SUREN CDL-608R12 User manual

N-ML00-0045-03-1
0-ML00-0045-03-1
A4
Notes:
1. Material: 80g printing paper, white. A4 size.
2. Printing: Black
3. Pack and tie a label with part number 0-ML00-0045-03-1 .
PIR & Ultrasonic Occupancy Sensor
CDL-608R12 embodies the technology of infrared and ultrasonic motion
detection into one easy-to-install occupancy sensor. Mounted at a height
of 2.4m, this sensor detects people moving within 8m diameter of a full
circular coverage area.
CDL-608R12 can be surface mounted or flush mounted for an attractive,
un-obstructive appearance. One or many sensors can be connected with
Suren's (or compatible) power packs to control a wide range of load types,
including lighting or HVAC devices.
The sensor becomes operational 30 seconds after power is supplied.
When a person enters a room, t he sensor detects major body motion and
turns the light on. The light is kept on even as smaller body movement is
detected. The sensor's (DSL) minimizes
false triggering by adjusting detection sensitivity based upon sequence of
occupancy events. The provides additional control such
that lighting is not activated when there is sufficient brightness in the
area.
When motion is no longer detected, the sensor turns the light off after a
set time delay (Delayed-Off Time).
The walk-through feature is useful in areas that are momentarily
occupied, e.g. hallway. If the sensor detects no movement for more than
10 seconds light was turned off, it will apply a Delayed-Off Time of 2.5
minutes. If the sensor detects movement less than 10 seconds after light
was turned off, it will next turn the light off based upon the set time delay.
Brackets, screws and wall plugs for surface mount in solid ceiling
Spring clips for flush mount in drop ceiling
Infrared zone mask
Determine the number of sensors required to cover the floor area
Install the sensor near work area where walk-path cuts across radial
lines, not towards the sensor
Do not install the sensor near ventilation outlet
Avoid facing the ultrasonic transceivers to each other to minimize
interference
Prepare sensor mount. See illustration in the next page
Connect the sensor as shown in the wiring diagram. Make sure power
supply is turned off
Make sure there are no wiring exposed before mounting the sensor
Mount the sensor and turn on the power supply
Open the cover, review settings and change if necessary. See
Settings section
Initiate test mode, replace the cover and conduct walk-test
Toggle dip switch B3 (Off-On-Off) to enter test mode. If B3 is already in
the On position, moving it to the Off position will also activate test
mode
Amber LED will flash once every second when the sensor is in test
mode
During this time, the sensor will turn the light off after 5 seconds if
there are no movement
Test movement at entry point, walk path and occupancy area
Sensor will exit test mode after 15 minutes
LED indicator can be enabled or disabled by dip switch setting
Recommended for troubleshooting
Red LED indicates motion detected by infrared sensor
Green LED indicates motion detected by ultrasonic sensor
Operation
Initialization:
Detection and Activation:
Detection Sequence Logic
Sunset Sensor
De-Activation (Normal Occupancy Mode):
Walk-thru Mode:
Accessories:
Location:
Procedure:
Walk-Test:
LED Indicator:
Installation
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
0
m
m
2
204
4
2
2
4
4
PIR Optical View Pattern Ultrasonic Detection Pattern
CDL-608R12
Operation and Specification SUREN
©2011 SUREN Systems, Ltd.. All rights reserved. SUREN™ SUREN Part no.: N-ML00-0045-03-1 Rev.1 Printed in China
w w w . s u r e n s y s t e m s . c o m
Detection range
at 2.4m height
m
2
2
4 0 4
Power Supply:
Power Consumption:
Control Signal Output:
IR Sensor:
Ultrasonic Frequency:
12V DC (Power pack PS-112 or
PS-212 required)
0.96 W
12V DC, 15 mA
P
Pyroelectric 2-element
40 Khz
,
H
High-impact ABS
110mm Diameter x 56 mm Height
-40 to 55 C
20 V/m 10-1000 Mhz; 10 V/m 1-2 GHz
ousing Material:
Dimension:
Operating Temperature Range:
RF Immunity:
Approvals:
o o
Specification
Drop-Ceiling Mounting: Base Preparation
Install the two retaining springs as shown.
Drop-Ceiling Mounting: Panel Preparation
Use a hole saw to cut a 85 mm circular hole in the
drop-ceiling panel at the desired location.
Drop-Ceiling Mounting: Sensor Installation
Press the retaining springs together, then push
the springs and the sensor base through the hole
until the sensor rim is seated against the panel.
Sensor Opening
Slide a fingertip under the tab at one end of the
cover. Pull gently to remove the cover.
Solid-Ceiling Mounting
Use the three screws (supplied with the sensor)
to fasten the base ring to the ceiling. Align the
sensor's two eyelets with the base ring's two
hooks. Press the sensor onto the base ring.
Sensor Mounting Choices
The sensor may be mounted either in a drop-
ceiling panel, or on a solid ceiling. In a drop-
ceiling panel, two metal springs serve to retain
the sensor in the panel. On a solid ceiling, the
