Siemens SIPART PS2 Parts list manual

Other manuals for SIPART PS2

21

This manual suits for next models

5

Other Siemens Valve Positioner manuals

Siemens SIPART PS2 6DR50xx User manual

Siemens

Siemens SIPART PS2 6DR50xx User manual

Siemens SIPART PS2 6DR5xx0 series Administrator guide

Siemens

Siemens SIPART PS2 6DR5xx0 series Administrator guide

Siemens SIPART PS2 User manual

Siemens

Siemens SIPART PS2 User manual

Siemens SIPART PS2 User manual

Siemens

Siemens SIPART PS2 User manual

Siemens SIPART PS2 6DR5 series Administrator guide

Siemens

Siemens SIPART PS2 6DR5 series Administrator guide

Siemens SIPART PS2 User manual

Siemens

Siemens SIPART PS2 User manual

Siemens SIPART PS100 User manual

Siemens

Siemens SIPART PS100 User manual

Siemens SIPART PS2 User manual

Siemens

Siemens SIPART PS2 User manual

Siemens SIPART PS2 Administrator guide

Siemens

Siemens SIPART PS2 Administrator guide

Siemens SIPART PS2 User manual

Siemens

Siemens SIPART PS2 User manual

Siemens SIPART PS2 FF Administrator guide

Siemens

Siemens SIPART PS2 FF Administrator guide

Siemens SIPART PS2 User manual

Siemens

Siemens SIPART PS2 User manual

Siemens SITRANS VP300 User manual

Siemens

Siemens SITRANS VP300 User manual

Siemens SIPART PS2 6DR5020 Series User manual

Siemens

Siemens SIPART PS2 6DR5020 Series User manual

Siemens SIPART PS2 User manual

Siemens

Siemens SIPART PS2 User manual

Siemens SIPART PS100 Administrator guide

Siemens

Siemens SIPART PS100 Administrator guide

Siemens SIPART PS2 User manual

Siemens

Siemens SIPART PS2 User manual

Siemens 73N12F Quick guide

Siemens

Siemens 73N12F Quick guide

Siemens 6DR50 Series User manual

Siemens

Siemens 6DR50 Series User manual

Siemens SIPART PS2 Installation guide

Siemens

Siemens SIPART PS2 Installation guide

Siemens SIPART Series User manual

Siemens

Siemens SIPART Series User manual

Siemens 6DR55 Series User manual

Siemens

Siemens 6DR55 Series User manual

Siemens SITRANS VP100 User manual

Siemens

Siemens SITRANS VP100 User manual

Siemens SIPART PS2 Assembly instructions

Siemens

Siemens SIPART PS2 Assembly instructions

Popular Valve Positioner manuals by other brands

HALDER 23111.0016 Short instruction manual

HALDER

HALDER 23111.0016 Short instruction manual

Parker 404XE Series product manual

Parker

Parker 404XE Series product manual

Ytc TMP-3000 product manual

Ytc

Ytc TMP-3000 product manual

PI M-605 Series user manual

PI

PI M-605 Series user manual

Pepperl+Fuchs PXV100AS-F200-SSI-V19 manual

Pepperl+Fuchs

Pepperl+Fuchs PXV100AS-F200-SSI-V19 manual

RTK RE 3442 Series Installation and operating instructions

RTK

RTK RE 3442 Series Installation and operating instructions

CVS Controls 1200 instruction manual

CVS Controls

CVS Controls 1200 instruction manual

Westlock Quantum 2800 Installation & operating instructions

Westlock

Westlock Quantum 2800 Installation & operating instructions

Samson 3730-0 Mounting and operating instructions

Samson

Samson 3730-0 Mounting and operating instructions

Samson TROVIS 3730-3 Mounting and operating instructions

Samson

Samson TROVIS 3730-3 Mounting and operating instructions

ESCO Technologies ETS LINDGREN 2302-001 user manual

ESCO Technologies

ESCO Technologies ETS LINDGREN 2302-001 user manual

Parker MX80L series product manual

Parker

Parker MX80L series product manual

SMC Networks IP8000 manual

SMC Networks

SMC Networks IP8000 manual

Burkert 8694 operating instructions

Burkert

Burkert 8694 operating instructions

iXBlue POSIDONIA II Technical description

iXBlue

iXBlue POSIDONIA II Technical description

Samson TROVIS 3730-3 Mounting and operating instructions

Samson

Samson TROVIS 3730-3 Mounting and operating instructions

Flowserve Logix 3200IQ Replacement instructions

Flowserve

Flowserve Logix 3200IQ Replacement instructions

Lang LHT500 Assembly instruction

Lang

Lang LHT500 Assembly instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Siemens FI 01 · 2009
6/2 Product overview
6/3 SIPART PS2
6/3 Technical description
6/8 Technical specifications
6/8 - all versions
6/9 - SIPART PS2
6/11 - SIPART PS2 PA
6/13 - SIPART PS2 FF
6/15 - Option modules
6/18 Ordering data
