7
EN
SETUP
General setup diagram Fig. 31
Meanings of the various parameters
Code Description Values Comments
P0 Total operating mode 0: sequential Each press on the remote control causes the motor to move (initial position:
door closed) as per the following cycle: open, stop, close, stop, open…
1: sequential + timed close
Automatic closure
mode operation
is only possible if
photoelectric cells
are tted, i.e. P2=1
or P2=2.
In sequential mode with automatic timed close:
- the door is closed automatically after the timed delay
programmed in parameter “t0”,
- pressing a button on the remote control interrupts the
movement taking place and the timed close.
2: automatic closure In automatic closure mode:
- the door is closed automatically after the timed delay
programmed in parameter “t0”,
- pressing a button on the remote control during
opening has no effect,
- pressing a button on the remote control during closing
causes it to reopen,
- pressing a button on the remote control during the
timed close restarts the timed delay.
3: automatic closure by cells After the door is opened, movement in front of the cells
(safe closure) will close the door after a short timed
delay (xed at 5 seconds).
If there is no movement in front of the cells, the door will
close automatically after the timed close programmed in
parameter “t0”.
If there is an obstacle in the cells’ detection zone, the
door will not close. It will close once the obstacle is
removed.
P1 Orange warning light 0: without advance warning
1: with 2 s advance warning If the garage opens onto a public road, always select with advance
warning: P1=1.
P2 Safety input 0: no safety mechanism
1: safety mechanism with self test
2: safety mechanism without self test
If value 0 is selected, the safety input is not taken into account.
If value 1 is selected, the system’s self test is run at the start of every
operating cycle.
If value 2 is selected, the safety system runs without a self test: it is essential
to test its proper operation every six months.
P3 Obstacle detection
sensitivity 0: low sensitivity
1: low sensitivity
2: standard
3: high sensitivity
If this setting is changed, it is essential to run the force measurement
sequence at the end of the installation procedure or install a sensor bar.
P4 Partial operating mode 0: sequential Each press on the remote control causes the motor to move (initial position:
door closed) as per the following cycle: open, stop, close, stop, open…
1: sequential + timed close Automatic closure mode operation is only possible if photoelectric cells are
tted, i.e. P2=1 or P2=2.
In sequential mode with automatic timed close:
- the door is closed automatically after the timed delay programmed in
parameter “t2”,
- pressing a button on the remote control interrupts the movement taking place
and the timed close.
P5 Closing speed 0: slowest speed: approx. 3.5 cm/s
to
9: fastest speed: approx. 18 cm/s
By default, 6: approx. 12 cm/s
If this setting is changed, it is essential to run the force measurement
sequence at the end of the installation procedure or install a sensor bar.
P6 Partially open position Storing the position as illustrated in Fig. 33.
P7 Closure approach speed 0: no slowdown
1: short soft stop
2: long soft stop
P7=0: the door does not slow before closure.
P7=1: the door speed slows 20 centimetres before closure.
P7=2: the door speed slows 50 centimetres before closure.
If this setting is changed, it is essential to run the force measurement
sequence at the end of the installation procedure or install a sensor bar.
P8 Opening speed 0: slowest speed: approx. 3.5 cm/s
to
9: fastest speed: approx. 18 cm/s
P9 Choice of operating direction
(type of door) 0: direction 1: all types of doors except
swinging doors
1: direction 2: swinging doors
If this setting requires modication the end limit setting must be repeated along
with self-learning.