sensor is mounted on a base ring (supplied with
the sensor).The base ring is fastened to the
ceiling by means of three screws.
2
11
Delayed-Off Time Adjustment
The sensor turns light off if motion is not detected
within the Delayed-Off Time interval. For less
disruption, adjust clockwise (CW). For better
energy savings, adjust counter-clockwise (CCW).
Ultrasonic Adjustment
For maximum range and sensitivity, set fully
clockwise (CW). If reduced range and sensitivity
are required, then turn counter-clockwise (CCW)
and test.
Infrared Adjustment
For maximum range and sensitivity, set fully
clockwise (CW). If reduced range and sensitivity
are required, then turn counter-clockwise (CCW)
and test.
Sets the infrared range
Range setting
Full CCW = min.
Full CW = max.
Sets the ultrasonic range
Range setting
Full CCW = min.
Full CW = max.
Operation Control Console
All aspects of sensor operation can be adjusted
here.
Dip Switch Settings
Note: The mounting clips indicated by the arrows
represent the direction of the longer ultrasonic
range shown in the Detection Area diagram.
Sunset Sensor Adjustment
The sunset sensor saves energy by not switching
the light on when there is sufficient daylight in the
room. It can be enabled or disabled by the dip
switch B1. When the sunset sensor is enabled, the
sensor goes into stand-by mode when the natural
light level exceeds the selected Lux level
inhibiting the light from turning on. To set the Lux
level, draw curtains or shades until the room is at
the darkness that light should be turned on. Adjust
the Lux level from low to high until lighting is
activated. Note that the sunset sensor is disabled
when the occupancy sensor is in test mode.
Off On
A1 Multi/Single Technology
A2 Technology Activated
A3 Not Used
A4 Walk-Thru/Normal Walk-Thru Enabled Normal Occupancy
B1 Sunset Sensor Enabled Disabled
B2 LED Indicator Enabled Disabled
B3 Test Mode
B4 Not Used
Off-On-Off / On-Off
Bank A
Bank B
Dip
Switch Function
Settings
Features enabled by the combination of
A1 & A2 are shown in the table below.
A1 A2 Feature
Off Off
PIR technology turns light on; however, motion detection by
either technology will keep the light on. If neither technology
detects motion, the light turns off after the Delayed-Off time.
[Choose this option to reduce false activation due to ultrasonic
technology.]
Off On
PIR or Ultrasonic technology turns light on and keeps light on.
If neither technology detects motion, the light turns off after the
Del ayed-Off time. [Default]
On Off Only PIR technology is active.
On On Only Ultrasonic technology is active.
PIR & Ultrasonic Occupancy Sensor
CDL-608R24 embodies the technology of infrared and ultrasonic motion
detection into one easy-to-install occupancy sensor. Mounted at a height
of 2.4m, this sensor detects people moving within 8m diameter of a full
circular coverage area.
CDL-608R24 can be surface mounted or flush mounted for an attractive,
un-obstructive appearance. One or many sensors can be connected with
Suren's (or compatible) power packs to control a wide range of load types,
including lighting or HVAC devices.
The sensor becomes operational 30 seconds after power is supplied.
When a person enters a room, t he sensor detects major body motion and
turns the light on. The light is kept on even as smaller body movement is
detected. The sensor's (DSL) minimizes
false triggering by adjusting detection sensitivity based upon sequence of
occupancy events. The provides additional control such
that lighting is not activated when there is sufficient brightness in the
area.
When motion is no longer detected, the sensor turns the light off after a
set time delay (Delayed-Off Time).
The walk-through feature is useful in areas that are momentarily
occupied, e.g. hallway. If the sensor detects no movement for more than
10 seconds light was turned off, it will apply a Delayed-Off Time of 2.5
minutes. If the sensor detects movement less than 10 seconds after light
was turned off, it will next turn the light off based upon the set time delay.
Brackets, screws and wall plugs for surface mount in solid ceiling
Spring clips for flush mount in drop ceiling
Infrared zone mask
Determine the number of sensors required to cover the floor area
Install the sensor near work area where walk-path cuts across radial
lines, not towards the sensor
Do not install the sensor near ventilation outlet
Avoid facing the ultrasonic transceivers to each other to minimize
interference
Prepare sensor mount. See illustration in the next page
Connect the sensor as shown in the wiring diagram. Make sure power
supply is turned off
Make sure there are no wiring exposed before mounting the sensor
Mount the sensor and turn on the power supply
Open the cover, review settings and change if necessary. See
Settings section
Initiate test mode, replace the cover and conduct walk-test
Toggle dip switch B3 (Off-On-Off) to enter test mode. If B3 is already in
the On position, moving it to the Off position will also activate test