6/18 - SIPART PS2, PS2 PA, PS2 FF
6/19 - SIPART PS2 EEx-d, PS2 EEx-d PA,
PS2 EEx-d FF
6/20 - Accessories
6/22 Dimensionsal drawings
6/23 Schematics
6/24 Mounting kits
Software
Sec. 9 SIMATIC PDM, for parameterize
HART and PROFIBUS PA devices
You can download all instructions, cata-
logs and certificates for SIPART PS2 free
of charge at the following Internet
address:
www.siemens.com/sipartps2
Electropneumatic positioners
SIPART PS2
© Siemens AG 2008
Electropneumatic positioners
Product overview
6/2 Siemens FI 01 · 2009
6
■
Overview
Application Device description Catalog
page
Software for
parameterization
Electropneumatic positioners SIPART PS2
Position control
Pneumatic linear or part-
turn actuators, also for
intrinsically-safe opera-
tion
SIPART PS2
Universal device for positioning pneumatic actuators
• Connection: 4 to 20 mA
• HART, PROFIBUS PA or Foundation Fieldbus
• Local manual operation
• Binary inputs and outputs
• Diagnosis functions
• Blocking function
• Automatic startup
6/3 SIMATIC PDM
As above, but in flame-
proof casing for explo-
sion-proof application
SIPART PS2
As above, but in flameproof aluminium
casing
6/3 SIMATIC PDM
© Siemens AG 2008
Electropneumatic positioners
SIPART PS2
Technical description
6/3
Siemens FI 01 · 2009
6
■
Overview
SIPART PS2 electropneumatic positioner
SIPART PS2 EEx d electropneumatic positioner in flameproof casing
SIPART PS2 in stainless steel casing
The SIPART PS2 electropneumatic positioner is used to control
the final control element of pneumatic linear or part-turn actua-
tors. The electropneumatic positioner moves the actuator to a
valve position corresponding to the setpoint. Additional function
inputs can be used to block the valve or to set a safety position.
A binary input is present as standard in the basic device for this
purpose.
■
Benefits
SIPART PS2 positioners offer decisive advantages:
• Simple installation and automatic commissioning (self-adjust-
ment of zero and span)
• Simple operation with
- Local operation and configuration of the device using three
input keys and a user-friendly two-line LCD
- Programming through SIMATIC PDM
• Very high-quality control thanks to an online adaptation proce-
dure
• Negligible air consumption in stationary operation
• "Tight shut-off" function (ensures maximum positioning pres-
sure on the valve seat)
• Numerous functions can be activated by simple configuring
(e.g. characteristics and limits)
• Extensive diagnosis functions for valve and actuator
• Only one device version for linear and part-turn actuators
• Few moving parts, hence insensitive to vibrations
• External non-contacting position sensor as option for extreme
ambient conditions
• "Intelligent solenoid valve": Partial Stroke Test and solenoid
valve function in a single device
• Partial Stroke Test e.g. for safety valves
• SIL (Safety Integrity Level) 2
• Can also be operated with natural gas
■
Application
The SIPART PS2 positioner is used, for example, in the following
industries:
• Chemical/petrochemical
• Power stations
• Paper and glass
• Water, waste water
• Food and pharmaceuticals
• Offshore plants
The SIPART PS2 positioner is available:
• For single-action actuators: in plastic, stainless steel or alumi-
num casings, as well as flameproof aluminium casing (EEx d)
• For double-action actuators: in plastic and stainless steel cas-
ing, as well as flameproof aluminum casing (EEx d)
• For non-hazardous applications
• For hazardous applications in the designs
- as intrinsically-safe device (EEx ia/ib) or
- in flameproof aluminum casing (EEx d) or
- in EEx n design (non sparking)
and in the versions:
• 0/4 to 20 mA control communication without/with communica-
tion through HART signal
• With PROFIBUS PA communication interface
• With FOUNDATION Fieldbus (FF) communications interface.
Explosion-proof versions
The basic version of the device is available in an intrinsically-
safe design with degree of protection EEx ia/ib or in a design
with approval for zone 2/zone 22 (dust).
Operation in zone 1 is permitted when enclosed in the flame-
proof casing version SIPART PS2 EEx d. (see "Technical Data").
It is then permissible to use all option modules (except external
actuator travel detection systems, SIA module, limit value con-
