STI LATCHING/TIMER MODEL LT-1UL
NOTE
It is important to read, understand and follow all instructions provided with this product. It is the installer’s responsibility to
comply with NFPA 70, 72 & 101, NEC, mounting specifications according to ADA and other applicable codes. This product
is not to be used in place of panic hardware. To avoid electrical shock, DO NOT attempt to install this product when power
is on. After installation and testing are complete, provide a copy of this manual to all personnel responsible for testing and
maintenance of this product.
*For access control installations, power for the LT-1UL Timer must be supplied by a power source Listed to UL294. When
used for access control, this device shall be used a part of an access controlled egress door system. It is up to the local AHJ
to allow use of this device in place of an automatic sensor. For higher security installations, lower time limits should be used.
RELAY MODE
N.O. - Relay N.O. -switches with power to circuit - Fail Safe (default)
N.C. - Relay is in same state as with no power to circuit - Fail Secure (cut jumper)
TO CHANGE TIMER SETTINGS (default = 15 seconds): Cut jumpers with “X”, do not cut jumpers with “ “.
If the trigger is activated during a timing cycle, the timer is restarted.
NOTE To ensure jumpers do not reattach or short to other components, cut jumper off completely flush to PCB.
+
-
+
-
x
RELAY ACTIVE LED RED
POWER LED GREEN
1.28 in.
33mm
1.74 in.
44mm
.632 in.
16mm
#6 - 32 x 5/16”
PHILLIPS PAN HEAD SCREW
(2) PROVIDED
CASE BASE
CASE TOP
LT-1PCB
POWER IN
12 - 24 VAC/VDC
TIMER
CONTROL
FORM “C”
DRY CONTACTS
3A, 30VDC
RESET
INPUT COM
TRIGGER
N.C.
COM
N.O.
TIMER START
SWITCH
TIMER OVERRIDE
RESET (OPTIONAL)
*POWER IN
12-24 VAC/VDC
TO MAGNETIC LOCK
(FAIL SAFE MODE)
JUMPERS
15 SEC
RELAY MODE JUMPER
30 SEC 45 SEC LATCH
+
-
*POWER IN
≠≠VAC/VDC, 18 mA
TIMER
CONTROL
FORM “C”
DRY CONTACTS
3A, 30VDC
RESET
INPUT COM
TRIGGER
N.C.
COM
N.O.
19082 #6 - 32 x 5/16”
PHILLIPS PAN HEAD SCREW
(2) PROVIDED
CASE BASE
LT-1PCB
CASE TOP
FAIL SAFE MODE
WIRING DIAGRAM
FAIL SECURE MODE
WIRING DIAGRAM
12-24 VAC/VDC
12-24 VAC/VDC
UB-1/UB-2
UB-1/UB-2
BUTTON LED
CONTACT SET 1
CONTACT SET 2
MESSAGE LED
BUTTON LED
CONTACT SET 1
CONTACT SET 2
MESSAGE LED
NO COM
NO
NC
NC
COM
NO COM
NO
NC
NC
COM
+
–
RST
INPUT COM
TRIG
RELAY NC
RELAY COM
RELAY NO
+
–
RST
INPUT COM
TRIG
RELAY NC
RELAY COM
RELAY NO
LT-1
LT-1
DOOR
LOCK
RESET SWITCH
(OPTIONAL EXCEPT ON
LATCH TIMER SETTING)
DOOR
LOCK
RESET SWITCH
(OPTIONAL EXCEPT ON
