Simplex 4100-5116 User manual

Expansion Signal (XSIG) Card
Installation Instructions
2005,-2011 SimplexGrinnell LP. All rights reserved.
Specifications and other information shown were current as of publication and are subject to change without notice.
Simplex and the Simplex logo are trademarks of Tyco International Ltd. and its affiliates and are used under license.
579-516
Rev. E
This publication describes the installation procedure for the Expansion Signal (XSIG) Card
(4100-5116).
This product is compatible with 4100U and 4100ES Fire Alarm Control Panels (FACP).
IMPORTANT: Verify FACP System Programmer, Executive, and Slave Software
compatibility when installing, or replacing system components. Refer to
the Technical Support Information and Downloads website for
compatibility information..
This publication discusses the following topics:
Topic See Page
Cautions, Warnings, and Regulatory Information 2
Introduction to the Expansion Signal Card 3
Installing the Expansion Signal Card onto the PDI 6
Card Configuration 7
Wiring 9
Troubleshooting 16
Introduction
In this Publication
firealarmresources.com

2
Cautions and
Warnings
READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation
manual. These instructions must be followed to avoid damage to this product and associated
equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED- Upon
unpacking your Simplex product, inspect the contents of the carton for shipping damage. If
damage is apparent, immediately file a claim with the carrier and notify an authorized
Simplex product supplier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjust-
ments or repairs. All repairs should be performed by a representative or authorized agent of
your local Simplex product supplier.
EYE SAFETY HAZARD - Under certain fiber optic application conditions, the optical output
of this device may exceed eye safety limits. Do not use magnification (such as a microscope
or other focusing equipment) when viewing the output of this device.
STATIC HAZARD - Static electricity can damage components. Handle as follows:
Ground yourself before opening or installing components.
Prior to installation, keep components wrapped in anti-static material at all times.
FCC RULES AND REGULATIONS – PART 15 - This equipment has been tested and found to
comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of
this equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES -To ensure proper
system operation, this product must be tested in accordance with NFPA 72® after any
programming operation or change in site-specific software. Reacceptance testing is required
after any change, addition or deletion of system components, or after any modification, repair
or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a
change must be 100% tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that are not directly affected by the
change, up to a maximum of 50 devices, must also be tested and proper system operation
verified.
NFPA 72® is a registered trademark of the National Fire Protection Association.
Cautions, Warnings, and Regulatory Information
firealarmresources.com

3
The Expansion Signal (XSIG) Card provides three additional NACs for use with either an
Amplifier Audio NAC or a power supply card (SPS, RPS, and XPS). When an XSIG Card is
added for audio NAC expansion, the card is programmed for operation with the specific amplifier
that it is expanding.
Each XSIG card must be dedicated to provide either all Audio or all DC notification; these
operations cannot be mixed.
Functions of the XSIG Card
1. Provides three 1.5 A Class B NACs for Audio or DC notification.
2. Switches between two power audio input sources (for example,
Flex-35/Flex-50-style dual-channel power stage switching).
3. Accepts Class A Adapter and Class B Expander for a total of six Class B NACs or
three Class A NACs per card that can be used with audio or DC signaling.
4. Accepts constant supervision audio NAC module for a total of three Constant
Supervision NACs per card for use with audio signaling only.
5. When configured for use with non-alarm audio, quickly and automatically switches
to an audio source when a signal is detected at either input.
6. Supports earth fault isolation in conjunction with the source NAC supplying the card
input.
The XSIG Card also supports the WALKTEST system test as long as the following programming
guidelines are followed:
Custom Control must be written to turn on the NACs when the “WALKTEST Group
Active” pseudo turns ON.
Lists can be created for the NACs to allow you to have them turn ON when different
groups are activated. However, a Custom Control equation would be required for
each WALKTEST group.
Optional equipment to accompany the XSIG card consists of the following:
4100-1266 Expansion Signal (XSIG) Card XNAC (increases the quantity of Class B
NACs from three to six)
4100-1267 Expansion Signal (XSIG) Card Class A Adapter (upgrades the three on-
card NACs to Class A)
4100-1268 Expansion Signal (XSIG) Constant Supervision NAC (replaces the on-card
NACs with 3 Class A/B Constant Supervision NACs
Continued on next page
Introduction to the Expansion Signal Card
Overview
Optional Equipment
firealarmresources.com