tact module and NCS).
© Siemens AG 2008
Electropneumatic positioners
SIPART PS2
Technical description
6/4 Siemens FI 01 · 2009
6
Stainless steel casing for extreme ambient conditions
The SIPART PS2 is available in a stainless steel casing (without
window in the lid) for use in particularly aggressive environments
(e.g. offshore operation, chlorine plants etc.). The device func-
tions are the same as those of the basic versions.
■
Design
The SIPART PS2 positioner is a digital field device with a highly-
integrated microcontroller.
The positioner consists of the following components:
• Casing and cover
• PCB with corresponding electronics with or without communi-
cation through HART
or with electronics for communication in accordance with
- PROFIBUS PA specification, IEC 61158-2; bus-supplied de-
vice, or
- FOUNDATION Fieldbus (FF) specification, IEC 61158-2,
bus-supplied device
• Actuator travel detection system
• Terminal housing with screw terminals
• Pneumatic valve manifold with piezoelectric valve precontrol.
The valve manifold is located in the housing, the pneumatic con-
nections for the inlet air and the positioning pressure on the right-
hand side. A pressure gauge block and/or a safety solenoid
valve can be connected there as options. The SIPART PS2 posi-
tioner is fitted to the linear or part-turn actuator using an appro-
priate mounting assembly. The circuit board container in the
casing provides slots for separately ordered boards with the
following functions:
Iymodule:
• Position feedback as a two-wire signal 4 to 20 mA.
Alarm module (3 outputs, 1 input):
• Signaling of two limits of the travel or angle by binary signals.
The two limits can be set independently as maximum or mini-
mum values.
•Output of an alarm if the setpoint position of the final control
element is not reached in automatic mode or if a device/fitting
fault occurs.
• Second binary input for alarm signals of for triggering safety
reactions e. g. for blocking function or safety position.
Limit signaling through slot-type initiators (SIA module)
Two limits can be signaled redundantly as NAMUR signals
(EN 60947-5-6) by slot-type initiators. The module also contains
an alarm output (see Alarm module).
Limit value signal via mechanical contacts (Limit value con-
tact module)
Two limits can be signaled redundantly by switching contacts. A
fault message output is also integrated in the module (see alarm
module).
Valid for all modules described above:
All signals are electrically isolated from one another and from the
basic unit. The outputs indicate self-signaling faults. The mod-
ules are easy to retrofit.
Separate mounting of actuator travel detection system and
controller unit
The actuator travel detection system and controller unit can be
connected separately for all casing versions of the SIPART PS2
(except flameproof design). Measurement of the travel or angle
is carried out directly on the actuator. The controller unit can then
be fitted a certain distance away, e.g. on a mounting pipe or sim-
ilar, and is connected to the travel detection system by an elec-
tric cable and to the actuator by one or two pneumatic lines.
Such a split design is frequently advantageous if the ambient
conditions at the fitting exceed the specified values for the posi-
tioner (e.g. strong vibrations).
The following can be used for measuring the travel or angle:
• NCS sensor
• External position detection system C73451-A430-D78
• A commercially available potentiometer (10 kΩresistance)
(e.g. for higher application temperatures or customer-specific
applications)
The use of linear potentiometers is recommended for very small ac-
tuators with a short valve travel since, on the one hand, the space
required by the linear potentiometer is very small and, on the other,
the transmission characteristic is optimum for a small travel.
Separate connection of actuator travel detection system and controller unit
Non-contacting position sensor (NCS)
Contact and non-contacting positioning sensor (NCS) for part-turn actu-
ator (left) and for linear actuator 14 mm (0.55 inch) (right)
NCS for travels >14 mm (0.55 inch)
Separate connection of actuator travel detection system and controller unit