LATCH TIMER SETTING)
ILLUMINATING GREEN
ILLUMINATING RED
SHOWN: POWER ON
NORMAL CONDITION
x x
x
ELECTRONIC INSULATION PAPER
IF TRACES ARE INADVERTENTLY CUT,
SOLDER JUMPER WIRES USING
APPROPRIATE HOLES.
RELAY MODE
N.O.
N.C.
NO CUT
CUT
15s
30s
45s
Ltch
Relay
NO
Relay
COM
Relay
NC
Trig Input
Com
Reset Power Input
+
-
12 to 24 Volts
AC or DC
MODEL LT-1
RELAY MODE
N.O.
N.C.
NO CUT
CUT
15s
30s
45s
Ltch
+
-
+
-
x
RELAY ACTIVE LED RED
POWER LED GREEN
1.28 in.
33mm
1.74 in.
44mm
.632 in.
16mm
#6 - 32 x 5/16”
PHILLIPS PAN HEAD SCREW
(2) PROVIDED
CASE BASE
CASE TOP
LT-1PCB
POWER IN
12 - 24 VAC/VDC
TIMER
CONTROL
FORM “C”
DRY CONTACTS
3A, 30VDC
RESET
INPUT COM
TRIGGER
N.C.
COM
N.O.
TIMER START
SWITCH
TIMER OVERRIDE
RESET (OPTIONAL)
*POWER IN
12-24 VAC/VDC
TO MAGNETIC LOCK
(FAIL SAFE MODE)
JUMPERS
15 SEC
RELAY MODE JUMPER
30 SEC 45 SEC LATCH
+
-
*POWER IN
≠≠VAC/VDC, 18 mA
TIMER
CONTROL
FORM “C”
DRY CONTACTS
3A, 30VDC
RESET
INPUT COM
TRIGGER
N.C.
COM
N.O.
19082 #6 - 32 x 5/16”
PHILLIPS PAN HEAD SCREW
(2) PROVIDED
CASE BASE
LT-1PCB
CASE TOP
FAIL SAFE MODE
WIRING DIAGRAM
FAIL SECURE MODE
WIRING DIAGRAM
12-24 VAC/VDC
12-24 VAC/VDC
UB-1/UB-2
UB-1/UB-2
BUTTON LED
CONTACT SET 1
CONTACT SET 2
MESSAGE LED
BUTTON LED
CONTACT SET 1
CONTACT SET 2
MESSAGE LED
NO COM
NO
NC
NC
COM
NO COM
NO
NC
NC
COM
+
–
RST
INPUT COM
TRIG
RELAY NC
RELAY COM
RELAY NO
+
–
RST
INPUT COM
TRIG
RELAY NC
RELAY COM
RELAY NO
LT-1
LT-1
DOOR
LOCK
RESET SWITCH
(OPTIONAL EXCEPT ON
LATCH TIMER SETTING)
DOOR
LOCK
RESET SWITCH
(OPTIONAL EXCEPT ON
LATCH TIMER SETTING)
ILLUMINATING GREEN
ILLUMINATING RED
SHOWN: POWER ON
NORMAL CONDITION
x x
x
ELECTRONIC INSULATION PAPER
IF TRACES ARE INADVERTENTLY CUT,
SOLDER JUMPER WIRES USING
APPROPRIATE HOLES.
RELAY MODE
N.O.
N.C.
NO CUT
CUT
15s
30s
45s
Ltch
Relay
NO
Relay
COM
Relay
NC
Trig Input
Com
Reset Power Input
+
-
12 to 24 Volts
AC or DC
MODEL LT-1
RELAY MODE
N.O.
N.C.
NO CUT
CUT
15s
30s
45s
Ltch
+
-
+
-
x
RELAY ACTIVE LED RED
POWER LED GREEN
1.28 in.
33mm
1.74 in.
44mm
.632 in.
16mm
#6 - 32 x 5/16”
PHILLIPS PAN HEAD SCREW
(2) PROVIDED
CASE BASE
CASE TOP
LT-1PCB
POWER IN
12 - 24 VAC/VDC
TIMER
CONTROL
FORM “C”
DRY CONTACTS
3A, 30VDC
RESET
INPUT COM
TRIGGER
N.C.
COM
N.O.
TIMER START
SWITCH
TIMER OVERRIDE
RESET (OPTIONAL)
*POWER IN
12-24 VAC/VDC
TO MAGNETIC LOCK
(FAIL SAFE MODE)
JUMPERS
15 SEC
RELAY MODE JUMPER
30 SEC 45 SEC LATCH
+
-
*POWER IN
≠≠VAC/VDC, 18 mA
TIMER
CONTROL
FORM “C”
DRY CONTACTS
3A, 30VDC
RESET
INPUT COM
TRIGGER
N.C.
COM
N.O.
19082 #6 - 32 x 5/16”
PHILLIPS PAN HEAD SCREW
(2) PROVIDED