4
PDI CONNECTOR
(reverse side)
Figure 1 is an illustration of the Expansion Signal (XSIG) card.
NAC1
B+ B- SHLD SHLD IN1+ IN1-
ADDRESS
P3
OUT IN
EOLR
P4
OUT IN
F1
2.5 A 250V
2.5 A 250V
2.5 A 250V
F2
F3
NAC1 IN2->NAC1
IN2->NAC2
IN2->NAC3
COMM TBL
NAC2
NAC3
BAUD
ADDRESS
MSB
LSB
IN1 IN2
IN2+ IN2-
B-
NAC2
B+ B-
NAC3
B+
LED3
LED7
LED5
LED2
LED4
LED6
LED8
Figure 1. XSIG Card
Continued on next page
Introduction to the Expansion Signal Card,
Continued
Expansion Signal
(XSIG) Card
Illustration
LEDs (2 THROUGH 8)
EOLR JUMPER
FOR INPUT 2 (P4)
EOLR JUMPER
FOR INPUT 1 (P3)
ADDRESS
CONFIGURATION
DIP SWITCH (SW1)
firealarmresources.com

5
The XSIG card is a 4100 Comm slave according to the 4100 slave architecture. The card plugs
onto the Power Distribution Interface (PDI) that supplies card power and 4100 Comm
communications.
LEDs on the XSIG card are used to indicate card status. See Table 1.
Table 1. Status LEDs
*LED No. Use Interpretation Color
2 On when the amplifier is not
communicating with the system CPU ON Steadily during comm loss; flashing during
firmware failure. Yellow
3 Status of audio NAC 1 ON Steadily when NAC is ON;
ON Steadily when NAC detects trouble. Yellow
4 NAC1 routing relay status = routed
to Input 2 (audio use only) ON Steadily when NAC1 is routed to Input 2. Green
5 Status of audio NAC 3 ON Steadily when NAC is ON;
ON Steadily when NAC detects trouble. Yellow
6 NAC2 routing relay status = routed
to Input 2 (audio use only) ON Steadily when NAC2 is routed to Input 2. Green
7 Status of audio NAC 2 ON Steadily when NAC is ON;
ON Steadily when NAC detects trouble. Yellow
8 NAC3 routing relay status = routed
to Input 2 (audio use only) ON Steadily when NAC3 is routed to Input 2. Green
*
LED1 is not provided on the XSIG card.
Refer to Table 2 for electrical and environmental requirements.
Table 2. Electrical and Environmental Specifications
Electrical Specifications
Voltage 24 VDC from FACP (19-32 VDC)
Power Requirements
Supervision
Current 20 mA
Alarm Current 52 mA – Power Supply or 100 W Amplifier
80 mA – Flex-35 or Flex-50 Amplifier
NAC Specifications
DC Use 1.5 A maximum
Audio Use 1.5 A maximum, 50 W, OR 100 speakers (whichever comes first)
Environmental Specifications
Operating
Temperature 32to 120F (0to 49C)
Humidity Up to 93% relative humidity at 90F (32C)
Introduction to the Expansion Signal Card,
Continued
XSIG Card Receives
Power and
Communications
from PDI
XSIG Card LEDs
Requirements
and Limitations
firealarmresources.com