© Siemens AG 2008
Electropneumatic positioners
SIPART PS2
Technical description
6/5
Siemens FI 01 · 2009
6
The NCS sensor consists of a non-contacting position sensor. All
coupling elements are omitted such as coupling wheel and
driver pin with part-turn actuators or lever and pick-up bracket
with linear actuators up to 14 mm travel.
This results in:
• Even greater resistance to vibration and shock
• No wear of sensor
• Problem-free mounting on very small actuators
• Negligible hysteresis with very small travels.
The sensor does not require an additional power supply, i.e.
SIPART PS2 (not for EEx d version) can be operated in a 2-wire
system. The NCS (Non Contacting Position Sensor) consists of a
potted sensor housing which must be mounted permanently and
a magnet which is mounted on the spindle of linear actuators or
on the shaft butt of part-turn actuators. For the version for travels
>14 mm (0.55 inch), the magnet and the NCS are premounted
on a stainless steel frame and offer the same interface mechan-
ically as the positioner itself, i.e. they can be mounted using the
standard mounting kits 6DR4004-8V, -8VK and -8VL.
The installation of a EMC filter module in the positioner (controller
unit) is necessary in order to ensure a connection level with EMC
according to EN 61326/A1 and NAMUR NE21 when using exter-
nal sensors (see Ordering data for "EMC filter module")
■
Function
The SIPART PS2 electropneumatic positioner works in a com-
pletely different way to normal positioners.
Mode of operation
Comparison of the setpoint and the actual value takes place
electronically in a microcontroller. If the microcontroller detects a
deviation, it uses a 5-way switch procedure to control the piezo-
electric valves, which regulates the flow of air into and from the
chambers of the pneumatic actuator or blows it in the opposite
direction.
The microcontroller then outputs an electric control command to
the piezoelectric valve in accordance with the size and direction
of the deviation (deviation between setpoint w and control
output x). The piezoelectric valve converts the command into a
pneumatic positional increment.
The positioner outputs a continuous signal in the area where
there is a large control deviation (high-speed zone); in areas of
moderate control deviation (slow-speed zone) it outputs a se-
quence of pulses. No positioning signals are output in the case
of a small control deviation (adaptive or variable dead zone).
The linear or rotary motion of the actuator is detected by the
mounting assembly and transferred to a high-quality potentio-
meter made of plastic conductive material over a shaft and a
non-floating gear transmission.
The angular error of the pick-up in cases where the assembly is
mounted on a linear actuator is corrected automatically.
When connected in a 2-wire system, the SIPART PS2 draws its
power exclusively from the 4 to 20 mA setpoint signal. The elec-
tric power is also connected through the 2-wire bus signal with
PROFIBUS operation (SIPART PS2 PA). The same applies for the
FOUNDATION Fieldbus version.
Pneumatic valve manifold with piezoelectric valve precontrol
The piezoelectric valve can release very short control pulses.
This helps achieve a high positioning accuracy. The pilot ele-
ment is a piezoelectric bending converter which switches the
pneumatic main control unit. The valve manifold is characterized
by an extremely long service life.
Local operation
Local operation is performed using the built-in LCD and the
three input keys. Switching between the operating levels Auto-
matic, Manual, Configuring and Diagnosis is possible at the
press of a button.
In Manual mode the drive can be adjusted over the entire range
without interrupting the circuit.
Operation and monitoring with the SIMATIC PDM communi-
cations program
The SIMATIC PDM program is available for communication
through the HART interface and also for the PROFIBUS PA cou-
pling.
The SIMATIC PDM communications software permits easy re-
mote operation and monitoring using a PC or laptop. The posi-
tioner can also be configured using this program. Parameters
which provide important information for maintenance and fault
diagnosis of the complete unit can also be determined using