CASE BASE
LT-1PCB
CASE TOP
FAIL SAFE MODE
WIRING DIAGRAM
FAIL SECURE MODE
WIRING DIAGRAM
12-24 VAC/VDC
12-24 VAC/VDC
UB-1/UB-2
UB-1/UB-2
BUTTON LED
CONTACT SET 1
CONTACT SET 2
MESSAGE LED
BUTTON LED
CONTACT SET 1
CONTACT SET 2
MESSAGE LED
NO COM
NO
NC
NC
COM
NO COM
NO
NC
NC
COM
+
–
RST
INPUT COM
TRIG
RELAY NC
RELAY COM
RELAY NO
+
–
RST
INPUT COM
TRIG
RELAY NC
RELAY COM
RELAY NO
LT-1
LT-1
DOOR
LOCK
RESET SWITCH
(OPTIONAL EXCEPT ON
LATCH TIMER SETTING)
DOOR
LOCK
RESET SWITCH
(OPTIONAL EXCEPT ON
LATCH TIMER SETTING)
ILLUMINATING GREEN
ILLUMINATING RED
SHOWN: POWER ON
NORMAL CONDITION
x x
x
ELECTRONIC INSULATION PAPER
IF TRACES ARE INADVERTENTLY CUT,
SOLDER JUMPER WIRES USING
APPROPRIATE HOLES.
RELAY MODE
N.O.
N.C.
NO CUT
CUT
15s
30s
45s
Ltch
Relay
NO
Relay
COM
Relay
NC
Trig Input
Com
Reset Power Input
+
-
12 to 24 Volts
AC or DC
MODEL LT-1
RELAY MODE
N.O.
N.C.
NO CUT
CUT
15s
30s
45s
Ltch
All manuals and user guides at all-guides.com
INSTRUCTIONS FOR MOUNTING
1. Locate suitable mounting position
in a listed gang box.
2. Using case base as a template,
mark and drill (2) 7/64” holes.
3. Attach case base with 2 thread
forming screws (included).
4. Install insulation paper.
5. Snap circuit board into place with
terminal strip toward case edge
with arrow.
6. Snap on case top.
7. Wire devices.
+
-
+
-
x
RELAY ACTIVE LED RED
POWER LED GREEN
1.28 in.
33mm
1.74 in.
44mm
.632 in.
16mm
#6 - 32 x 5/16”
PHILLIPS PAN HEAD SCREW
(2) PROVIDED
CASE BASE
CASE TOP
LT-1PCB
POWER IN
12 - 24 VAC/VDC
TIMER
CONTROL
FORM “C”
DRY CONTACTS
3A, 30VDC
RESET
INPUT COM
TRIGGER
N.C.
COM
N.O.
TIMER START
SWITCH
TIMER OVERRIDE
RESET (OPTIONAL)
*POWER IN
12-24 VAC/VDC
TO MAGNETIC LOCK
(FAIL SAFE MODE)
JUMPERS
15 SEC
RELAY MODE JUMPER
30 SEC 45 SEC LATCH
+
-
*POWER IN
≠≠VAC/VDC, 18 mA
TIMER
CONTROL
FORM “C”
DRY CONTACTS
3A, 30VDC
RESET
INPUT COM
TRIGGER
N.C.
COM
N.O.
19082 #6 - 32 x 5/16”
PHILLIPS PAN HEAD SCREW
(2) PROVIDED
CASE BASE
LT-1PCB
CASE TOP
FAIL SAFE MODE
WIRING DIAGRAM
FAIL SECURE MODE
WIRING DIAGRAM
12-24 VAC/VDC
12-24 VAC/VDC
UB-1/UB-2
UB-1/UB-2
BUTTON LED
CONTACT SET 1
CONTACT SET 2
MESSAGE LED
BUTTON LED
CONTACT SET 1
CONTACT SET 2
MESSAGE LED
NO COM
NO
NC
NC
COM
NO COM
NO
NC
NC
COM
+
–
RST
INPUT COM
TRIG
RELAY NC
RELAY COM
RELAY NO
+
–
RST
INPUT COM
TRIG
RELAY NC
RELAY COM
RELAY NO
LT-1
LT-1
DOOR
LOCK
RESET SWITCH
(OPTIONAL EXCEPT ON
LATCH TIMER SETTING)
DOOR
LOCK
RESET SWITCH
(OPTIONAL EXCEPT ON
LATCH TIMER SETTING)
ILLUMINATING GREEN
ILLUMINATING RED
SHOWN: POWER ON
NORMAL CONDITION
x x
x
