manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. System Sensor
  6. •
  7. Marine Equipment
  8. •
  9. System Sensor MASS12LO User manual

System Sensor MASS12LO User manual

D900-05-00 1 I56-496-16
MA12/24D* Electronic Sounder,
SS12LO, SS24LO*, SS24M*
Electronic Strobe, MASS12LO,
MASS12M, MASS24LO*, MASS24M*
Sounder/Strobe Combined
*ULC models add suffix “A”; strobes and sounder/strobes available in 24VDC only
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
General Description
The National Fire Protection Association has published standards
and recommended practices for the installation and use of the
listed appliances. It is recommended that the installer be familiar
with these requirements, with local codes, and any special re-
quirements of the authority having jurisdiction.
The electronic Multi-Alert sounder and the signaling strobe are in-
tended to be connected to the alarm indicating circuit of a listed
fire alarm control panel. Both are compatible with DC line super-
vision. The model MA12/24D is suitable for connection to either a
12 or 24 volt panel. Models SS24LO, SS24M, MASS24LO and
MASS24M require 24 volt panels; models SS12LO, MASS12LO and
MASS12M require 12 volt panels. Horn, strobe, or combination
strobe models may be used with panels that have full wave recti-
Sound (Hz) Clips on Tabs Current (mA) ( Note 1) Output (dBA) UL (dBA) Ratings
( Note 4) DC Regulated/ (Note 2) (Note 3)
FWR Unfiltered
12V 24V 30V 12V 24V 12V 24V
Slow Whoop ABC 21/40 38/56 46/72 85 92 79 85
800 Continuous BC 15/24 28/45 35/55 87 93 79 85
800/1000 Alternating AC 17/32 34/46 43/58 85 92 79 85
2400 Interrupted AB 19/23 35/56 43/64 89 90 79 85
2400 Continuous C 21/31 38/59 46/73 85 94 79 85
1200 Interrupted B 13/19 23/33 27/41 85 91 75 82
Swept Frequency A 17/24 34/47 43/60 85 92 79 85
Fast Warble NONE 15/27 30/47 38/59 85 92 79 85
Note 1: Total current for horn/strobe combinations = horn current +
strobe current; refer to tables 1 and 2.
Note 2: Sound output measured in anechoic room at 10 feet.
Note 3: Sound output measured in UL reverberant room.
Note 4: See Figure 4 for tab clip removal & storage.
Note 5: All horn or combination strobe models can be powered using
full wave rectified unfiltered supplies.
Under no circumstances can
the SS24 or MASS24 input volt-
age exceed 33 VDC or be less
than 18 VDC. Under no cir-
cumstances can the SS12 or
MASS12 input voltage exceed
18.7 VDC or be less than 9.6
VDC. Under no circumstances
can the MA12/24D input volt-
age exceed 33 VDC or be less
than 9.6 VDC.
Table 2. Sound output and current ratings for the MA12/24D:
Model Supply Operating Operating Current Peak Minimum Output
Voltage Current from from Rectified Current @ 100% Viewing
Regulated Supply Unfiltered Supply Angle (see Fig. 3)
(VDC) (mA) (mA, RMS) (mA) (Candela)
SS12LO 12-17 50 80 550 1.5
SS24LOA 22.5-30 (.22@-35oC)
SS24MA 22.5-30 (5.9 @-35oC)
SS24LO 22.5-30 25 45 225 1.5
(.22@-35oC)
SS24M 22.5-30 75 125 450 15
(5.9 @-35oC)
Table 1. SS12/24 electrical and light ratings:
fied, unfiltered supplies. The MA12/24D sounder and MASS12/24
sounder/strobes are suitable for outdoor applications (–35°C to
66°C) when used with a Weatherproof Back Box (Model WBB) as
tested by UL. In Canada, rigid steel conduit must be used when
installing the Weatherproof Back Box. The light output of the
SS12LO, SS24LO, MASS12LO and MASS24LO is 1.5 cd min
@100% viewing angle. The light output of the SS24M, MASS12M,
and MASS24M is 15 cd min @100% viewing angle (See Figure 3).