mode
Amber LED will flash once every second when the sensor is in test
mode
During this time, the sensor will turn the light off after 5 seconds if
there are no movement
Test movement at entry point, walk path and occupancy area
Sensor will exit test mode after 15 minutes
LED indicator can be enabled or disabled by dip switch setting
Recommended for troubleshooting
Red LED indicates motion detected by infrared sensor
Green LED indicates motion detected by ultrasonic sensor
Operation
Initialization:
Detection and Activation:
Detection Sequence Logic
Sunset Sensor
De-Activation (Normal Occupancy Mode):
Walk-thru Mode:
Accessories:
Location:
Procedure:
Walk-Test:
LED Indicator:
Installation
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
0
m
m
2
204
4
2
2
4
4
PIR Optical View Pattern Ultrasonic Detection Pattern
CDL-608R24
Operation and Specification SUREN
©2011 SUREN Systems, Ltd.. All rights reserved. SUREN™ SUREN Part no.: N-ML00-0045-04-1 Rev.1 Printed in China
w w w . s u r e n s y s t e m s . c o m
Detection range
at 2.4m height
m
2
2
4 0 4
Power Supply:
Power Consumption:
Control Signal Output:
IR Sensor:
Ultrasonic Frequency:
24 V DC (Power pack PS-124
or PS-224 required)
0.96 W
24 V DC, 15 mA
P
Pyroelectric 2-element
40 Khz
,
H
High-impact ABS
110mm Diameter x 56 mm Height
-40 to 55 C
20 V/m 10-1000 Mhz; 10 V/m 1-2 GHz
ousing Material:
Dimension:
Operating Temperature Range:
RF Immunity:
Approvals:
o o
Specification
Drop-Ceiling Mounting: Base Preparation
Install the two retaining springs as shown.
Drop-Ceiling Mounting: Panel Preparation
Use a hole saw to cut a 85 mm circular hole in the
drop-ceiling panel at the desired location.
Drop-Ceiling Mounting: Sensor Installation
Press the retaining springs together, then push
the springs and the sensor base through the hole
until the sensor rim is seated against the panel.
Sensor Opening
Slide a fingertip under the tab at one end of the
cover. Pull gently to remove the cover.
Solid-Ceiling Mounting
Use the three screws (supplied with the sensor)
to fasten the base ring to the ceiling. Align the
sensor's two eyelets with the base ring's two
hooks. Press the sensor onto the base ring.
Sensor Mounting Choices
The sensor may be mounted either in a drop-
ceiling panel, or on a solid ceiling. In a drop-
ceiling panel, two metal springs serve to retain
the sensor in the panel. On a solid ceiling, the
sensor is mounted on a base ring (supplied with
the sensor).The base ring is fastened to the
ceiling by means of three screws.
2
11
Delayed-Off Time Adjustment
The sensor turns light off if motion is not detected
within the Delayed-Off Time interval. For less
disruption, adjust clockwise (CW). For better
energy savings, adjust counter-clockwise (CCW).
Ultrasonic Adjustment
For maximum range and sensitivity, set fully
clockwise (CW). If reduced range and sensitivity
are required, then turn counter-clockwise (CCW)
and test.
Infrared Adjustment
For maximum range and sensitivity, set fully
clockwise (CW). If reduced range and sensitivity
are required, then turn counter-clockwise (CCW)
and test.
Sets the infrared range
Range setting
Full CCW = min.
Full CW = max.
Sets the ultrasonic range
Range setting
Full CCW = min.
Full CW = max.
Operation Control Console
All aspects of sensor operation can be adjusted
here.
Dip Switch Settings
Note: The mounting clips indicated by the arrows
represent the direction of the longer ultrasonic
range shown in the Detection Area diagram.
Sunset Sensor Adjustment
The sunset sensor saves energy by not switching
the light on when there is sufficient daylight in the
room. It can be enabled or disabled by the dip
switch B1. When the sunset sensor is enabled, the
sensor goes into stand-by mode when the natural
light level exceeds the selected Lux level
inhibiting the light from turning on. To set the Lux
level, draw curtains or shades until the room is at
the darkness that light should be turned on. Adjust
the Lux level from low to high until lighting is
activated. Note that the sunset sensor is disabled
when the occupancy sensor is in test mode.
Off On
A1 Multi/Single Technology
A2 Technology Activated
A3 Not Used
A4 Walk-Thru/Normal Walk-Thru Enabled Normal Occupancy
B1 Sunset Sensor Enabled Disabled
B2 LED Indicator Enabled Disabled
B3 Test Mode
B4 Not Used
Off-On-Off / On-Off
Bank A
Bank B
Dip
Switch Function
Settings
Features enabled by the combination of
A1 & A2 are shown in the table below.
A1 A2 Feature
Off Off
PIR technology turns light on; however, motion detection by
either technology will keep the light on. If neither technology
detects motion, the light turns off after the Delayed-Off time.
[Choose this option to reduce false activation due to ultrasonic
technology.]
Off On
PIR or Ultrasonic technology turns light on and keeps light on.
If neither technology detects motion, the light turns off after the
Del ayed-Off time. [Default]
On Off Only PIR technology is active.
On On Only Ultrasonic technology is active.

