HGM6100U2C SERIES GENSET CONTROLLER
HGM6100U2C Genset Controller 2016-12-19 Version 1.0 Page 14 of 34
5.2 SHUTDOWN ALARMS
When controller detects shutdown alarm, it will send signal to open switch and stop genset. The alarms are
displayed in LCD.
Shutdown alarms as following,
No. Items Description
1 Emergency Stop When controller detects emergency stop signal, it will send a stop alarm
signal and it will be displayed in LCD.
2 High Temp.
Shutdown When the temperature of water/cylinder is higher than set threshold,
controller will send a stop alarm signal and it will be displayed in LCD.
3 Low Oil Pressure
Shutdown When oil pressure is lower than threshold, controller will send a stop
alarm signal and it will be displayed in LCD.
4 Over
Shutdown When genset speed is higher than set threshold, controller will send a
stop alarm signal and it will be displayed in LCD.
5 Under Speed
Shutdown When genset speed is lower than set threshold, controller will send a
stop alarm signal and it will be displayed in LCD.
6 Loss Of Speed Signal
Shutdown When rotate speed is 0 and delay is not 0, controller will send a stop
alarm signal and it will be displayed in LCD.
7 Genset Over Voltage
Shutdown When genset voltage is higher than threshold, controller will send a stop
alarm signal and it will be displayed in LCD.
8 Genset
Voltage Shutdown When genset voltage is under set threshold, controller will send a stop
alarm signal and it will be displayed in LCD.
9 Genset
Shutdown When genset current is higher than set threshold and delay is not 0, it will
send a stop alarm signal and it will be displayed in LCD.
10 Fail To Start Within set start times, if failed to start, controller will send a stop alarm
signal and it will be displayed in LCD.
11 Over Frequency
Shutdown When genset frequency is higher than set threshold, controller will send a
stop alarm signal and it will be displayed in LCD.
12 Under Frequency
Shutdown When genset frequency is lower than set threshold, controller will send a
stop alarm signal and it will be displayed in LCD.
13 Genset Failed When genset frequency is 0, controller will send a stop alarm signal and
it will be displayed in LCD.
14 Low Fuel Level When fuel level low input is active, controller will send a stop alarm signal
and it will be displayed in LCD.
15 Low Water Level When genset water level low input is active, controller will send a stop
alarm signal and it will be displayed in LCD.
16 Temp
Circuit When sensor hasn’t connected to corresponding port, controller will send
shutdown alarm signal and it will be displayed in LCD.
17 Oil Pressure Sensor
Open Circuit When sensor hasn’t connected to corresponding port, controller will send
shutdown alarm signal and it will be displayed in LCD.
18 Maintenance time out
shutdown
When genset running is longer than maintenance time of user setting,
and maintenance action is set as
shutdown, controller send shutdown
alarm signal and it will be displayed in LCD. When maintenance action
type is set as “Not used”, maintenance alarm reset.