Thank you for purchasing our smoke alarm!
Please read these instrucons carefully and store them in a safe place
where you can access them easily.
Product descripon and intended use
This is a smoke alarm with an opcal sensor for installaon in residenal
buildings, apartments and rooms with residenal-like use. Smoke alarms
are designed to provide an early warning of fire smoke and fires to
persons present, so that these persons can react appropriately to the
hazardous event. Always consult local regulaons for smoke alarms.
Product specificaons
Detecon method : Opcal
Power supply : Mains powered with back-up baery
Voltage : AC 220-240 V~
Current consumpon : <100mA
Mains frequency : 50 Hz
Baery lifeme : >1 year
Recommended baeries : 1. Gold Peak GP1604S (9V DC)
: 2. Gold Peak GP1604A (9V DC)
: 3. Raymax 6LR61 (9V DC)
: 4. EVE CR9V/P (9V DC)
Alarm volume : > 85 dB (A) at 3 meters
Alarm sensivity : 0,095 - 0,175 dB/m
Monitored area : 20 - 40 m²
Operang temperature : 0 °C - 40 °C
Operang humidity : < 93 %
Date of replacement : See product label
Individual alarm indicator : Yes
Alarm silence facility : Yes | Hush me: 8 minutes
Low baery warning : Yes
Installaon in leisure
accommodaon vehicles : No
Mounng locaon : Ceiling
Interconnectable : Yes | Max amount: 12
Type of wires : 0,8mm² – 1,5mm² or according local
wiring standard
Warnings:
ŸTo prevent injury, this apparatus must be securely aached to the
ceiling in accordance with the installaon instrucons.
ŸBaeries should not be exposed to excessive heat such as sunshine,
fire or the like.
• Do not paint or cover the smoke alarm.
• The apparatus shall not be exposed to dripping or splashing and no
objects filled with liquids, such as vases, shall be placed on the
apparatus.
• The smoke alarm, together with any associated supply and
interconnect wiring, shall be installed in accordance with appropriate
naonal electrical installaon regulaons.
Where to install a smoke alarm
Smoke alarms must be installed in such a way that they can be reached
unhindered by the fire smoke so that fires can be reliably detected during
the development phase.
• Install at least in sleeping areas (especially children's rooms);
• Install at least in escape rooms;
• In the middle of the ceiling of a room;
• At least 50 cm away from the wall and other objects;
• Maximum installaon height of 6 meter.
Where to install a smoke alarm in rooms
with special geometries
• Corridors with a maximum width of 3m: Max. 15m between 2 smoke
alarms. Max. 7,5m to the front side of the gallery and smoke alarms at
edges/crossings of corridors.
• Rooms with sloping ceilings:
- If the ceiling inclinaon is > 20° to the horizontal: Smoke
alarms must be installed at least 0.5 m and at most 1 m
from the ceiling top.
- Paral roof slopes: If the flat ceiling is ≤ 1m wide, consider
as ceiling inclinaon is of > 20°. If the flat ceiling is >1m
wide, consider as flat ceiling.
• Rooms with subdivided ceilings:
- Height of the subdivisions is ≤ 0.2 m: Beams without consideraon;
smoke alarm may be installed on the beams as well as on the
ceiling.
- Height of subdivisions is > 0.2 m and area of ceiling panels > 36 m²
: Smoke alarm should be installed in each ceiling panel.
- Height of subdivisions > 0.2 m and area of ceiling panels ≤ 36 m²
: Individual ceiling without consideraon.
Where not to install a smoke alarm
• In an environment with a high risk of draught (e.g. close to air
condioning, fans and venlaon outlets). The movement of air can
impair the penetraon of fire smoke into the smoke alarm.
• Areas where combusons regularly occurs, such as kitchens.
• Areas with high humidity such as bathrooms, or close to devices such
as dish washers or washing machines.
Acvaon
• Before commissioning the smoke alarm, it is important to acvate it
and test it for correct operaon.
• Open the baery compartment and place the baery. Connect the +
on the baery to the + on the baery compartment and the - baery
to the - on the baery compartment. Close the baery cover.
• Test the correct acvaon of your smoke alarm by pressing the test
buon. If no sound is generated, the smoke alarm is not acvated
properly and should not be used!
Mounng and connecng
• WARNING: Turn off the mains power before installing this alarm to
avoid the risk of electrical shocks;
• Connect the wires of the AC connector to the mains power supply and
signal wires:
- Brown wire: Connect to live wire of mains power
- Blue wire: Connect to neutral wire of mains power
- White wire: Connect to signal wire to other devices
• Remove the fixing plug from the mounng plate (if necessary, use a
screw driver for this);
• Pull the AC connector through the
centre hole in the mounng plate.
• Hold the mounng plate on the
desired installaon locaon and
mark where holes should be drilled;
• Drill two holes with a diameter of 5
millimetres;
• Push the plasc plugs into the holes;
• Insert the screws into the mounng
plate, and ghten them firmly into
the plugs;
• Connect the AC connector to the
smoke alarm;
• Fit the smoke alarm on the mounng
plate and secure it by turning it
clockwise;
Connue on page 4 >>
Minimum
Opmal
Restricons
Test buon
LED indicators
Sound output
Ceiling
AC connector
fixing plug
fixing plug