
Document #518101 RevD 20 SunPower Proprietary
o690.43(A) – SunPower Equinox is grounded when installed according to the instructions and connected to
an equipment grounding conductor bonded to the premises grounding electrode system.
o690.43(B) – SunPower Equinox requires the installation of an equipment grounding conductor between the
array and other equipment (typically originating at the rooftop junction box and terminating at the
grounding busbar or terminal in the main service panel).
o690.43(C) – InvisiMount end clamps and mid clamps are Listed and identified for bonding module frames to
rails.
o690.43(D) – InvisiMount end clamps and mid clamps are Listed and identified for bonding module frames to
rails.
o690.43(E) – InvisiMount mid clamps are identified for the purpose of grounding modules.
o690.43(F) – The integrated AC module cable and AC module extension cables do include an equipment
grounding conductor.
•690.45 specifies that EGCs should be sized based on 250.122. Equinox meets this requirement by including a 12
AWG equipment grounding conductor. The EGC in every AC module cable is 12 AWG. The maximum overcurrent
protection for an AC module circuit is 20 A. The minimum EGC size based on the table at 250.122 is 12 AWG. If
multiple circuits are routed with a single EGC for the array, 250.122(C) permits the installer to use 12 AWG for the
combined EGC.
•690.46 modifies 690.45 when the EGC is not protected within a raceway, and does not apply to SunPower
Equinox. It modifies 690.45 by requiring a larger conductor when the EGC is not routed with circuit conductors
and installed outside of a raceway. But SunPower Equinox does comply with 690.31(D) which requires that the
EGC be contained within the cable assembly. 690.46 was inserted into the Code to prevent installers from using
small conductors such as 14, 12, or 10 AWG to ground rails in systems having no integrated grounding.
•690.47 does not apply to AC modules:
o690.47(A) does not apply to Equinox because the AC “system” was already existing on the premises (already
installed per Article 250 of the code) and the AC module system connects to the load side of this service.
Installing AC modules constitutes the installation of new “equipment” on an existing AC system. As such, the
existing system already has a grounding electrode system, and the only requirement is to connect the new
equipment to that system.
o690.47(B) applies to DC systems; it does not apply to AC modules, and does not apply to SunPower Equinox.
This section pertains only to DC systems in which a photovoltaic source circuit would be either grounded or
ungrounded; but 690.6 exempts AC modules from requirements pertaining to photovoltaic source circuits.
Code language states that the intention of an auxiliary grounding electrode can be achieved through a
properly installed EGC back to the premises grounding electrode. SunPower Equinox meets this intention
for rooftop arrays by using the integrated grounding system along with a properly sized and installed EGC.
o690.47(C) does not apply to SunPower Equinox for the same reasons that 690.47(A) and 690.47(B) do not
apply.
o690.47(D) only provides guidance for a “dc grounding electrode conductor” and does not apply to SunPower
Equinox on residential rooftops where there is an existing adequate premises grounding electrode system.
In most cases (99%), the premises wiring electrode eliminates the need for an additional array grounding
electrode (Exception No. 2) and the equipment grounding conductor connected to the grounding busbar or
terminal in the main service panel is sufficient for connecting the metallic surfaces of the array to ground.
•690.48 addresses module removal. When an AC module is removed from a SunPower Equinox system, it
interrupts the circuit and equipment grounding connection between modules. This can leave the equipment