There are eight different sounds which can be selected on the
electronic sounder by adding or removing tab clips (see Figure 4).
The sound selected will determine the maximum current and
sound power output per device. See Table 2 for these values.
Technical Manuals Online! - http://www.tech-man.com
D900-05-00 2 I56-496-16
To calculate battery requirements, use current values shown on page 1. It
should be noted, however, that there is an in-rush current associated with
strobe power-up. This information may be used in consideration of fuse
selection.
Independent Sounder/Strobe Operation:
There may be applications where it is desirable to drive the
sounder and strobe as independent devices. The System Sensor
sounder/strobe combination model MASS12 or MASS24 is easily
configured for this feature. The terminal connection for this appli-
cation is shown in the wiring diagram Figure 8. It must be noted
that for this particular operation the PC TABS must be broken off.
Independent strobe operation in a “coded” system requires a
separate “non-coded” power supply for the strobe.
Installation
A. General:
Slotted head screws are used to attach each device or combina-
tion of devices to the electrical outlet box. Phillips head screws
are used to attach accessories to the horn. Refer to Figures 5, 6,
7 and 8 for wiring methods.
CAUTION
Do not loop wires under the terminal screw. Wires connecting the
device to the panel must be broken at the device terminal connec-
tion in order to maintain electrical supervision.
The sounder is 1-1/4"deep. Back boxes should be 4"square by 1-
1/2"deep minimum; 2-1/8"deep is recommended.
B. Sounder/Strobe combination mounting:
Determine the two holes which will be used to mount the
sounder/strobe combination to the electrical outlet box. Use
the remaining holes to attach the strobe to the sounder with
two phillips head screws.
1. Surface Mount: (See Fig. 11)
2. Semi Flush Mount: (See Fig. 12 and 15)
C. Sounder mounting:
1. Surface Mount : (See Fig. 9)
2. Semi Flush Mount: (See Fig. 12 and 15)
3. Flush Mount: (See Fig. 14)
Flush mounting requires the use of the deep box BB-D or
equivalent. Determine which of the two holes will be used to
attach the device to the box. Mount the flush plate to the
sounder using the two 1-5/16-inch phillips head screws and
two square nuts through the remaining two holes.
D. Strobe mounting:
1. Surface Mount: (See Fig. 10)
2. Semi Flush Mount: (See Fig. 13)
Installation procedures must conform to appropriate agency re-
quirements including but not limited to the following:
NFPA 72, NEC ART. 760 ET.AL., CAN/ULC-S524, CEC PART 1 SEC
32 (ULC models have suffix "A").
CAUTION
The rated output of the sounder is specified at 10 feet. It should
not be assumed that the output will meet the NFPA requirement
of 15 dB over ambient noise at all locations within a room. Addi-
tional sounders may be needed to ensure sound output level com-
plies with NFPA requirements.
WARNING
Limitations Of Sounder/Strobes
The sounder and/or strobe will not work without power. The sounder/
strobe gets its power from the fire/security panel monitoring the alarm
system. If power is cut off for any reason, the sounder/strobe will not pro-
vide the desired audio or visual warning.
The sounder may not be heard. The loudness of the sounder meets (or
exceeds) current Underwriters Laboratories’ standards. However, the
sounder may not alert a sound sleeper or one who has recently used drugs
or has been drinking alcoholic beverages. The sounder may not be heard if
it is placed on a different floor from the person in hazard or if placed too
far away to be heard over the ambient noise such as traffic, air condition-
ers, machinery or music appliances that may prevent alert persons from
hearing the alarm. The sounder may not be heard by persons who are
hearing impaired.