6
The Expansion Signal (XSIG) card mounts on the Power Distribution Interface (PDI). The module
can be mounted on any of the PDI connectors.
Use connector P4, labeled on the backside of the given card, to connect to any of the eight PDI
connectors as shown in Figure 2 below.
Note: Figure 2 is a general-purpose illustration that applies to most
4-inch (102 mm) X 5-inch (127 mm) cards.
Figure 2. Mounting onto the Power Distribution Interface (PDI)
Installing the Expansion Signal Card onto the PDI
Overview
XSIG CARD
STANDOFFS
#6 SCREWS
WASHERS
PDI CONNECTOR
(reverse side) PDI
firealarmresources.com

7
This section contains instructions on configuring the XSIG card via jumpers and DIP switches.
These jumpers are used to connect an end-of-line resistor to the inputs when the card is installed as
the last in the line of XSIG cards. The default position is OUT (Positions 1-2).
P3
Input 1: Position 2-3 (IN) when last in line of XSIG cards; otherwise, Position 1-2 (OUT).
P4
Input 2: Position 2-3 (IN) when last in line of XSIG cards; otherwise, Position 1-2 (OUT).
Switch SW1 on the XSIG card is an eight-position DIP switch. From left to right (see Figure 3
below) these switches are designated as SW1-1 through SW1-8. The function of these switches is
as follows:
SW1-1. This switch sets the baud rate for the internal 4100 communications line running
between the card and the 4100 CPU. Set this switch to ON.
SW1-2 through SW1-8. These switches set the card’s address within the 4100 FACP.
Refer to Table 3 for a complete list of the switch settings for all of the possible card addresses.
Note: You must set these switches to the value assigned to the card by the
Programmer.
1
8
7
6
5
4
3
2
Figure 3. DIP Switch SW1
Continued on next page
Card Configuration
Overview
Setting the EOLR
Jumpers (P3 & P4)
Setting the Device
Address and Baud
Rate (SW1)
ON
OFF
DIP Switches SW1-2 through
SW1-8 set the Card Address.
Figure 3 shows an Address of 3.
4100 Comm. Baud Rate.
Switch (SW1-1)
Must Be Set to ON
firealarmresources.com

