A6V10323928_c_en_-- SIEMENS Industry, Inc.
2020-07-14 Smart Infrastructure
Installation Instructions
Model OP921
Photoelectric Detector
UL268 7th edition listed
Scan for electronic version
Figure 1
These instructions are written in accordance with the
installation guidelines of NFPA 72,
National Fire Alarm
Code, and CAN/ULC-
S524, The Installation of Fire Alarm
Systems.
Do not locate the detectors next to an oil burner, or
garage where exhaust fumes can trigger an alarm. Other
causes of false alarms are dust accumulation, heavy
concentrations of steam, heavy pipe or cigar smoke, and
certain aerosol sprays.
CAUTION
DO NOT install this detection device until all construction
is completed.
DO NOT store this detection device where it can be
contaminated by dirt, dust, or humidity.
AIR
CURRENTS
Before a detector can sense a fire, the products of
combustion or smoke must travel from the fire to the
detector. This travel is especially influenced by air
currents; therefore, consider air movement when
designing the system. Whi
le combustion products tend
to rise, drafts from hallways, air diffusers, fans, etc., may
help or hinder the travel of combustion products to the
detector. When positioning a detector at a particular
location, give consideration to windows and doors, both
open and closed, to ventilating systems, both in and out
of operation, and to other factors influencing air
movement. Do not install a detector in the air stream of
a room air supply diffuser. It is better to position a
detector closer to an air return.
Th
e distance that products of combustion or smoke
travel from a fire to the detector is not usually the shortest
linear route. Combustion products or smoke usually rise
to the ceiling, then spread out. Average ceiling heights of
8 to 10 feet do not abnormall
y affect detector response.
High ceilings, located in churches, warehouses,
auditoriums, etc., do affect detector response and should
be considered.
SPECIAL CEILING CONSTRUCTION FACTORS
Ceiling obstructions change the natural movement of air
and
combustion products. Depending on the direction of
smoke travel, joists and beams can slow the movement
of heated air and smoke, while pockets between them
can contain a reduced level of smoke. Take obstructions
created by girders, joists, beams, air condi
tioning ducts,
or architectural design into consideration when
determining area protection. Refer to the Initiating
Devices chapter of NFPA Standard 72 for Location and
Spacing requirements for specific types of construction;
e.g. beam, suspended, level, s
loped and peaked
ceilings. The detector is also compatible with the
following mechanical protection guard model: STI-
9604
(see www.STI-USA.com for details).
DETECTOR PLACEMENT
Although no specific spacings are set for the detectors
used for a clean air application, use 30-foot
center
spacing (900 sq ft) from NFPA Standard 72 initiating
devices chapter and CAN/ULC-
S524, if practical, as a
guide or starting point for a detector installation layout.
This spacing, however, is based on ideal conditions
–
smooth ceiling, no air movement, and no physical
obstructions. In some applications, therefore,
considerably less area is protected adequately by each
smoke detector. This is why it is mandatory to closely
follow the installation drawings. In all installat
ions place
the detector on the ceiling, a minimum of 6 inches from
a side wall, or on a wall, 12 inches from the ceiling.
For an ideal, smooth ceiling condition, place the
detectors at a maximum center spacing of 50 feet (2500
square feet). Drawings provided or approved by
Siemens Industry, Inc., or by its authorized distributors
are extremely important.The detector placements
shown on these drawings were chosen after a careful
evaluation of the area that is protected. Such factors as
air currents, temperature, humidity, pressure, and the
nature of the fire load were carefully considered.
Especially noted were the room or area configuration
and the type of ceiling (sloped or flat, smooth or
beamed). Siemens Industry, Inc.’s extensive experience
in the design of the system assures the best detector
placement by following these drawings. Sound
engineering judgment by qualified personnel must be