The signal strobe may not be seen. The electronic visual warning signal
uses an extremely reliable xenon flash tube. It flashes at least once every
three seconds and exceeds current Underwriters Laboratories standards
for private mode viewing. The visual warning signal is suitable for direct
viewing and must be installed within an area where it can be seen by
building occupants. The strobe must not be installed in direct sunlight or
areas of high light intensity (over 60 foot candles) where the visual flash
might be disregarded or not seen. The strobe may not be seen by the visu-
ally impaired and is not intended to meet American Disabilities Act (ADA)
requirements.
The signal strobe may cause seizures. Individuals who have positive
photic response to visual stimuli with seizures, such as persons with epi-
lepsy, should avoid prolonged exposure to environments in which strobe
signals, including this strobe, are activated.
The signal strobe cannot operate from coded power supplies.Coded
power supplies produce interrupted power. The strobe must have an unin-
terrupted source of dc power in order to operate correctly. System Sensor
recommends that the sounder and signal strobe always be used in combi-
nation so that the risks from any of the above limitations are minimized.
Figure 1. 12V strobe in-rush current: Figure 2. 24V strobe in-rush current:
1A/div
200
µ
S/div
1A/div
200
µ
S/div
This in-rush current, as can be seen in Figure 1 for the 12V strobe, typi-
cally peaks at 3A and drops to nominal in 600
µ
S.
For the 24V strobe, as shown in Figure 2, the in-rush current typically
peaks at 7.0A, then drops to nominal in 800
µ
S.
Technical Manuals Online! - http://www.tech-man.com
D900-05-00 3 I56-496-16
MA12/24D
A
B
B
A
BB-STD
1. Complete Field Wiring. (See Fig. 5)
2. Screw Sounder to Box with A.
3. Fill Remaining Holes with Screw B.
A78-1593-00
A78-1137-00
A78-1137-29
A78-1137-03
F
I
R
E
60% 60%
100%100% 100%
(REF)
7%
60% 60%
7%
A78-2167-00
Figure 3: Light output vs. viewing angle:
CLIP
STORAGE CLIPS REMOVED OR
ADDED TO SELECT
DESIRED TONE.
COVER SLOT
TAB A
TAB B
TAB C
FOR STORING UNUSED CLIPS:
SLIDE COVER BACK TO ALIGN COVER SLOT
WITH CLIP STORAGE POST.
SLIDE COVER
FOR CLIP STORAGE
USE A
SMALL-
BLADED
SCREWDRIVER
TO REMOVE
CLIPS
TONE
SELECTION TABS
Figure 4:
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
Figure 5. Multi-Alert Sounder:
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
+–
Figure 6. Strobe only (SS Series only):
A78-2467-01
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
Note: Use uncoded supply only.
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
Figure 7. Multi-Alert Sounder and Strobe Multi-Alert
Sounder and Strobe operating in tandem:
A78-1137-01
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
+ VDC
– VDC
STROBE
SOUNDER
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
Non-
Coded
Supply
Can Be
Coded
Supply
Caution: Break off P.C.B. Tabs
Figure 8. Operating independently:
Figure 9. Sounder surface mount:
Screw types used in Figures 9 through 15
A = 8-32x1-7/16" Slot
B = #8 Sheet Metal Phillips
C = 8-32x1-5/16" Phillips
D = #8 Square Nut
E = 8-32x5/8" Slot
F = 8-32x2-3/4" Slot
G = 6-32x5/8" Slot
Technical Manuals Online! - http://www.tech-man.com
D900-05-00 4 I56-496-16
© System Sensor 1996
1. Complete field wiring. (See Fig. 6)
2. Screw strobe to box with screw A.
3. Fill remaining holes with screw B.
A78-1137-04 1. Screw strobe to sounder with screw B.