Other SUREN Security Sensor manuals

SUREN CPL-1312 User manual

SUREN

SUREN CPL-1312 User manual

SUREN CDL-608C24 Instruction Manual

SUREN

SUREN CDL-608C24 Instruction Manual

SUREN M-TEC CDP-808 User manual

SUREN

SUREN M-TEC CDP-808 User manual

SUREN CDL-608 User manual

SUREN

SUREN CDL-608 User manual

SUREN CDL-1608 User manual

SUREN

SUREN CDL-1608 User manual

SUREN HB-1316 User manual

SUREN

SUREN HB-1316 User manual

SUREN PYROFLEX CS-106 User manual

SUREN

SUREN PYROFLEX CS-106 User manual

SUREN M-TEC CDP-1808 User manual

SUREN

SUREN M-TEC CDP-1808 User manual

SUREN M-TEC CDP-808C24 User manual

SUREN

SUREN M-TEC CDP-808C24 User manual

Popular Security Sensor manuals by other brands

Zamel RCR-01 Manual instruction

Zamel

Zamel RCR-01 Manual instruction

Moniron Mobile Quick user guide

Moniron

Moniron Mobile Quick user guide

Tynetec ZXT413 manual

Tynetec

Tynetec ZXT413 manual

Bosch DS9360 TriTech installation instructions

Bosch

Bosch DS9360 TriTech installation instructions

netvox RA08B Series user manual

netvox

netvox RA08B Series user manual

Terrier FHX owner's manual

Terrier

Terrier FHX owner's manual

Vega Absolute Smart-MS0101 user manual

Vega Absolute

Vega Absolute Smart-MS0101 user manual

RAM CSS300 user manual

RAM

RAM CSS300 user manual

Notifier B616LP installation instructions

Notifier

Notifier B616LP installation instructions

C.Nord CN-Magnetic-Mini installation guide

C.Nord

C.Nord CN-Magnetic-Mini installation guide

SGB DLR-G Documentation

SGB

SGB DLR-G Documentation

SPX RADIODETECTION RD5100 H2O+ Operation manual

SPX

SPX RADIODETECTION RD5100 H2O+ Operation manual

Optex VX-402R installation instructions

Optex

Optex VX-402R installation instructions

Phoenix ISL SP-ARC user manual

Phoenix ISL

Phoenix ISL SP-ARC user manual

Aprilaire Z10IDT Installation and operator's manual

Aprilaire

Aprilaire Z10IDT Installation and operator's manual

Honeywell DT7235T installation instructions

Honeywell

Honeywell DT7235T installation instructions

AEMC 6681 user manual

AEMC

AEMC 6681 user manual

UEi CD200 instruction manual

UEi

UEi CD200 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.