A6V10331032_j_en_-- Building Technologies
2019
-
01
-
24
Control Products and Systems
Sinteso™ Cerberus™ PRO
FDA241, FDA221
ASD Aspirating smoke detector
Siemens aspirating smoke detector (ASD) for the addressed FDnet/C
-
NET
detector line or for standalone operation
●Patented technology
●Early detection of a wider spectrum of particle sizes in the air
●Configuration using the USB interface or the control panel via FDCC221S
(optional)
●'ASD Asyst-Tool' software to assist with pipe configuration
●Unique dust-resistant detection chamber
●Intuitive front indicator for airflow and smoke value
●Access to service functions
●Different event protocols
●Offline/online configuration supported
●Cleaning function (FDA241)
●4…20 mA output
2
Building Technologies
A6V10331032_j_en_
--
Fire Safety 2019-01-24
Properties
●Extended optical detection thanks to dual wavelengths (blue and infrared): The
aspirating smoke detectors FDA241 and FDA221 use dual-wavelength technology to
trigger an alarm at the earliest possible moment. They are designed to protect small and
medium-sized business-critical environments for monitoring areas of up to 800 m2
(FDA241) or 500 m2(FDA221). The detectors continually suck in air through a pipe
system via their aspirating holes. The air is fed into a uniquely designed detection
chamber, in which tiny smoke particles are detected by scattered light.
●Lower mounting and service costs: The aspirating smoke detectors FDA241 and
FDA221 can be used on an FDnet/C-NET detector line. For this purpose, communication
transponder FDCC221S is required.
●Configuration using the USB interface or the control panel via FDCC221S (optional): All
detector configurations, maintenance work, and alarm and fault management processes
can be carried out at a central location – the fire control panel. This ensures better
control while also reducing the costs of the overall solution.
●'Out-of-the-box' mounting and commissioning: Installation is simple thanks to combined
functions for normalizing smoke values and airflow, as well as appropriate presettings for
alarm and fault thresholds.
●ASD filter box FDAZ292 available as an accessory: Dust and other dirt is filtered out of
the aspirated air and does not get into the aspirating smoke detector. The filters in the
ASD filter box are easy to replace.
Use
Aspirating smoke detectors are used for early detection of smoke-generating fires in rooms
and equipment. They are especially suited to applications in which point detectors are
pushed to their limits, cannot be used or can only be used with restrictions.
The aspirating smoke detector continually takes air from the monitored room using a
connected pipe system with defined aspirating holes. The air is supplied to the detection
chamber and is analyzed for smoke particles using the detector installed there. The
sensitivity of the detector can be adjusted.
The position and size of the aspirating holes are calculated with the 'FXS2056 ASD Asyst
Tool V2' software. The calculation ensures that the air passes from the aspirating hole to the
detector in the time specified and with the required calculated sensitivity.
The '
FXS2056
ASD Asyst Tool V2
' software is replacing the '
FXS2055
ASD Asyst Tool
'
software.
Examples of application
●Cavities such as false ceilings or false floors
●Clean rooms
●Rooms the height of which is greater than that permitted for point detectors
●Rooms with electromagnetic fields which influence the function of point detectors
●Large rooms up to 800 m²
●Separate monitoring of control cabinets and electronics cabinets
●Data centers
●Telecommunication centers
●Mounting lines
●Cable tunnels
●Conveyor belts
3
Building Technologies
A6V10331032_j_en_
--
Fire Safety 2019-01-24
Applications with a filter box
●Rooms with polluted air, in which the pollution has impaired the performance of optical
point detectors
●Mounting lines
●Recycling facilities
●Cement factories
●Mining industry
●Subway stations
●Agricultural operations
●All other applications with visible dust load