followed.
TO AVOID NUISANCE ALARMS
Do not locate the detectors where excessive smoke
concentrations exist under norma
l conditions, or in areas
of prolonged high relative humidity where condensation
occurs.
2 A6V10323928_c_en_--
TEMPERATURE – HUMIDITY – PRESSURE - AIR
VELOCITY
The temperature range for the OP921 detector is 32
°F
(0 °C) to 100 °F (38
°C). Use the detector in
environments where the humidity does not exceed 95%
(non-
condensing). Normal changes of atmospheric
pressure do not affect detector sensitivity. The air
velocity range is 0-
300 ft/min for open areas applications
and 0-4000 ft/min for direct in air duct
applications.
Follow detector spacing and location requirements in
NFPA 72 Chapter for High Air Movement Areas and
Control of Smoke Spread.
LED INDICATOR OPERATION
The Model OP921
contains an LED indicator capable of
flashing either one of three distinct colors: green, yellow,
or red. The microprocessor-
based detector monitors the
following:
·Smoke in its sensing chamber
·
Smoke sensitivity is within the range indicated on the
nameplate label
·Internal sensors and electronics
Based on the results of the monitoring, the LED indicator
flashes the following:
F
l
a
sh
C
o
l
o
r
Cond
iti
on
Flash I
n
t
e
r
v
a
l
(
S
e
conds
)
Green *
Normal supervisory operation.
S
moke
sensitivity is within rated
limits.
10
Yellow Detector is in trouble and
needs
replacemen
t.
4
Red
A
larm 1
No
Flashes
Detector is not powered,
or
replacement is
needed
.
–
* LED can be turned off. Please follow the corresponding
description
o
f the Panel
used
.
DETECTOR PROGRAMMING
Each detector must be programmed to respond to a
n
address between 001 - 252.
To program the detector address, use the Model DPU
Device Programming Unit. Refer to the DPU Manual, P/N
315-033260.
Record the loop and device number (system
address) for
the detector on the detector label and on the base to
prevent installing the detector in the wrong base. The
optional DPU label printer can be used for this purpose.
Each detector provides pre-
programmed parameter sets
which can be selected by
the panel. Follow the
corresponding description of the panel used.
·Standard
·Duct
NOTE
·
When using this detector direct in air duct
applications, be sure the detector is set to the
parameter “Duct”.
WIRING
The OP921
supports two operation modes: polarity
insensitive mode and isolator mode. The Detector can be
wired for either mode (refer to Figure 2 and 3). During
the isolator mode, the built-
in dual isolators will work at
both sides of the Detector to isolate the li
ne short in front
or behind the device.
When the OP921
is wired in polarity insensitive mode,
Line -6 and -5 can be either line of the loop.
When the OP921 is wired for I
solator mode, the positive
line needs to be connected to 1b and the negative line to
6. The next device needs to be connected to 1b and 5.
The Line Isolator is located between connector 6 and 5.
NOTICE
Ensure that the panel supports Isolator
mode for
the OP921 product version 17.
Isolator mode must not be used with an OP921
product version <17. You will find the product
version number on the detector label.
DETECTOR MOUNTING
To ensure proper installation of the detector head into the
base, be sure the wires are properly dressed at
installation:
·Position all wires flat against the base.
·Take up all slack in the outlet box
·Route wires away from connector terminals.
TO INSTALL DETECTOR HEAD
·
Rotate detector counterclockwise while gently
pressing on it until the detector seats fully into base.
·Then rotate the
detector clockwise until it stops and
locks in place. Insert optional locking screw (Order
Model LK-11).
TO REMOVE DETECTOR HEAD:
·
Loosen locking screw, if installed. Then rotate the
detector counterclockwise until stop is reached.
·Pull detector out of base.
DETECTOR TESTING
Only qualified service personnel should test. To assure
proper operation of the detector, both the Sensitivity and
Functional Test should be conducted. The minimum test
schedule may be found in the current edition of NFPA
72.
SENSITIVITY MEASUREMENT
The sensitivity of OP921
detectors can be tested
individually using the DPU. Refer to the DPU Manual,
P/N 315-
