PB-1191 Beam Detector Manual
9
Planning
Fundamentals of planning
The linear smoke detector PBA-1191 is ideal for certain applications. Use it to supplement or replace
point-type smoke detectors. Refer to the Fields of Use table for suitable applications.
FIELDS OF USE
Very Suitable: Suitable:
Large and high halls
Aircraft hangars
Cable and energy ducts
Churches
Buildings with artwork ceilings of historical interest
Rooms with complex ceiling sructures
Rooms with strong air currents
Heavy soiling of point detectors (textile and wood processing)
Monitoring at different levels
Expensive installation and maintenance of point detectors,
for example:
-- in sawtooth roofs
-- very high rooms
-- where point detectors would have to be
suspended at a lower level
Underground garages >9ft high (min)
Computer rooms
Under floor
Above ceiling
Corridors
Inner courtyards (malls)
Open-plan offices
Cross zone releasing appliances
In combination with flame detectors
Operating conditions
The distance between the PBA-1191 and the reflector must be between 17 ft and 280 ft.
- There must be a permanent line of vision between the PBA-1191 and the reflector. Care should
be taken to ensure that the IR beam is not interrupted by moving objects such as overhead
cranes, etc., which can lead to trouble signals.
- If point detectors cannot be used because of the interfering effects of smoke, steam, or dust,
note that the PBA-1191 will only solve the problem in certain cases.
- Avoid frontal incidence of sunlight, light from halogen lamps, etc. on the PBA-1191.
- Always mount the PBA-1191 in the vicinity of the ceiling (See Figure 11 for distances). The
detector placement must not be too close to or too far from the ceiling.
- The PBA-1191 is also suitable for very high rooms. As a supplementary measure, install
additional PBA-1191s at different levels and/or use additional flame detectors.