Functions
Indication
The display contains clear, comprehensible bar graphs for smoke and airflow, as well as an
alarm indicator, an error indicator, and a dust indicator (FDA241).
When the housing cover is open, the operator has access to the 'Reset', 'Normalize Smoke',
and 'Normalize Flow' functions, as well as the mini USB connector.
Front indicator FDA241
Front indicator FDA221
4
Building Technologies
A6V10331032_j_en_
--
Fire Safety 2019-01-24
Legend for the response indicators
Operation Flow warnings Smoke alarm Info alarm
Blowing
out
High flow
Normal flow
Low flow
Fire 2 No smoke
Error Fire 1
Pre-alarm
Fault/test
Dust
Opening the detector
CAUTION
Damage to the
connection cable
In order to prevent damage to the connection cable when positioning the housing cover,
make sure that the connection cable has been routed correctly.
The service area for the detector can be accessed in two ways.
●Partial access:
– Remove the two screws on the top of the detector.
– Slide the housing cover up until you hear it snap into place.
●Full access:
– Remove the two screws on the top of the detector.
– Slide the housing cover up until you hear it snap into place.
– Pull the housing cover out slightly at the sides and lift it up.
– Remove the housing cover.
1
2
5
Building Technologies
A6V10331032_j_en_
--
Fire Safety 2019-01-24
Service LED indicators and buttons
Flow OK
As soon as the selftest for normal operation has been completed successfully, the 'Flow OK'
LED starts to flash.
Smoke OK
As soon as the selftest for normal operation has been completed successfully, the
'Smoke OK' LED starts to flash.
Alarm
In the event of a smoke alarm, the 'Alarm' LED starts to flash.
Normalization of the airflow
To determine the nominal airflow of the detector, perform this function during commissioning.
The nominal value established during normalization of the airflow forms the setpoint value for
monitoring the airflow during normal operation.
To perform this function, use a thin object (such as a paper clip or a watchmaker's
screwdriver) to press the button in the opening.
Once you have finished with this function, press the button in the opening again.
The smoke detector uses standard values for monitoring during normalization.
Normalization of the smoke density
To determine the nominal air quality in relation to the smoke density, perform this function
during commissioning. The nominal value established during normalization forms the
setpoint value for monitoring the smoke density during normal operation.
To perform this function, use a thin object (such as a paper clip or a watchmaker's
screwdriver) to press the button in the opening.
Once you have finished with this function, press the button in the opening again.
The smoke detector uses standard values for monitoring during normalization.
The detector provides information about the current normalization process via
FDnet/C-NET (no distinction is made between smoke and airflow).
6
Building Technologies
A6V10331032_j_en_
--
Fire Safety 2019-01-24
Reset button
Use the reset button to reset all of the detector's status indicators. These indicators can refer
to fire alarms or airflow events. Resetting the fire alarm also resets the associated relay.
If the detector is operated on the
FDnet/C
-
NET
, the alarms and the associated relays are
not reset.
USB connection
You can use a mini USB cable to connect the detector to a Windows PC. To set up the
detector, use the configuration tool 'FXS2051 ASD Configuration Tool'.
Test function LED
Hold the 'Buzzer silence' button down for 5 seconds. The LEDs on the display are tested
with 3 different brightness settings.
If the aspirating smoke detector is to be operated on the FDnet/C-NET, the communication
interface FDCC221S (S24218-A201-A2) must be ordered separately.
7
Building Technologies
A6V10331032_j_en_
--
Fire Safety 2019-01-24
Accessories
Communication interface FDCC221S
●For connecting the aspirating smoke detector to FDnet/C-NET
●Integrated 'line separator' function