033260. The sensitivity can be measured by the
panel. Follow the instructions of the panel used.
OP921
S54320-F4-A2
17
A6V10323928_c_en_-- 3
FUNCTIONAL TEST
Perform a functional (Go, No-
Go) test by activating the
detector using the following test gases:
·Smoke Sabre, P/N SMOKESABRE-01-001
·Smoke Centurion (M8), P/N M8-001-024
·Solo A5 Smoke Detector Tester Gas
P/N SOLOA5 001
·Solo A10, P/N SOLO A10 / A10s
·Testifire 1001 / 2001, P/N TS3-001
·HSI PurCheck, P/N HO-30S
·HSI SmokeCheck™, P/N HO-25S
Follow the instruction on the gas canister label. This test
is simply used to ensure that smoke can enter the
sensing chamber and alarm the control panel when the
detector reaches the programmed obscuration
(concentration) level.
The OP921
detectors can also be tested individually
using the DPU.
Refer to the DPU Manual, P/N 315-033260.
MAINTENANCE
The control unit automatically indicates the trouble
message for the OP921
detector whose smoke chamber
changes to the level where the set sensitivity cannot be
maintained. In such circumstances, the detector may
require replacement.
CAUTION
Under no circumstances is the detector head to be
disassembled.
No repairs should be attempted.
DO NOT PAINT
The detector is marked DO NOT PAINT. This is intended
to prohibit painting during routine maintenance of the
occupancy which can affect proper operation of the
detector.
Polarity insensitive wiring:
Figure 2
Isolator mode
wiring:
Figure 3
Wire size: maximum 14 AWG, minimum 18 AWG (Wire larger than 14 AWG can damage the connector)
TO INITIATING CIRCUIT
OF SIEMENS COMPATIBLE
CONTROL UNIT
OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
8727W / 8727C /
RL-HW / RL-HC
TO NEXT BASE
TO NEXT BASE
DO NOT USE AN
END OF LINE DEVICE
DETECTOR BASE
MODEL DB-11/DB-11E
LINE 1 *
LINE 2 *
5
6
1a
TB1
TB3
TB2
1b
5
6
1a
1b
** The relay contacts are shown after System reset, which represents the non-alarm condition.
* OP921 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.
5+
NO
C
NC
6-
RELAY CONTACTS **
3A, 120 VAC
3A, 30 VDC
DO NOT USE AN
END OF LINE DEVICE
OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
8727W / 8727C /
RL-HW / RL-HC
TO NEXT BASE
TO NEXT BASE
DO NOT USE AN
END OF LINE DEVICE
DETECTOR BASE
MODEL DB-11/DB-11E
LINE 1
LINE 2
5
6
1a
TB1
TB3
TB2
1b
5
6
1a
1b
*
The relay contacts are shown after System reset, which represents the non-alarm condition.
5+
NO
C
NC
6-
RELAY *
CONTACTS
3A, 120 VAC
3A, 30 VDC
DO NOT
USE AN
END OF LINE DEVICE
++
–
–
To initiating circuit of
SIEMENS compatible control unit
Siemens Industry, Inc.
Smart Infrastructure
8, Fernwood Road
Florham Park, New Jersey 07932
www.siemens.com/buildingtechnologies
Siemens Canada Limited
Smart Infrastructure
2 Kenview Boulevard
Brampton, Ontario L6T 5E4
Canada
© Siemens Industry, Inc.
Data and design subject to change without notice.
A6V10323928_c_en_-- P/N A5Q00041071
In the device line, up to 30 of any compatible devices in
polarity insensitive mode with 20 ohms max line
resistance can be isolated between two
modules in
isolator mode in a Class A Style 6 wiring.
In the device line, up to 30 of any compatible devices in
polarity insensitive mode with 20 ohms max line
resistance can be isolated behind one module in isolator
mode in a Class B Style 4 wiring.
HLIM isolator module and SBGA-
34 sounder base
cannot be used in the same loop with the modules in
isolator mode.
FCC Statement
WARNING!
Installation and usage of equipment not in accordance with instructions manual may
result in:
Radiation of radio frequency energy
Interference to radio communications
·Install and use equipment in accordance with installation instructions manual
·Read the following information
This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in
accordance with the instructions manual, may cause interference to radio communications.
It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC
Rules, which are designed to provide reasonable protection against such interference when operated in a
commercial environment.
Operation of this equipment in a residential area is likely to cause interference in which case the user at his own
expense will be required to take whatever measures may be required to correct the interference.