8
Table 3. XSIG Card Addresses
Card Configuration,
Continued
Setting the Device
Address and Baud
Rate (SW1),
(continued)
Address SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW 1-8 Address SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW 1-8
1 ON ON ON ON ON ON OFF 61 ON OFF OFF OFF OFF ON OFF
2 ON ON ON ON ON OFF ON 62 ON OFF OFF OFF OFF OFF ON
3 ON ON ON ON ON OFF OFF 63 ON OFF OFF OFF OFF OFF OFF
4 ON ON ON ON OFF ON ON 64 OFF ON ON ON ON ON ON
5 ON ON ON ON OFF ON OFF 65 OFF ON ON ON ON ON OFF
6 ON ON ON ON OFF OFF ON 66 OFF ON ON ON ON OFF ON
7 ON ON ON ON OFF OFF OFF 67 OFF ON ON ON ON OFF OFF
8 ON ON ON OFF ON ON ON 68 OFF ON ON ON OFF ON ON
9 ON ON ON OFF ON ON OFF 69 OFF ON ON ON OFF ON OFF
10 ON ON ON OFF ON OFF ON 70 OFF ON ON ON OFF OFF ON
11 ON ON ON OFF ON OFF OFF 71 OFF ON ON ON OFF OFF OFF
12 ON ON ON OFF OFF ON ON 72 OFF ON ON OFF ON ON ON
13 ON ON ON OFF OFF ON OFF 73 OFF ON ON OFF ON ON OFF
14 ON ON ON OFF OFF OFF ON 74 OFF ON ON OFF ON OFF ON
15 ON ON ON OFF OFF OFF OFF 75 OFF ON ON OFF ON OFF OFF
16 ON ON OFF ON ON ON ON 76 OFF ON ON OFF OFF ON ON
17 ON ON OFF ON ON ON OFF 77 OFF ON ON OFF OFF ON OFF
18 ON ON OFF ON ON OFF ON 78 OFF ON ON OFF OFF OFF ON
19 ON ON OFF ON ON OFF OFF 79 OFF ON ON OFF OFF OFF OFF
20 ON ON OFF ON OFF ON ON 80 OFF ON OFF ON ON ON ON
21 ON ON OFF ON OFF ON OFF 81 OFF ON OFF ON ON ON OFF
22 ON ON OFF ON OFF OFF ON 82 OFF ON OFF ON ON OFF ON
23 ON ON OFF ON OFF OFF OFF 83 OFF ON OFF ON ON OFF OFF
24 ON ON OFF OFF ON ON ON 84 OFF ON OFF ON OFF ON ON
25 ON ON OFF OFF ON ON OFF 85 OFF ON OFF ON OFF ON OFF
26 ON ON OFF OFF ON OFF ON 86 OFF ON OFF ON OFF OFF ON
27 ON ON OFF OFF ON OFF OFF 87 OFF ON OFF ON OFF OFF OFF
28 ON ON OFF OFF OFF ON ON 88 OFF ON OFF OFF ON ON ON
29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF
30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON
31 ON ON OFF OFF OFF OFF OFF 91 OFF ON OFF OFF ON OFF OFF
32 ON OFF ON ON ON ON ON 92 OFF ON OFF OFF OFF ON ON
33 ON OFF ON ON ON ON OFF 93 OFF ON OFF OFF OFF ON OFF
34 ON OFF ON ON ON OFF ON 94 OFF ON OFF OFF OFF OFF ON
35 ON OFF ON ON ON OFF OFF 95 OFF ON OFF OFF OFF OFF OFF
36 ON OFF ON ON OFF ON ON 96 OFF OFF ON ON ON ON ON
37 ON OFF ON ON OFF ON OFF 97 OFF OFF ON ON ON ON OFF
38 ON OFF ON ON OFF OFF ON 98 OFF OFF ON ON ON OFF ON
39 ON OFF ON ON OFF OFF OFF 99 OFF OFF ON ON ON OFF OFF
40 ON OFF ON OFF ON ON ON 100 OFF OFF ON ON OFF ON ON
41 ON OFF ON OFF ON ON OFF 101 OFF OFF ON ON OFF ON OFF
42 ON OFF ON OFF ON OFF ON 102 OFF OFF ON ON OFF OFF ON
43 ON OFF ON OFF ON OFF OFF 103 OFF OFF ON ON OFF OFF OFF
44 ON OFF ON OFF OFF ON ON 104 OFF OFF ON OFF ON ON ON
45 ON OFF ON OFF OFF ON OFF 105 OFF OFF ON OFF ON ON OFF
46 ON OFF ON OFF OFF OFF ON 106 OFF OFF ON OFF ON OFF ON
47 ON OFF ON OFF OFF OFF OFF 107 OFF OFF ON OFF ON OFF OFF
48 ON OFF OFF ON ON ON ON 108 OFF OFF ON OFF OFF ON ON
49 ON OFF OFF ON ON ON OFF 109 OFF OFF ON OFF OFF ON OFF
50 ON OFF OFF ON ON OFF ON 110 OFF OFF ON OFF OFF OFF ON
51 ON OFF OFF ON ON OFF OFF 111 OFF OFF ON OFF OFF OFF OFF
52 ON OFF OFF ON OFF ON ON 112 OFF OFF OFF ON ON ON ON
53 ON OFF OFF ON OFF ON OFF 113 OFF OFF OFF ON ON ON OFF
54 ON OFF OFF ON OFF OFF ON 114 OFF OFF OFF ON ON OFF ON
55 ON OFF OFF ON OFF OFF OFF 115 OFF OFF OFF ON ON OFF OFF
56 ON OFF OFF OFF ON ON ON 116 OFF OFF OFF ON OFF ON ON
57 ON OFF OFF OFF ON ON OFF 117 OFF OFF OFF ON OFF ON OFF
58 ON OFF OFF OFF ON OFF ON 118 OFF OFF OFF ON OFF OFF ON
59 ON OFF OFF OFF ON OFF OFF 119 OFF OFF OFF ON OFF OFF OFF
60 ON OFF OFF OFF OFF ON ON
firealarmresources.com

