, this means
you have successfully paired the zone.
Repeat the same steps above if you want to
pair additional available transmitters individually.
Unsuccessful wireless learning:
12) If the channel fails to receive wireless data,
the red LED starts to flash **.
13) Repeat steps 1 to 10 until pairing is
successful.
Note:
Always start receiver learning before starting
pairing with the transmitter.
The units must be placed such that transmitter
and received signals have limited external
wireless interference.
**In normal operation, if a drop in wireless
communication occurs due to unforseeable noise,
just leave the receiver and it will recover
automatically.
The pairs are saved even if there is a power shut
down. Communication restarts automatically after
several minutes without any user action.
Option 2: One transmitter for more zones on RDE-MZ6
Learn
Mode
+
–
!
To pair a single transmitter to more zones on
the RDE-MZ6, proceed as follows:
Transmitter setting:
1) On the transmitter, enter the parameter
settings (refer to section "Do youwant to
change parameters?" in RDE100.1RFS or
RDD100.1RFS Operation Instructions).
2) Assign the transmitter to the following specific
zone and ensure the parameter number is set
as follows:
Zone no. 1 on transmitter, adjust P19=1
RDE-MZ6 receiver setting:
3) Press and hold LEARN button of the multiple
channels/zones you want to learn on RDE-
MZ6 for at least 3 seconds, then release
them.
Example: If you want to assign zone 1, 2 and
3 of the RDE-MZ6 to zone 1 of the
transmitter, press zone 1, 2 and 3 LEARN
button on the receiver simultaneously.
Observe that the LEDs of zone 1, 2 and 3
flash alternately in red and green which means
all 3 channels are in learning mode.
Initiate learning:
4) On the transmitter, enter the parameter
settings once again.
5) Proceed to parameter P20. Set the value to
P20=1 (ON), then confirm.
6) During wireless learning, the LCD displays
"rF" and "Lrn". Wait for time out and the
transmitter exits the parameter settings.
Summary above:
Zone 1 on the transmitter can control zone 1, 2
and 3 of the RDE-MZ6.
Note:
To check successful learning, refer to step 9-10
of the previous section.
How to reset the ID of the zone?
Reset Reset all zones
If the RDE-MZ6 is not in learning mode, press
and hold the RESET button for more than 10
seconds to reset all IDs of all 6 zones. 6 green
LEDs flash for 5 seconds and then extinguish
(recommended for first time setup).
Reset one zone
Press and hold the RESET button and the
respective zone button for more than 10
seconds. This only resets the specific zone.
The green LED of the channel flashes for 5
seconds and then extinguishes; the respective
zone ID is reset.
RED regulation
Siemens Switzerland Ltd. declares that the radio
equipment type RDE-MZ6 is in compliance with Directive
2014/53/EU. The full text of the EU declaration of
conformity is available at
www.siemens.com/download?A6V10403583.
3/3 Operating Instructions CB1B1428en_02 / 2018-03-21 Siemens Building Technologies
Alternative: Driving the circulating pump/
boiler
DIP
switch
!
For this application:
Step 1: Operate the DIP switch
Power off the RDE-MZ6.
Open the cover of the controller and set the DIP
switch to positionto 1 (ON). This means that
zone 6 is now reconfigured for the circulating
pump/boiler (default is OFF)
Switch no.
1
2
Application
All valves (zone 1 to 6)
OFF
OFF
Pump/boiler (zone 6 only)
ON
OFF
Step 2: Making connections
Connect zone 1 to zone 5 with valves or
actuators.
Connect zone 6 to the circulating pump or
boiler.
Step 3: Learning
Power on the RDE-MZ6.
Press and hold the RESET button for more
than 10 seconds to make a complete reset.
To pair zones 1 to 5, follow either option 1 or 2
in the previous section.
Zone 6: No pairing is required and the button is
disabled.
Functionality
The output of zone 6 is enabled if either one or
more of the remaining zones is turned on. Zone
6 will turn off if all remaining zones are turned
off (same as LED indication).
Note:
Always power off the receiver before operating
the DIP switch.
Whenever a DIP switch has changed its
position, it is highly recommended to make a
complete reset and perform wireless learning
again.
Controller’s LED indication
State of controller State of LED
Power up (or reset)
All 6 red and green LEDs flash
alternately for 5 seconds and then
extinguish.
Note: If the receiver zone was
previously programmed, it will
immediately change to constantly
red.
Learning mode
Successful learning
mode
The respective zone’s red and green
LEDs flash alternately.
The respective green LED will flash
for 10 minutes if controller learning is
successful.
Signal ok and output
status change
For boiler or pump
configuration
The respective zone’s green LED is
constantly lit. If the output status
changes, the green LED will flash for
3 seconds and then changes back to
constantly green.
Zone 6:
Green LED is lit when relay is
energized.
Green LED is extinguished when
relay is deenergized.
Fail to receive
wireless data
If the respective zone of the
controller fails to receive wireless
data, the red LED will start to flash
after 125 minutes.
If RDE-MZ6 signal is recovered, it
will return to the previous LED state.
Respective zone has
no ID
The respective LED is extinguished.