●Additional MC link interface (port for 3.5 mm jack)
●Tool-free mounting on a designated PCB slot
●Supplied with:
– 2x spacers with thread
– 4-pin plug-in terminal
– ID adhesive label
Power supply kit FP120-Z1
●Standalone power supply (70 W)
●Supply to external devices and components in accordance with EN 54-4 and
VdS
●With operating and fault indicator, shown via a green and a yellow LED
●With potential-free relay contacts for fault messages
●Additional installation of an I/O module possible
●Uninterruptible power supply with battery charging
●Batteries: max. 17 Ah
●Dimensions: (W x H x D) 430 x 399 x 124 mm
Battery FA2003-A1 (12 V, 7 Ah, VdS)
●For supplying fire control panels and aspirating smoke detectors with power
●Compatible with:
– Fire control panels for the 'Sinteso' and 'Cerberus PRO' product lines
– External power units for the aspirating smoke detectors FDA241 and
FDA221
Battery FA2004-A1 (12 V, 12 Ah, VdS)
●For supplying fire control panels and aspirating smoke detectors with power
●Compatible with:
– Fire control panels for the 'Sinteso' and 'Cerberus PRO' product lines
– External power units for the aspirating smoke detectors FDA241 and
FDA221
8
Building Technologies
A6V10331032_j_en_
--
Fire Safety 2019-01-24
Battery FA2005-A1 (12 V, 17 Ah, VdS)
●For supplying fire control panels and aspirating smoke detectors with power
●Compatible with:
– Fire control panels for the 'Sinteso' and 'Cerberus PRO' product lines
– External power units for the aspirating smoke detectors FDA241 and
FDA221
FDAZ291 aspirator (FDA241/FDA221)
●Spare part for the aspirating smoke detectors FDA241 and FDA221
●You will find more information in document A6V10916366
FDAZ292 ASD filter box
●Filter box for installation in the pipe system for aspirating smoke detectors
●Filters dust and other dirt out of the air aspirated by the aspirating smoke
detector
●Minimizes internal contamination of the aspirating smoke detector
●Contains filter set FDAZ292-AA with three filters, coarse/medium/fine
●Compatible with the aspirating smoke detectors FDA241 and FDA221
●You will find more information in document A6V10877841
FDAZ292-AA ASD filter set
●Spare part for the ASD filter box FDAZ292
●Filter set contains one coarse filter, one medium filter, and one fine filter
9
Building Technologies
A6V10331032_j_en_
--
Fire Safety 2019-01-24
Type Overview
Type Designation Order number Weight [kg]
FDA241 Aspirating smoke detector (8H) S54333-F17-A1 1.495
FDA221 Aspirating smoke detector (5S) S54333-F15-A1 1.495
Accessories
FDCC221S Communications interface S24218-A201-A2 0.019
FP120-Z1 Power supply kit A (70 W) S54400-S122-A1 3.920
FA2003-A1 Battery (12 V, 7 Ah, VdS) A5Q00019353 2.450
FA2004-A1 Battery (12 V, 12 Ah, VdS) A5Q00019354 3.930
FA2005-A1 Battery (12 V, 17 Ah, VdS) A5Q00019677 5.640
FDAZ292 ASD filter box S54333-C92-A1 0.220
Spare parts
FDAZ292-AA ASD filter set S54333-S91-A1 0.009
FDAZ291 Aspirator (FDA241/FDA221) S54333-G1-A1 0.106
Product documentation
Document ID Title
A6V10334410 Technical manual Aspirating smoke detector FDA241, FDA221
A6V10393194 Technical manual Power supply kit A 70 W FP120-Z1
A6V10345654 Installation, Mounting Aspirating Smoke Detectors FDA241, FDA221
A6V10340094 User Manual 'ASD Asyst Tool FXS2055'
A6V10728226 User Manual 'ASD Asyst Tool V2 FXS2056'
A6V10334435 Planning, Installation ASD Pipe system
A6V10332759 Installation, Operation Manual, Configuration 'ASD Configuration Tool FXS2051'
A6V10877841 Installation ASD Filterbox FDAZ292
A6V10916591 Installation Aspirator (FDA241/FDA221) FDAZ291
Related documents such as environmental declarations, CE declarations, etc., can be
downloaded at the following Internet address:
http://siemens.com/bt/download
Notes
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
●Dispose of the device through channels provided for this purpose.
●Comply with all local and currently applicable laws and regulations.
10
Building Technologies
A6V10331032_j_en_
--
Fire Safety 2019-01-24
Technical data
FDA241 FDA221