9
This section describes wiring for the XSIG card. Audio NAC, DC NAC, Amplifier (Constant and
Non-Constant Supervision), and Power Supply Wiring are included.
Make sure these prerequisites are accounted for before installing the cards:
Conductors must test free of all grounds.
All wires must be between 18 AWG (0.8231 mm
2
) and 12 AWG (3.309 mm
2
), or as the
local code dictates.
“T” tapping is not permitted for any field wiring.
Continued on next page
Wiring
Overview
Wiring Guidelines
firealarmresources.com

10
IN1+
IN1-
IN2+
IN2-
SHLD
SHLD
SHLD
SHLD
A+
A-
A+
A-
A+
A-
B+
B-
B+
B-
B+
B-
EOLR
NAC1 NAC2 NAC3
NAC1 NAC2 NAC3
IN1 IN2NAC1 NAC2 NAC3 IN1 IN2
SPEAKER
SPEAKER
SPEAKER
CLASS A WIRING
SHIELD
NOTE 1
EOLR
NOTE 1
4100-5116 Expansion Signal Card
4100-1267 Class A Adapter
To Source
NAC(s)
B+
B-
IN1+
IN1-
IN2+
IN2-
B+
B-
B+
B-
B+
B-
SHLD
B+
B-
SHLD
SHLD
SHLD
B+
B-
EOLR
EOLR
EOLR
NAC1 NAC2 NAC3
EOLR
EOLR
SPEAKER
SPEAKER
SPEAKER
EOLR
SPEAKER
SPEAKER
SPEAKER
4081-9008
EOL HARNESS
10 K 1/2 W
4081-9008
EOL HARNESS
10 K 1/2 W
CLASS B WIRING
SHIELD
SHIELD
NOTE 1
NOTE 1
4100-1266 Class B Expander (option)
4100-5116 Expansion Signal Card To Source
NAC(s)
NOTE 1
NOTE 1
Provide Audio NAC wiring without Constant Supervision as shown in Figure 4.
Figure 4. Audio NAC Wiring (without Constant Supervision)
Continued on next page
Wiring,
Continued
Audio NAC Wiring
(without Constant
Supervision)
1. Leave the 10 K, ½ W resistors (378-030 – brown/black/orange) on the “B+” and “B-” terminals of
unused circuits.
2. All wiring is between 18 AWG (0.8231 mm
2
) (minimum) and 12 AWG (3.309 mm
2
) (maximum).
3. Field wiring is power-limited.
4. Maximum speaker load per NAC is 50 W. Maximum current per NAC is 1.5 A. Maximum number of
speakers per NAC is 100.
5. Shields, when required, are normally connected to 0 V as shown. Alternate shield termination using
earth ground is provided on amplifier chassis.
6. Si
g
nal wirin
g
must test free of all
g
rounds.
firealarmresources.com

