
(1*,1((5,1*,1)250$7,21 ,QWHUQDWLRQDO(QJOLVK
MICROMASTER 420 Reference Manual
12 Issue A1
3 This parameter sets the% boost applied at 0 Hz. The boost level is then
reduced with increasing frequency to a minimum value, set by P1316,
typically around about 10 Hz.
3 This parameter sets a boost voltage, as P1310, except that the boost is
applied only during acceleration, either following a start command or from
set point changes.
3 This parameter allows a constant linear boost, again as P1310, to be
applied following a start command only to improve ‘first time’ starting.
The maximum values of P1310, 1311,and 1312 are 250%, but the overall
maximum boost is limited by P0640, the motor overload setting. The boost voltage
will also be limited by the operation of the I2t function, so boost may be reduced
further if the motor is in danger of overheating. The progress of the I2t function can
be monitored by parameter r0034.
The default settings (P1310 = 50, P1311 and P1312 = 0) allow satisfactory
operation with most loads. Increasing the boost up to say 200% (note that P0640
setting will limit) on smaller motors and 100% on larger motors will often give
improved torque at low frequencies. Use P1311 and P1312 to limit this to
accelerating boost only (e.g. P1310 = 100, P1312 = 100), to reduce the possibility
of overheating.
2.8Proportional and Integral Control (PI)
2.8.1What is Closed Loop control?
Closed loop control is widely used in industrial applications to control a wide variety
of processes. Control engineering is a complex subject, but a simple closed loop
control uses a feedback signal from the process (such as temperature, pressure,
speed) a desired value or setpoint (often set manually) and a control system that
compares the two and derives an error signal. The error signal is then processed
and used to control the inverter and motor (in this case) to try to reduce the error.
The error signal processing can be very complex because of delays in the system.
The error signal is usually processed using a Proportional and Integral (PI)
controller whose parameters can be adjusted to optimize the performance and
stability of the system. Once a system is set up and stable, very efficient and
accurate control can be achieved. See Figure 2-10. Page 19.
2.8.2Implementation on MICROMASTER 420
The MICROMASTER 420 has a built in PI controller that can be enabled by the
user to allow closed loop control. Once the PI controller is enabled (using P2200),
the PI controller internally generates the motor frequency necessary to minimize
the error between the PI setpoint and the PI feedback. It does this by continuously
comparing the feedback signal with the setpoint and uses the PI controller to
determine the necessary motor frequency. The normal frequency setpoint (P1000
setting) and ramp times (P1120 & P1121) are automatically disabled but the
minimum and maximum output frequency settings (P1080 and P1082) remain
active.
2.8.3Setting up the PI controller
$FFHVVLQJ3,SDUDPHWHUV
The PI parameters are in the range between P2200 and P2294. For most
applications, the level 2 parameters are sufficient for setting up the PI controller.