Operating voltage DC 19…30 V
Operating current at DC 24 V 150 mA (nominal), 250 mA (during alarm)
Dimensions (W x H x D) 162 x 285 x 120 mm
Protection category IP30
Installation position Vertically upward, vertically downward
Sound power level LWA [dBA]: 1) -
At suction speed
- High
- Medium
- Low
37
33
30
33
30
26
Operating temperature -20…+60 °C
Air humidity 5…95 % (no moisture condensation)
Dust indicator Yes -
Maximum pipe length
- Single line
- Branched lines
60 m
2x 60 m
30 m
2x 25 m
Options for aspirating holes Prefabricated option or the maximum pipe length must correspond to the
calculation made using the 'FXS2056 ASD Asyst Tool V2' software
Air intake/exhaust pipe Metric: 25 mm outer diameter (OD)
Monitoring area (dependent on local
provisions and standards)
Up to 800 m² Up to 500 m²
System compatibility Compatible with all Siemens FC20/FC720 (FS20/FS720 systems)
Relay alarm outputs
Can be selected with/without lock
Nominal current 2.0 A at DC 30 V.
Contact: NO/NC
4 3
Fault relay 1 1
Cable inlet 10 cm x 2.5 cm on the rear or from above
Terminal configuration Screw terminals
Cable cross section 0.2…2.5 mm2(AWG 12…30)
Other interfaces Power supply, 4…20 mA
Alarm threshold for parameter sets:
Fire 1 10 sets
0.05…2.0 %/m obs
5 sets
0.20…2.0 %/m obs
Fire 2 10 sets
2.0…20 %/m obs
5 sets
6.0…20 %/m obs
Alarm delay, can be set individually 0…300 seconds: default value 0 seconds smoke density and
15 seconds flow
11
Building Technologies
A6V10331032_j_en_
--
Fire Safety 2019-01-24
FDA241 FDA221
Indication ●4x alarm status indicators (FDA241)
●3x alarm status indicators (FDA221)
●Faults
●Blowing out (FDA241)
●Dust (FDA241)
●Smoke density and flow indicator
Service area ●LED 'Status OK'
●USB
●Settings for reset functions
●Settings for smoke density and airflow
Event log Non-volatile event memory with time and date stamp for: smoke density,
airflow, detector status, and faults
Normalization of smoke value and
airflow
●Setting of threshold values for smoke alarms and faults
●User setting for normalization of smoke density and airflow
●Preset values are retained during the normalization period
Warranty period 2 years
Approvals
●VdS
FDA241
G213050
FDA221
G213050
1A-weighted sound power level in [dB] as per DIN EN ISO 3744-2009,
measured with a pipe piece at the air inlet and at the air outlet
Dimensional drawings
FDA241, FDA221
12
Building Technologies
A6V10331032_j_en_
--
Fire Safety 2019-01-24
Issued by
Siemens Switzerland Ltd
Building Technologies Division
International Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2013
Technical specifications and availability subject to change without notice.
Document ID A6V10331032_j_en_--
Edition 2019-01-24
FDAZ292
73
95
214
174.2
74
5
0786
Siemens Schweiz AG; Theilerstrasse 1a
CH-6300 Zug
Technical data: see doc.
A6V10334410
The declared performance and conformity can be seen in the Declaration of Performance (DoP) and the EU Declaration of Conformity (DoC),
which is obtainable via the Customer Support center: Tel. +49 89 9221-8000 or http://siemens.com/bt/download
13
FDA221 / FDA241 - Aspirating smoke detector for use in fire detection and fire alarm systems installed in buildings.
305/2011/EU (CPR): EN 54-20 / EN 54-17 ; 2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2011/65/EU (RoHS): EN 50581
DoP No.: 0786-CPR-21270; DoC No.: CED-FDA221/FDA241
FDA221 / FDA241
0786
Siemens Schweiz AG, Theilerstrasse 1a
CH-6300 Zug
Technical data: see doc.
A6V10334410
The declared performance and conformity can be seen in the Declaration of Performance (DoP) and the EC Declaration of Conformity (DoC),
which is obtainable via the Customer Support center: Tel. +49 89 9221-8000 or https://siemens.com/bt/download
13
FDCC221S - Input/output device incl. short-circuit isolator for use in fire detection and fire alarm systems installed in buildings.
305/2011/EU (CPR): EN 54-17 / EN 54-18 ; 2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2011/65/EU (RoHS): EN 50581
DoP No.: 0786-CPR-21270; DoC No.: CED-FDA221/FDA241
FDCC221S

