6. MODEM
This unit has support for connecting a modem to the
network. An external modem is required, as well as a
special cable for interconnection with the GOLD. In this
way, one or more GOLD air handling units can be moni-
tored via one modem. In the event of an alarm, an alarm
message is e-mailed to the user who can then establish a
connection via modem to the network and use the web
interface available to him. A browser with support for Java
is required. See the web instructions for particulars of how
to configure this function.
Power
Modem
Hub/Switch
GOLD
Modem
Ordinary
modem cable
Special cable
5. DIGITAL INPUTS
(Applicable to Program Version 4.00.0 and newer)
5.1 General
The unit is equipped with 2 digital inputs. The status of
the inputs can then be read as 2 parameters in the report
(Digital in 1 and Digital in 2) via the network.
If the built-in web page is used, the inputs are designed
for forwarding alarms. Provision is available for free alarm
text and input inversion. It is also possible to e-mail alarms.
5.2 Electrical connection
The digital input is rated for a 10-30 V DC supply. The con-
trol unit of the Version B GOLD units has terminal blocks
for supplying 12 V DC current.
TBLZ-1/2-1-2-41 Communication unit
- + - +
17 18 19 20
- 10-30VDC + - 10-30VDC +
Digital in 1 Digital in 2