Other Siemens Smoke Alarm manuals

Siemens FDA2 Series Technical manual

Siemens

Siemens FDA2 Series Technical manual

Siemens DB-ADPT User manual

Siemens

Siemens DB-ADPT User manual

Siemens 5TC1292-7 User manual

Siemens

Siemens 5TC1292-7 User manual

Siemens FDA241 Guide

Siemens

Siemens FDA241 Guide

Siemens Sinteso Cerberus PRO FDA221 User manual

Siemens

Siemens Sinteso Cerberus PRO FDA221 User manual

Siemens DM1101 User manual

Siemens

Siemens DM1101 User manual

Siemens Cerberus DO1101A-Ex Parts list manual

Siemens

Siemens Cerberus DO1101A-Ex Parts list manual

Siemens FDA2 1 Series User manual

Siemens

Siemens FDA2 1 Series User manual

Siemens DELTA Reflex SD9 Service manual

Siemens

Siemens DELTA Reflex SD9 Service manual

Siemens FDA241 User manual

Siemens

Siemens FDA241 User manual

Siemens AD1-C11 User manual

Siemens

Siemens AD1-C11 User manual

Siemens FDA241 Technical manual

Siemens

Siemens FDA241 Technical manual

Siemens DOW1171 User manual

Siemens

Siemens DOW1171 User manual

Siemens Synco living AP260 User manual

Siemens

Siemens Synco living AP260 User manual

Siemens DELTA reflex SD230N Service manual

Siemens

Siemens DELTA reflex SD230N Service manual

Siemens AD2-C11 User manual

Siemens

Siemens AD2-C11 User manual

Siemens FDOT421 User manual

Siemens

Siemens FDOT421 User manual

Siemens OP121 User manual

Siemens

Siemens OP121 User manual

Siemens AD2-C11 User manual

Siemens

Siemens AD2-C11 User manual

Siemens TITANUS 3000 User manual

Siemens

Siemens TITANUS 3000 User manual

Siemens Cerberus DOT1151A-Ex Parts list manual

Siemens

Siemens Cerberus DOT1151A-Ex Parts list manual

Siemens DELTA reflex SD9L Service manual

Siemens

Siemens DELTA reflex SD9L Service manual

Siemens FDL241-9 Guide

Siemens

Siemens FDL241-9 Guide

Siemens OH921 User manual

Siemens

Siemens OH921 User manual

Popular Smoke Alarm manuals by other brands

Innotek Protek Wireless IW-101A user manual

Innotek

Innotek Protek Wireless IW-101A user manual

Climax Technology SD-29-H manual

Climax Technology

Climax Technology SD-29-H manual

Bellman & Symfon BE1281 user manual

Bellman & Symfon

Bellman & Symfon BE1281 user manual

Kidde SMOKE AND CARBON MONOXIDE ALARM user guide

Kidde

Kidde SMOKE AND CARBON MONOXIDE ALARM user guide

Wheelock E-7025 manual

Wheelock

Wheelock E-7025 manual

Olympia BS-506/WL manual

Olympia

Olympia BS-506/WL manual

Elkron SD610 Installation, programming and functions manual

Elkron

Elkron SD610 Installation, programming and functions manual

System Sensor D2-AUS Installation and maintenance instructions

System Sensor

System Sensor D2-AUS Installation and maintenance instructions

BRK electronic DS700RF user manual

BRK electronic

BRK electronic DS700RF user manual

Hoyles GX32 installation instructions

Hoyles

Hoyles GX32 installation instructions

x-sense XS01-WT user manual

x-sense

x-sense XS01-WT user manual

Ei Electronics Ei161RC Ionisation installation instructions

Ei Electronics

Ei Electronics Ei161RC Ionisation installation instructions

Meridian WLS906 Instructions for installation and use

Meridian

Meridian WLS906 Instructions for installation and use

First Alert SA340B Specification & installation instructions

First Alert

First Alert SA340B Specification & installation instructions

koban KDH-BAT manual

koban

koban KDH-BAT manual

Mobeye CM2410 user manual

Mobeye

Mobeye CM2410 user manual

jablotron JA-85ST quick start guide

jablotron

jablotron JA-85ST quick start guide

Universal Security Instruments MPI305 instructions

Universal Security Instruments

Universal Security Instruments MPI305 instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.