process data and comparison data.
When operating the SIPART PS2 through the HART interface, the
connection is made directly to the 2-wire cable to the
SIPART PS2 positioner through a HART modem that can be con-
nected to the RS 232 or USB interface. The signals needed for
communication in conformity with the HART protocol are super-
imposed on the current signal in accordance with the Frequency
Shift Keying (FSK) method.
Automatic commissioning
With a simple configuration menu the SIPART PS2 can be quickly
adapted to the fitting and adjusted by means of an automatic
startup function.
During initialization, the microcontroller determines the zero
point, full-scale value, the direction of action and the positioning
speed of the fitting. From this data it establishes the minimum
pulse time and the dead zone, thus optimizing the control.
Low air consumption
A hallmark of the SIPART PS2 is its own extremely low consump-
tion of air. Normal air losses on conventional positioners are very
costly. Thanks to the use of modern piezoelectric technology, the
SIPART PS2 consumes air only when it is needed, which means
that it pays for itself within a very short time
Comprehensive monitoring functions
The SIPART PS2 has various monitoring functions with which
changes on the actuator and valve can be detected and sig-
naled if applicable when a selectable limit has been exceeded.
This information may be important for diagnosis of the actuator
or valve. The measured values to be determined and monitored,
some of whose limits can be adjusted, include:
• Travel integral
• Number of changes in direction
• Alarm counter
• Self-adjusting dead zone
• Valve end limit position (e.g. for detection of valve seat wear
or deposits)
• Operating hours (also according to temperature and position-
ing ranges) as well as min./max. temperature
• Operating cycles of piezoelectric valves
• Valve positioning time
• Actuator leakages
© Siemens AG 2008
Electropneumatic positioners
SIPART PS2
Technical description
6/6 Siemens FI 01 · 2009
6
Status monitoring with 3-stage alarm concept
The intelligent electropneumatic SIPART PS2 positioner is
equipped with additional monitoring functions. The status indi-
cations derived from these monitoring functions signal active
faults of the unit. The severity of these faults are graded using
"traffic light signaling", symbolized by a wrench in the colors
green, yellow and red (with SIMATIC PDM and Maintenance Sta-
tion):
• Need for maintenance (green wrench)
• Urgent need for maintenance (yellow wrench)
• Imminent danger of unit failure or general failure (red wrench)
This allows users to put early measures into action in the run-up
to a serious valve or actuator fault, which can prevent an immi-
nent system shutdown. The fact that a fault indication is sig-
naled, such as the onset of a diaphragm break in the actuator or
the progressive sluggishness of a unit, enables the user to en-
sure system reliability at any time by means of suitable mainte-
nance strategies.
This three-stage alarm hierarchy also allows early detection and
signaling of other faults, such as the static friction of a packing
box, the wearing of a valve plug/seating, or precipitations or in-
crustations on the fittings.
These fault indications can be output either line-conducted over
the alarm outputs (see above) of the positioner (max. 3), or via
communication over the HART or fieldbus interfaces. In this
case, the HART, PROFIBUS and FF versions of SIPART PS2 per-
mit a differentiation of the various fault indications, as well as a
trend representation and histogram function of all key process
variables with regard to the fittings.
The LCD of the device also displays the graded maintenance re-
quirements, complete with identification of the source of the fault.
Functional safety acc. to SIL 2
The SIPART PS2 positioners are also suitable for control of fit-
tings, which meet the special requirements of the functional
safety up to SIL 2 to IEC 61508 or IEC 61511-1.
This is a single-action, venting positioner with an input of 4 to
20 mA, PROFIBUS PA and FOUNDATION Fieldbus (FF) for
mounting on pneumatic actuators with spring return.
The positioner vents the valve actuator on demand or in the
