5
SMART 7KT0308 Manual
Technical
specification
7KT0308 (Multi Line LED Class 1)
PowerMonitoringDevicePanelinstrumentforstdelectrical
valuesProtocol:ModbusRTU,MultilineLEDDisplayVaux:95V
to240VACx/1or5A,Class1
Measurements
measuringprocedure
•forvoltagemeasurement True RMS
•forcurrentmeasurement True RMS
typeofmeasuredvaluedetection complete
voltagecurve Sinusoidal or distorted
measurablelinefrequency
•initialvalue 45Hz
•full-scalevalue 65Hz
operatingmodeformeasuredvaluedetectionautomaticlinefrequency
detection
Yes
Supply voltage
designofthepowersupply SMPSpowersupply
typeofvoltageofthesupplyvoltage AC
Degree of protection class
protectionclassIPonthefront IP54
protectionclassIPoftheterminal IP20
Suitability
suitability for operation Installation in stationary panels in closed rooms
Product Functions
product function
•voltagemeasurement Yes
•currentmeasurement Yes
•activepowermeasurement Yes
•reactivepowermeasurement Yes
•apparentpowermeasurement Yes
•powerfactormeasurement Yes
•frequencymeasurement Yes
•apparentenergy/activeenergy/reactiveenergy Yes
•%TotalHarmonicsDistortion(THD) Yes
•Powerdemandmeasurement Yes
Display and operation
designofthedisplay LED
heightofthedisplay 48 mm
widthofthedisplay 62 mm
colorofthebackgroundofthedisplay Black
nationallanguageonthedisplayscreenissupported EN
numberofkeys 4
Fault limits
referenceconditionformeteringaccuracy InaccordancewithIEC61557-12,IEC62053-21,IEC62053-23
formulaforrelativetotalmeasurementinaccuracy
•formeasuredvariablevoltage Class0.5asperIEC61557-12
•formeasuredvariablecurrent Class0.5asperIEC61557-12
•formeasuredvariableapparentpower Class1asperIEC61557-12
•formeasuredvariableactivepower Class1asperIEC61557-12
•formeasuredvariablereactivepower Class2asperIEC61557-12
•formeasuredvariablepowerfactor Class1asperIEC61557-12
•formeasuredvariableactiveenergy Class1asperIEC61557-12andIEC62053-21
•formeasuredvariablereactiveenergy Class2asperIEC61557-12andIEC62053-23