ELECTRONIC INSULATION PAPER
IF TRACES ARE INADVERTENTLY CUT,
SOLDER JUMPER WIRES USING
APPROPRIATE HOLES.
RELAY MODE
N.O.
N.C.
NO CUT
CUT
15s
30s
45s
Ltch
Relay
NO
Relay
COM
Relay
NC
Trig Input
Com
Reset Power Input
+
-
12 to 24 Volts
AC or DC
MODEL LT-1
RELAY MODE
N.O.
N.C.
NO CUT
CUT
15s
30s
45s
Ltch
Printed in USA LT-1PCB OCT2018
+
-
+
-
x
RELAY ACTIVE LED RED
POWER LED GREEN
1.28 in.
33mm
1.74 in.
44mm
.632 in.
16mm
#6 - 32 x 5/16”
PHILLIPS PAN HEAD SCREW
(2) PROVIDED
CASE BASE
CASE TOP
LT-1PCB
POWER IN
12 - 24 VAC/VDC
TIMER
CONTROL
FORM “C”
DRY CONTACTS
3A, 30VDC
RESET
INPUT COM
TRIGGER
N.C.
COM
N.O.
TIMER START
SWITCH
TIMER OVERRIDE
RESET (OPTIONAL)
*POWER IN
12-24 VAC/VDC
TO MAGNETIC LOCK
(FAIL SAFE MODE)
JUMPERS
15 SEC
RELAY MODE JUMPER
30 SEC 45 SEC LATCH
+
-
*POWER IN
≠≠VAC/VDC, 18 mA
TIMER
CONTROL
FORM “C”
DRY CONTACTS
3A, 30VDC
RESET
INPUT COM
TRIGGER
N.C.
COM
N.O.
19082 #6 - 32 x 5/16”
PHILLIPS PAN HEAD SCREW
(2) PROVIDED
CASE BASE
LT-1PCB
CASE TOP
FAIL SAFE MODE
WIRING DIAGRAM
FAIL SECURE MODE
WIRING DIAGRAM
12-24 VAC/VDC
12-24 VAC/VDC
UB-1/UB-2
UB-1/UB-2
BUTTON LED
CONTACT SET 1
CONTACT SET 2
MESSAGE LED
BUTTON LED
CONTACT SET 1
CONTACT SET 2
MESSAGE LED
NO COM
NO
NC
NC
COM
NO COM
NO
NC
NC
COM
+
–
RST
INPUT COM
TRIG
RELAY NC
RELAY COM
RELAY NO
+
–
RST
INPUT COM
TRIG
RELAY NC
RELAY COM
RELAY NO
LT-1
LT-1
DOOR
LOCK
RESET SWITCH
(OPTIONAL EXCEPT ON
LATCH TIMER SETTING)
DOOR
LOCK
RESET SWITCH
(OPTIONAL EXCEPT ON
LATCH TIMER SETTING)
ILLUMINATING GREEN
ILLUMINATING RED
SHOWN: POWER ON
NORMAL CONDITION
x x
x
ELECTRONIC INSULATION PAPER
IF TRACES ARE INADVERTENTLY CUT,
SOLDER JUMPER WIRES USING
APPROPRIATE HOLES.
RELAY MODE
N.O.
N.C.
NO CUT
CUT
15s
30s
45s
Ltch
Relay
NO
Relay
COM
Relay
NC
Trig Input
Com
Reset Power Input
+
-
12 to 24 Volts
AC or DC
MODEL LT-1
RELAY MODE
N.O.
N.C.
NO CUT
CUT
15s
30s
45s
Ltch
2306 Airport Rd • Waterford, MI 48327, USA
Phone: 248-673-9898 • Fax: 248-673-1246
[email protected] • www.sti-usa.com
Taylor House • 34 Sherwood Road • Bromsgrove, Worcestershire • B60 3DR • England
Tel: +44 (0)1527 520 999 • Fax: +44 (0)1527 501 999 • [email protected] • www.sti-emea.com
CONTACT RATINGS
Models: UB-1, UB-2, SS2xx4, SS2xx5, SS2xx7 and
SS2xxB ending with LTUL Form “C” Conacts are
rated 30 VDC, 3A.
WARRANTY
One year guarantee on electro mechanical and
electronic components.
Electronic warranty form at www.sti-usa.com/wc14.
UL294 Performance Levels:
Line Security: I
Attack: I
Endurance: IV
Standby Power: I
All manuals and user guides at all-guides.com