11
B+
A+
A-
B-
SHLD
B+
A+
A-
B-
B+
A+
A-
B-
SHLD
SHLD
SHLD
SHLD
SHLD
B+
A+
A-
B-
SHLD
B+
A+
A-
B-
B+
A+
A-
B-
SHLD
SHLD
SHLD
SHLD
SHLD
SPEAKER
EOLR
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
NAC1 NAC2 NAC3
NAC1 NAC2 NAC3
EOLR
SHIELD
SHIELD
CLASS A WIRING
CLASS B WIRING
NOTE 1
EOLR
NOTE 1
EOLR
NOTE 1
EOLR
NOTE 1
4100-1268: XSIG Constant Supervision NAC Adapter Card
4100-1268: XSIG Constant Supervision NAC Adapter Card
For 25 V Systems, use 4081-9008 EOL Harness 10 K 1/2 W
For 70 V Systems, use 4081-9008 EOL Harness 10 K 1/2 W
4100-5116 XSIG CARD
4100-5116 XSIG CARD
Provide Audio NAC wiring with Constant Supervision as shown in Figure 5.
Figure 5. Audio NAC Wiring (with Constant Supervision)
Continued on next page
Wiring,
Continued
Audio NAC Wiring
(with Constant
Supervision)
1. Leave the 10 K, ½ W resistors (378-030 – brown/black/orange) on the “B+” and “B-” terminals of
unused circuits.
2. Remove the 10 K resistors from the “B+” and “B-” terminals on the XSIG card.
3. All wiring is between 18 AWG (0.8231 mm
2
) (minimum) and 12 AWG (3.309 mm
2
) (maximum).
4. Field wiring is power-limited.
5. Maximum speaker load per NAC is 50 W. Maximum current per NAC is 1.4 A. Maximum number of
speakers per NAC is 100.
6. Shields, when required, are normally connected to 0 V as shown. Alternate shield termination using
earth ground is provided on amplifier chassis.
7. Signal wiring must test free of all grounds.
firealarmresources.com

12
B+
B-
SHLD
B+
B-
SHLD
B+
B-
A+
A-
SHLD
A+
A-
SHLD
A+
A-
NAC1 NAC2 NAC3 IN1 IN2 NAC1 NAC2 NAC3 IN1 IN2
B+
B-
IN1+
IN1-
IN2+
IN2-
B+
B-
B+
B-
SHLD
SHLD
B+
B-
IN1+
IN1-
IN2+
IN2-
B+
B-
B+
B-
SHLD
SHLD
EOLR
EOLR
NAC1 NAC2 NAC3 NAC1 NAC2 NAC3
EOLR EOLR
4081-9008
EOL HARNESS
10 K 1/2 W
4081-9008
EOL HARNESS
10 K 1/2 W
TYPICAL
APPLIANCE
TYPICAL
APPLIANCE
TYPICAL
APPLIANCE
TYPICAL
APPLIANCE
TYPICAL
APPLIANCE
TYPICAL
APPLIANCE
TYPICAL
APPLIANCE
TYPICAL
APPLIANCE
TYPICAL
APPLIANCE
CLASS B WIRING CLASS A WIRING
NOTE 1 NOTE 1
EOLR EOLR
NOTE 1 NOTE 1
EOLR EOLR
NOTE 1 NOTE 1
4100-1266 Class B Expander (option)
4100-5116 Expansion Signal Card
4100-1245 Class A Adapter
4100-5116 Expansion Signal Card
To Source
NAC
To Source
NAC
Provide DC NAC wiring as shown in Figure 6.
Figure 6. DC NAC Wiring
Continued on next page
Wiring,
Continued
DC NAC Wiring
1. Leave the 10 K, ½ W resistors (378-030 – brown/black/orange) on the “B+” and “B-” terminals of
unused circuits.
2. All wiring is between 18 AWG (0.8231 mm
2
) (minimum) and 12 AWG (3.309 mm
2
) (maximum).
3. Field wiring is power-limited.
4. Maximum current is 1.5 A per NAC. Total NAC capacity is 3 A as limited by the source NAC rating.
5. Signal wiring must test free of all grounds.
4100-1267 Class A Adapter
firealarmresources.com