event of a fault and puts the valve in the preset safety position.
This positioner meets the following requirements:
• Functional safety up to SIL 2 to IEC 61508 or IEC 61511-1,
from firmware version C4 or higher for safe venting
• Explosion protection for the versions 6DR5...-.E...
• Electromagnetic compatibility to EN 61326/A1, Appendix A.1
SIPART PS 2 as "intelligent solenoid valve"
Open / Close valves, safety fittings in particular, are generally
pneumatically controlled over a solenoid valve. If you use SI-
PART PS2 instead of this type of solenoid valve, the positioner
performs two tasks in a single device (without extra wiring)
• Firstly, it switches the fitting off on demand by venting the ac-
tuator (functional safety acc. to SIL 2 (see above)
• Secondly, it can perform a Partial Stroke Test at regular inter-
vals (1 - 365 days), which prevents the blocking of the fitting,
e.g. due to corrosion or furring.
As in this case SIPART PS2 is constantly working in normal op-
eration (e.g. 99 % position), it also acts as a permanent test func-
tion for the pneumatic output circuit, which is not usually possi-
ble when using a solenoid valve.
Solenoid valves on control valves can also not normally be
tested during operation. They are therefore not necessary when
using SIPART PS 2 with a 4-wire connection system as the vent-
ing is carried out on demand by SIPART PS2. This means that on
control valves, both the control function and the shut-off function
can be carried out by a single device.
Configuring
The following settings, for example, can be configured in config-
uring mode as required with the SIPART PS2 positioner:
• Input current range 0 to 20 mA or 4 to 20 mA
• Rising or falling characteristic at the setpoint input
• Positioning speed limit (setpoint ramp)
• Split-range operation; adjustable start-of-scale and full-scale
values
• Response threshold (dead zone); self-adjusting or fixed
• Direction of action; rising or falling output pressure with rising
setpoint
• Limits (start-of-scale and full-scale values) of positioning
range
• Limits (alarms) of the final control element position; minimum
and maximum values
• Automatic "tight shut-off" (with adjustable response threshold)
• The travel can be corrected in accordance with the valve char-
acteristic.
• Function of binary inputs
• Function of alarm output etc.
The key aspects of configuring the different SIPART PS2 ver-
sions are largely identical.
© Siemens AG 2008
Electropneumatic positioners
SIPART PS2
Technical description
6/7
Siemens FI 01 · 2009
6
SIPART PS2, electropneumatic positioner, function diagram
AD
AD
1
BE1
IW+
IW-
W
y0
x0
+_
W
x
+U
BE2 A1 A2
6
+5 V
+24 V
2
_y
+y
U
UI
5
4
3
pZ
p2
p1
89
p2
p1
p1
_+
p2
p1
A1 A2
7
II
1 Motherboard w th m crocontroller and nput c rcu t
2 Control panel w th LCD and pushbuttons
3 P ezoelectr c valve un t, always present
4 Valve un t, present as accessory n double-act on pos t oner
5 Iy module for SIPART PS2 controller
6 Alarm module for 3 alarm outputs and one b nay nput
Travel
Travel
Exhaust
Exhaust
Inlet a r
HART
M cro-
controller
7 SIA module (slot n t ator alarm module, f g.) or l m t value contact module
8 Spr ng loaded pneumat c actuator (s ngle-act on)
9 Spr ngless pneumat c actuator (double-act on)
Note:
Alarm module (6) and SIA module (7) can only be nserted as alternat ves.
© Siemens AG 2008
Electropneumatic positioners
SIPART PS2
Technical specifications
all versions
6/8 Siemens FI 01 · 2009
6
■
Technical specifications
SIPART PS2 (all versions)
General data
Travel range (linear actuators) 3 ... 130 mm (0.12 ... 5.12 inch)
(angle of feedback shaft 16 ... 90°)
Angle of rotation
(part-turn actuators)
30 ... 100°
Installation
• On linear actuators Using attachment set
6DR4004-8V and where necessary
with an additional lever arm
6DR4004-8L on actuators accord-
ing to IEC 534-6 (NAMUR) with
ribs, bars or flat face
• On part-turn actuators Using attachment set
6DR4004-8D on actuators with
mounting plane according to
VDI/VDE 3845 and DIN 3337:
The required mounting console
has to be provided on the actuator
side; shaft with groove and female
thread M6
Controller
• Five-point switch Self-adjusting
• Dead zone