Other STI Timer manuals

STI LT-1 User manual

STI

STI LT-1 User manual

STI Stopper Station Series User manual

STI

STI Stopper Station Series User manual

STI LT-1 User manual

STI

STI LT-1 User manual

STI Stopper SS2 8 Series Quick guide

STI

STI Stopper SS2 8 Series Quick guide

STI LT-1 User manual

STI

STI LT-1 User manual

STI LT-1UL User manual

STI

STI LT-1UL User manual

Popular Timer manuals by other brands

REV 25500 operating instructions

REV

REV 25500 operating instructions

Prostat PDT-740B user manual

Prostat

Prostat PDT-740B user manual

ACU-RITE 535 instruction manual

ACU-RITE

ACU-RITE 535 instruction manual

BLACK DECKER BDXPA0031 instruction manual

BLACK DECKER

BLACK DECKER BDXPA0031 instruction manual

CO/Tech EMT306CD manual

CO/Tech

CO/Tech EMT306CD manual

Flofab FFPFDT owner's manual

Flofab

Flofab FFPFDT owner's manual

digi-tech QM-6325 user manual

digi-tech

digi-tech QM-6325 user manual

Air Posi-Drain PD7020 Installation & operation manual

Air

Air Posi-Drain PD7020 Installation & operation manual

ANV APT1-S manual

ANV

ANV APT1-S manual

Exhausto TIMERBUTTON2 Product information

Exhausto

Exhausto TIMERBUTTON2 Product information

PowerTech MS-6114 operating instructions

PowerTech

PowerTech MS-6114 operating instructions

Hahnel Captur manual

Hahnel

Hahnel Captur manual

ELPRO ASTOL operating manual

ELPRO

ELPRO ASTOL operating manual

GSE Timer box IV user manual

GSE

GSE Timer box IV user manual

Woods TM16+RC Series instructions

Woods

Woods TM16+RC Series instructions

Radio Shack Big Digit Timer owner's manual

Radio Shack

Radio Shack Big Digit Timer owner's manual

Red Ion CUB7T0 manual

Red Ion

Red Ion CUB7T0 manual

Sylvania SA 306 Installation and operation guide

Sylvania

Sylvania SA 306 Installation and operation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.