13
NAC1
B+
B-
SHLD
IN1+
IN1-
P3
OUT IN
EOLR
P4
OUT IN
IN1 IN2
IN2+
IN2-
NAC2 NAC3
Note 3
B+
B-
SHLD
B+
B-
IN1 IN2
4100-5116 Expansion Signal Card
NAC1
B+
B-
SHLD
NAC2
B+
B-
100W Amplifier
NAC1
B+
B-
SHLD
IN1+
IN1-
P3
OUT IN
EOLR
P4
OUT IN
IN1 IN2
IN2+
IN2-
NAC2 NAC3
Note 3
B+
B-
SHLD
B+
B-
IN1 IN2
4100-5116 Expansion Signal Card
Notes 2, 5
Note 4
Note 1
Notes:
1. Up to 5 XSIG cards allowed per source NAC.
2. XSIG cards must be in same unit as the source NACs.
3. Last XSIG card in chain requires EOLR Jumpers P3 & P4 to
be installed in the IN position (2-3); otherwise, jumpers are installed in OUT position.
4. The source NAC is wired in a Class B configuration even when the source NAC is configured as Class A.
5. Minimum wire gauge is 18 AWG (0.8231 mm
2
).
Note 4
B-
B+
NAC2
SHLD
B-
B+
NAC1
Flex-35 / Flex-50 Amplifier
IN1+
IN1-
IN2+
IN2-
NAC3
SHLD
B+
B-
IN1 IN2
Notes 2, 5
Note 1
NAC1
B+
B-
SHLD
IN1+
IN1-
P3
OUT IN
EOLR
P4
OUT IN
IN1 IN2
IN2+
IN2-
NAC2 NAC3
Note 3
P3
OUT IN
EOLR
P4
OUT IN
IN1 IN2
Note 3
B+
B-
SHLD
B+
B-
IN1 IN2
4100-5116 Expansion Signal Card 4100-5116 Expansion Signal Card
Source NAC
B+
B-
SHLD
B+
B-
NAC1 NAC2
Notes 4,6
Provide wiring to an amplifier (without constant supervision) as shown in Figure 7.
Figure 7. Wiring to an Amplifier (Without Constant Supervision)
Continued on next page
Wiring,
Continued
Wiring to Amplifiers
(without Constant
Supervision)
firealarmresources.com

14
Notes:
1. Up to 5 XSIG cards allowed per source NAC.
2. XSIG cards must be in same location as the source NACs.
3. Last XSIG card in chain requires EOLR Jumpers P3 & P4 to
be installed in the IN position (2-3); otherwise, jumpers are installed in OUT position.
4. The source NAC is dedicated to providing a signal to the XSIG card and is wired in a Class B configuration.
5. Minimum wire gauge is 18 AWG (0.8231 mm2).
6. Remove the 10 k, 1/2W EOL resistors from the amplifiers and XSIG Cards that accept the Constant Supervision NAC modules.
B-
B+
NAC2
SHLD
B-
B+
NAC1
Notes 2, 5
Note 1
Constant Supervision NAC card
removed to install Source NAC wiring.
Constant Supervision NACs 1&2
(if installed) are not available for use
when configured as Source NACs.
Constant Supervision NAC card
removed to install Source NAC wiring.
Constant Supervision NACs 1
(if installed) are not available for use
when configured as Source NACs.
IN1+
IN1-
IN2+
IN2-
NAC3
SHLD
B+
B-
IN1 IN2
Notes 2, 5
Note 1
NAC1
B+
B-
SHLD
IN1+
IN1-
P3
OUT IN
EOLR
P4
OUT IN
IN1 IN2
IN2+
IN2-
NAC2 NAC3
Note 3
P3
OUT IN
EOLR
P4
OUT IN
IN1 IN2
Note 3
P3
OUT IN
EOLR
P4
OUT IN
IN1 IN2
Note 3
P3
OUT IN
EOLR
P4
OUT IN
IN1 IN2
Note 3
B+
B-
SHLD
B+
B-
B-
B+
SHLD
B-
B+
IN1+
IN1-
IN2+
IN2-
SHLD
B+
B-
B+
B-
SHLD
IN1+
IN1-
IN2+
IN2-
B+
B-
SHLD
B+
B-
IN1 IN2
NAC2
NAC1 NAC3 IN1 IN2NAC1 NAC2 NAC3 IN1 IN2
4100-5116 Expansion Signal Card
(Constant Supervision NAC removed to install
Source NAC wiring)
4100-5116 Expansion Signal Card
(Constant Supervision NAC removed to install
Source NAC wiring)
4100-5116 Expansion Signal Card
(Constant Supervision NAC removed to install
Source NAC wiring)
4100-5116 Expansion Signal Card
(Constant Supervision NAC removed to install
Source NAC wiring)
Flex-35 / Flex-50 Amplifier
25/70 V
Analog/Digital Source NAC
Source NAC
B+
B-
SHLD
B+
B-
B+
B-
SHLD
B+
B-
NAC1
NAC1
NAC2
Notes 4,6
Notes 4,6
Provide wiring to an amplifier (with Constant Supervision NACs) as shown in Figure 8.
Figure 8. Wiring to an Amplifier (With Constant Supervision NACs)
Continued on next page
Wiring,
Continued
Wiring to Amplifiers
(with Constant
Supervision NACs)
firealarmresources.com