This manual suits for next models

1

Other Siemens Smoke Alarm manuals

Siemens PE-11C User manual

Siemens

Siemens PE-11C User manual

Siemens DELTA Reflex SD9 User manual

Siemens

Siemens DELTA Reflex SD9 User manual

Siemens Cerberus Pyrotronics PB-1191 User manual

Siemens

Siemens Cerberus Pyrotronics PB-1191 User manual

Siemens Synco living AP260 User manual

Siemens

Siemens Synco living AP260 User manual

Siemens Cerberus DO1101A-Ex Parts list manual

Siemens

Siemens Cerberus DO1101A-Ex Parts list manual

Siemens BH17 7ER User manual

Siemens

Siemens BH17 7ER User manual

Siemens 5TC1292-7 User manual

Siemens

Siemens 5TC1292-7 User manual

Siemens Cerberus DBW1171 User manual

Siemens

Siemens Cerberus DBW1171 User manual

Siemens FCI2016-U1 Guide

Siemens

Siemens FCI2016-U1 Guide

Siemens TITANUS SuperSens User manual

Siemens

Siemens TITANUS SuperSens User manual

Siemens DELTA reflex SD9L Service manual

Siemens

Siemens DELTA reflex SD9L Service manual

Siemens OP121 User manual

Siemens

Siemens OP121 User manual

Siemens AD1-C11 User manual

Siemens

Siemens AD1-C11 User manual

Siemens DELTA reflex SD230N Service manual

Siemens

Siemens DELTA reflex SD230N Service manual

Siemens DELTA reflex SD230N Service manual

Siemens

Siemens DELTA reflex SD230N Service manual

Siemens Cerberus DOT1151A-Ex Parts list manual

Siemens

Siemens Cerberus DOT1151A-Ex Parts list manual

Siemens DOW1171 User manual

Siemens

Siemens DOW1171 User manual

Siemens DELTA reflex 5TC1 290 Service manual

Siemens

Siemens DELTA reflex 5TC1 290 Service manual

Siemens FDA2 1 Series User manual

Siemens

Siemens FDA2 1 Series User manual

Siemens DB721-CN User manual

Siemens

Siemens DB721-CN User manual

Siemens Cerberus DLO1191 Guide

Siemens

Siemens Cerberus DLO1191 Guide

Siemens TITANUS 3000 User manual

Siemens

Siemens TITANUS 3000 User manual

Siemens DM1101 User manual

Siemens

Siemens DM1101 User manual

Siemens OH921 User manual

Siemens

Siemens OH921 User manual

Popular Smoke Alarm manuals by other brands

x-sense XS01 user manual

x-sense

x-sense XS01 user manual

Firex I240C user manual

Firex

Firex I240C user manual

BRK electronic 650M owner's manual

BRK electronic

BRK electronic 650M owner's manual

Alecto SA-200 manual

Alecto

Alecto SA-200 manual

Bosch EVAX25E Easy installation and operation

Bosch

Bosch EVAX25E Easy installation and operation

Johnson Controls METASYS B501BHJ instructions

Johnson Controls

Johnson Controls METASYS B501BHJ instructions

BURGprotect Smoke 2050 user manual

BURGprotect

BURGprotect Smoke 2050 user manual

Metasys 2551J manual

Metasys

Metasys 2551J manual

Challenger SMART FORCE ASFSM Installation and operating instructions

Challenger

Challenger SMART FORCE ASFSM Installation and operating instructions

GLOBAL Export Import GS804 user manual

GLOBAL Export Import

GLOBAL Export Import GS804 user manual

Xtralis VESDA-E VEU Installation instructions manual

Xtralis

Xtralis VESDA-E VEU Installation instructions manual

Apollo AlarmSense manual

Apollo

Apollo AlarmSense manual

Convoy Security YT202 Installation and maintenance instructions

Convoy Security

Convoy Security YT202 Installation and maintenance instructions

Longsin LS-828-27 manual

Longsin

Longsin LS-828-27 manual

First Alert P1010 user manual

First Alert

First Alert P1010 user manual

aguilera AE/C5-OPT quick guide

aguilera

aguilera AE/C5-OPT quick guide

Wheelock SERIES NS-24MCW installation instructions

Wheelock

Wheelock SERIES NS-24MCW installation instructions

Quell Q946 manual

Quell

Quell Q946 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.