- dEbA = Auto Self-adjusting or can be set as
fixed value
- dEbA = 0.1 ... 10% Self-adjusting or can be set as
fixed value
A/D converter
• Scan time 10 ms
• Resolution ≤0.05%
• Transmission error ≤0.2%
• Temperature effect ≤0.1%/10 K (≤0.1%/18 °F)
Cycle time
• 20 mA/HART device 20 ms
• PA device 60 ms
• FF device 60 ms (min. loop time)
Binary input BE1 (terminals 9/10;
electrically connected to the basic
device)
Suitable only for floating contact;
max. contact load < 5 mA with 3 V
Degree of protection IP66 to EN 60 529/NEMA 4x
CE marking Conformity as regards EMC Direc-
tive 89/336 EC in accordance with
the following standards
EMC requirements EN 61326/A1 Appendix A.1 and
NAMUR NE21 August 98
Material
• Housing
- 6DR5..0-... (plastic) Glass-fiber-reinforced Macrolon
- 6DR5..1-... (metal) GD AISi12
- 6DR5..2-... (stainless steel) Austenitic stainless steel mat.
No. 1.4581
- 6DR5..5-... (metal, pressure-
proof)
GK AISi12
• Pressure gauge block Aluminium AIMgSi, anodized
Vibration resistance
• Harmonic oscillations
(sine-wave) according to
DIN EN 60062-2-6/05.96
3.5 mm (0.14 inch), 2 ... 27 Hz
3 cycles/axis
98.1 m/s² (321.84 ft/s²),
27 ... 300 Hz, 3 cycles/axis
• Bumping (half-sine)
to DIN EN 60068-2-29/03.95
150 m/s² (492 ft/s²), 6 ms,
1000 shocks/axis
• Noise (digitally controlled)
to DIN EN 60068-2-64/08.95
10 ... 200 Hz; 1 (m/s²)²/Hz
(3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz
(0.98 (ft/s²)²/Hz)
4 hours/axis
• Recommended continuous duty
range of the complete fitting
≤30 m/s² (≤98.4 ft/s²) without res-
onance sharpness
Weight, basic device
• Plastic casing Approx. 0.9 kg (1.98 lb)
• Metal casing, aluminium Approx. 1.3 kg (2.86 lb)
• Metal casing, stainless steel Approx. 3.9 kg (8.58 lb)
• Metal casing EEx d version Approx. 5.2 kg (11.46 lb)
Dimensions See "Dimensional drawings"
Climate class 4 To DIN EN 60721-3-4
• Storage1) 1K5, but -40 ... +80 °C
(1K5, but -40 ... +176 °F)
•Transport
1) 2K4, but -40 ... +80 °C
(2K4, but -40 ... +176 °F)
• Operation2) 4K3, but -30 ... +80 °C3)
(4K3, but -22 ... +176 °F)
Certificate and approvals
Classification according to pres-
sure equipment
directive (DRGL 97/23/EC)
For gases of fluid group 1, com-
plies with requirements of article 3,
paragraph 3 (sound engineering
practice SEP)
Pneumatic data
Power supply Compressed air, nitrogen or
cleaned natural gas
• Pressure 1.4 ... 7 bar (20.3 ... 101.5 psi):
Sufficiently greater than max. drive
pressure (actuating pressure)
Air quality to ISO 8573-1
• Solid particle size and density Class 2
• Pressure dew point Class 2 (min. 20 K (36 °F) below
ambient temperature)
• Oil content Class 2
Unthrottled flow
• Inlet air valve
(ventilate actuator)4)
- 2 bar (29 psi) 4.1 Nm³/h (18.1 USgpm)
- 4 bar (58 psi) 7.1 Nm³/h (31.3 USgpm)
- 6 bar (87 psi) 9.8 Nm³/h (43.1 USgpm)
• Outlet air valve
(exhaust actuator)4)
- 2 bar (29 psi) 8.2 Nm³/h (36.1 USgpm)
- 4 bar (58 psi) 13.7 Nm³/h (60.3 USgpm)
- 6 bar (87 psi) 19.2 Nm³/h (84.5 USgpm)
Valve leakage < 6⋅10-4 Nm³/h (0.0026 USgpm)
Throttle ratio Adjustable up to ∞: 1
Power consumption in the
controlled state
< 3.6⋅10-2 Nm³/h (0.158 USgpm)
Types of actuators
• In casing Single-action and double-action
• In aluminium casing Single-action
• In flameproof casing Single-action and double-action
• In stainless steel casing Single-action and double-action
1) During commissioning at ≤0 °C (≤32 °F) make sure that the valves are
flushed long enough with the dry medium.
2) At ≤-10 °C (14 °F) the display refresh rate of the LCD is limited. Only T4 is
permissible when using Iymodule.
3) -25 ... +75 °C (-13 ... +167 °F) for 6DR55..-0G..., 6DR56..-0G...,
6DR55..-0D... and 6DR56..-0D...
4) With EEx d version (6DR5..5-...) the values are reduced by approx. 20%.
© Siemens AG 2008
Electropneumatic positioners
SIPART PS2
Technical specifications
SIPART PS2
6/9
Siemens FI 01 · 2009
6
■
Technical specifications
SIPART PS2 Basic device
without Ex protection
Basic device
with Ex d protection
(flameproof casing)
Basic device
with Ex ia/ib protection
Basic device
with Ex n/dust protec-
tion
Explosion protection to ATEX Without Ex d
II 2 G Ex d II C T6
Ex ia/ib
II 2 G Ex ia/ib II C T6
Ex n
II 3 G Ex nA nL[nL] IIC T6
Dust
II 3 D Ex tD A22 IP66
T100°C