15
4100-5116 Expansion Signal Card
Note 2
SOURCE NAC
B+
B-
A+
A-
SPS/RPS/XPS NAC
Note 6
Notes 3, 5
Note 1
4100-5116 Expansion Signal Card
Note 2
NAC1
B+
B-
SHLD
IN1+
IN1-
P3
OUT IN
EOLR
P4
IN1 IN2
IN2+
IN2-
NAC2 NAC3
Note 4
B+
B-
SHLD
B+
B-
IN1 IN2NAC1
B+
B-
SHLD
IN1+
IN1-
P3
OUT IN
EOLR
P4
IN1 IN2
IN2+
IN2-
NAC2 NAC3
Note 4
B+
B-
SHLD
B+
B-
IN1 IN2
Notes 3, 5
Provide wiring to power supply-mounted DC NACs as shown in Figure 9.
Figure 9. Wiring to Power Supply NACs
Wiring,
Continued
Wiring to Power
Supply NACs
1. Up to 5 XSIG cards are allowed per source NAC.
2. XSIG cards must be in same location as the source NAC.
3. The source NAC does not supervise for shorts during standby; short circuit supervision is provided by
the XSIG NACs.
4. The EOLR Jumper P3 is installed in the IN position (2-3) for the last card in the chain.
5. The power supply source NAC is always wired in a Class B configuration even when the NAC is
configured as Class A.
6. All wiring is between 18 AWG (0.8231 mm
2
) (minimum) and 12 AWG (3.309 mm
2
) (maximum).
firealarmresources.com

579-516
Rev. E
This section describes possible causes of trouble messages that can appear on the FACP display.
Trouble messages appear on the left as titles, and possible causes are listed to the right in the text.
Trouble message appears when the XSIG card loses communications with the panel master.
Trouble message appears when the XSIG card does not match the card type configured by the
Programmer.
Open Circuit Troubles apply to opens on all wiring.
Short Circuit Troubles apply to shorts on all wiring.
Troubleshooting
Overview
Card Missing/Failed
Trouble
Wrong Card Trouble
Short/Open Circuit
Trouble
firealarmresources.com
Table of contents
Other Simplex Computer Hardware manuals

Simplex
Simplex Aval PKW1100 User manual

Simplex
Simplex SafeLINC 4120 User manual

Simplex
Simplex 4100-3109 IDNet 2 User manual

Simplex
Simplex 4100-5124 User manual

Simplex
Simplex 4100-3115 XALIC Installation guide

Simplex
Simplex 4001-9813 User manual

Simplex
Simplex XSIG User manual

Simplex
Simplex 4100-3101 User manual

Simplex
Simplex XPS User manual
Popular Computer Hardware manuals by other brands

CommTech
CommTech FASTCOM IG232/2-PCI Hardware reference manual

Acrosser Technology
Acrosser Technology AR-B1651 user guide

mikroElektronika
mikroElektronika LV24-33 v6 user manual

ADLINK Technology
ADLINK Technology COM Express nanoX-TC user manual

AMD
AMD Turion 64 X2 Product data sheet

TYAN
TYAN TS65-B7120 Service engineer's manual