IMPORTANT - CE & SAFETY REQUIREMENTS
Product must be mounted, inside a suitable enclosure providing environmental protection to IP65 or greater.
To maintain CE EMC requirements , input wires must be less than metres.
The product contains no serviceable parts , or internal adjustments. no attempt must be made to repair this product. Faulty units must be returned to supplier for repair.
This product must be installed by a qualified person. All electrical wiring must be carried out in accordance with the appropriate regulations for the place of installation.
Before attempting any electrical connection work, please ensure all supplies are switched off.
ABSOLUTE MAXIMUM CONDITIONS ( To exceed may cause damage to the unit) :-
Supply Voltage ± 0 V dc (Protected for over voltage and reverse connection)
Current with over voltage ± 100 mA
Input Voltage ± V between any terminals
Ambient Temperature (-40 to 85) °C Humidity (10 to 95) % RH (Non condensing)
SEM206/P USER GUIDE
SMART HEAD MOUNTED TRANSMITTER INPUT PT100
TWO WIRE (4 to 20) mA
Every effort ha been taken to en ure the accuracy of thi document, however we do not accept re pon ibility for damage, injury, lo or expen e re ulting from error and omi ion , and we re erve the right of amendment without notice.
Important - Please read this document be ore any installing.
PRODUCT SPECIFICATION
RECEIVE AND UNPACKING
CONFIGURATION
Please refer to the product data sheet for full specification, available to down load at www.status.co.uk.
Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify your supplier immediately.
The following parame er can be configured by simply en ering as promp ed by he sof ware package.
· Low range
· High range
· Uni s (°C, °F)
· Burnou (direc ion of ou pu curren on sensor burnou )
Factory default:
Low Range 0
High Range 100
Units °C
Burnout UPSCALE
Inpu PT100
1
2
3
2 Wire (4 o 20) mA
Ou pu
SEM206 P
+
-
V
s
Loop
Load
+
-
IMPORTANT Do not attempt to configure the SEM206 P when connected to a loop supply.
COMMS
Download @
www.status.co.uk
SEM206 P
USB SPEEDLINK
COMPUTER
USB CABLE
STATUS USB CONFIG-UNIT
Red +
Black -
CONFIGURATOR