Mounting location Zone 1 Zone 1 Zone 2/22
Permissible ambient temperature for
operation
At ≤-10 °C (+14 °F) the display refresh
rate of the LCD is limited.
(for basic devices with EEX ia/ib and
EEx n protection the following applies:
Only T4 is permissible when using Iy
module.)
-30 ... +80 °C
(-22 ... +176 °F)
T4: -30 ... +80 °C (-22 ... +176 °F)
T5: -30 ... +65 °C (-22 ... +149 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)
Electrical data
Input
2-wire connection (terminals 6/8)
Rated signal range 4 ... 20 mA 4 ... 20 mA 4 ... 20 mA 4 ... 20 mA
Current to maintain the power supply ≥3.6 mA ≥3.6 mA ≥3.6 mA ≥3.6 mA
Required load voltage
UB(corresponds to Ωat 20 mA)
• Without HART (6DR50..)
- Typical 6.36 V (corresponds to
318 Ω)
6.36 V (corresponds to
318 Ω)
7.8 V (corresponds to
390 Ω)
7.8 V (corresponds to
390 Ω)
- Max. 6.48 V (corresponds to
324 Ω)
6.48 V (corresponds to
324 Ω)
8.3 V (corresponds to
415 Ω)
8.3 V (corresponds to
415 Ω)
• Without HART (6DR53..)
- Typical 7.9 V (corresponds to
395 Ω)
–––
- Max. 8.4 V (corresponds to
420 Ω)
–––
• With HART (6DR51..)
- Typical 6.6 V (corresponds to
330 Ω)
6.6 V (corresponds to
330 Ω)
––
- Max. 6.72 V (corresponds to
336 Ω)
6.72 V (corresponds to
336 Ω)
––
• With HART (6DR52..)
- Typical – 8.4 V (corresponds to
420 Ω)
8.4 V (corresponds to
420 Ω)
8.4 V (corresponds to
420 Ω)
- Max. – 8.8 V (corresponds to
440 Ω)
8.8 V (corresponds to
440 Ω)
8.8 V (corresponds to
440 Ω)
• Static destruction limit ±40 mA – –
Internal capacitance Ci
• Without HART – – 22 nF 22 nF (at "nL")
• With HART – – 7 nF 7 nF (at "nL")
Internal inductance Li
• Without HART – – 0.12 mH 0.12 mH (at "nL")
• With HART – – =0.24 mH 0.24 mH (at "nL")
For connection to power circuits with
the following max. ratings
– – intrinsically safe
Ui= 30 V DC
Ii= 100 mA
Pi= 1 W
at "nA" and "tD":
Un= 30 V DC
In= 100 mA
at "nL":
Ui= 30 V DC
Ii= 100 mA
© Siemens AG 2008
Electropneumatic positioners
SIPART PS2
Technical specifications
SIPART PS2
6/10 Siemens FI 01 · 2009
6
3-/4-wire device (terminals 2/4
and 6/8) (6DR52.. and 6DR53..)
• Power supply UH18 ... 35 V DC 18 ... 35 V DC 18 ... 30 V DC 18 ... 30 V DC
• Current consumption IH(UH- 7.5 V)/2.4 kΩ[mA] (UH- 7.5 V)/2.4 kΩ[mA] (UH- 7.5 V)/2.4 kΩ[mA] (UH- 7.5 V)/2.4 kΩ[mA]
• Internal capacitance Ci––≤22 nF –
• Internal inductance Li––≤0.12 mH –
For connection to power circuits with
the following max. ratings
– – intrinsically safe
Ui = 30 V DC
Ii = 100 mA
Pi = 1 W
Un = 30 V DC
In = 100 mA
at "nL":
Ui = 30 V DC
Ii = 100 mA
Current input IW
Rated signal range 0/4 ... 20 mA 0/4 ... 20 mA 0/4 ... 20 mA 0/4 ... 20 mA
Load voltage at 20 mA ≤0.2 V (corresponds to
10 Ω)
≤0.2 V (corresponds to
10 Ω)
≤1 V (corresponds to
50 Ω)
≤1 V (corresponds to
50 Ω)
Internal capacitance Ci– – 22 nF 22 nF (at "nL")
Internal inductance (Li) – – 0.12 mH 0.12 mH (at "nL")
For connection to power circuits with
the following max. ratings
– – intrinsically safe
Ui = 30 V DC
Ii = 100 mA
Pi = 1 W
at "nA" and "tD":
Un = 30 V DC
In = 100 mA
at "nL":
Ui = 30 V DC
Ii = 100 mA
Electrical isolation between UHand IWbetween UHand IWbetween UHand IW
(2 intrinsically safe cir-
cuits)
between UHand IW
Test voltage 840 V DC (1 s) 840 V DC (1 s) 840 V DC (1 s) 840 V DC (1 s)
Connections
• Electric Screw terminals 2.5
AWG28-12
Cable gland M20 x 1.5 or
½-14 NPT
Screw terminals 2.5
AWG28-12
EEx d certified cable
gland M20 x 1.5,
½-14 NPT or M25 x 1.5
Screw terminals 2.5
AWG28-12
Cable gland M20 x 1.5 or
½-14 NPT
Screw terminals 2.5
AWG28-12
Cable gland M20 x 1.5 or
½-14 NPT
• Pneumatic Female thread G¼ DIN
EN ISO 228-1 or ¼-18
NPT
Female thread G¼ DIN
EN ISO 228-1 or ¼-18
NPT
Female thread G¼ DIN
EN ISO 228-1 or ¼-18
NPT
Female thread G¼ DIN
EN ISO 228-1 or ¼-18
NPT
External position sensor (potentiometer or NCS; as option) with the following max. ratings
•U
o––5V5V
• Io (static) – – 75 mA 75 mA
•I
s (short-time) – – 160 mA -
•P
o– – 120 mW 120 mW
Maximum permissible external capaci-
tance Co
––1μF1μF
Maximum permissible external induc-
tance Lo
– – 1 mH 1 mH
SIPART PS2 Basic device
without Ex protection
Basic device
with Ex d protection
(flameproof casing)
Basic device
with Ex ia/ib protection
Basic device
with Ex n/dust protec-
tion
© Siemens AG 2008