2. Complete field wiring. (See Fig. 7 & 8)
3. Screw sounder/strobe to box with screw A.
A78-1137-15
1. Screw strobe to plate with screw C.
2. Complete field wiring. (See Fig. 6)
3. Screw strobe plate to box with screw A. A78-1137-17A78-1137-26
1. Screw plate to box with screw E.
2. Complete field wiring. (See Fig. 5, 7, and 8)
3. Screw sounder or sounder/strobe to plate with screw A.
4. Fill remaining holes with screw B.
A
B
B
G
G
MA 12/24
MP-SF
Plaster
Ring
Standard
Backbox
A
1. Fasten MP-F plate to sounder with screws C and nuts D.
2. Complete field wiring. (See Fig. 5)
3. Screw plate sounder to box with screws F.
1. Plaster ring should be properly mounted to electrical box
with screws supplied with box.
2. Screw plate to plaster ring with screw G.
3. Complete field wiring. (See Fig. 5, 7, and 8)
4. Screw sounder or sounder/strobe to plate with screw A.
5. Fill remaining holes with screw B.
A78-1137-08 A78-1137-20
C
FF
C
MP-F
MA 12/24D
D
D
BB-D
BB-STD
B
A
A
B
Signal Strobe
Figure 10. Strobe surface mount:
MA12/24D
BB-STD
A
B
B
A
Signal Strobe
Figure 11. Sounder/Strobe surface mount:
STANDARD
BACKBOX
E
MP-SF
MA 12/24D
EB
BA
A
Figure 12. Sounder or Sounder/Strobe semi-flush
mount:
BB-STD
MP-SF
C
C
A
A
Signal Strobe
Figure 13. Strobe semi-flush mount:
Figure 14. Sounder flush mount (deep box required): Figure 15. Sounder or Sounder/Strobe semi-flush
mount with plaster ring:
Technical Manuals Online! - http://www.tech-man.com
D900-01-00 1 I56-650-16
SS12/24ADA* Series Strobes and
MASS12/24ADA* Series Horn/Strobes
for Fire Protective Signaling Systems
*ULC models add suffix “A”; strobes and sounder/strobes available in 24VDC,
15cd only
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
General Description
The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the listed appliances. It is recommended that the
installer be familiar with these requirements, local codes,
and any special requirements of the local fire authority hav-
ing jurisdiction.
The Multi-Alert sounder and signaling strobe are intended
to be connected to the alarm indicating circuit of a UL-
listed fire alarm control panel. Both are compatible with DC
line supervision. The electronic sounder can be connected
Sound (Hz) Clips on Tabs Current (ma) Output (dBA)
UL (dBA)
( Note 1) DC Regulated/ (Note 3)
Ratings
FWR Unfiltered (Note 4)
12V 24V 30V 12V 24V 12V 24V
Slow Whoop ABC 21/40 38/56 46/72 85 92 79 85
800 Continuous BC 15/24 28/45 35/55 87 93 79 85
800/1000 Alternating AC 17/32 34/46 43/58 85 92 79 85
2400 Interrupted AB 19/23 35/56 43/64 89 90 79 85
2400 Continuous C 21/31 38/59 46/73 85 94 79 85
1200 Interrupted B 13/19 23/33 27/41 85 91 75 82
Swept Frequency A 17/24 34/47 43/60 85 92 79 85
Fast Warble NONE 15/27 30/47 38/59 85 92 79 85
Note 1: See Figure 2 for tab clip removal & storage.
Note 2: All models can be powered using full wave rectified unfiltered
supplies. Under no circumstances can SS24ADA or
MASS24ADA series devices input voltage exceed 33 VDC or be
less than 16 VDC (16-33Vrms for full-wave rectified, unfiltered
supplies). Under no circumstances can the MA12/24D input
Table 1. SS12/24ADA Series electrical ratings:
Model Supply
Voltage
Range
Operating Current from Regulated Supply Operating Current from Full-Wave Rectified Unfiltered
Supply
Average
Operating
Current
Peak
Current
(mA)
20/30V
Peak
Current
(mA)
10.5V/17V
Inrush
Current
(mA in
access of
Peak)
Average
Operating
Current
(mArms)
Peak Current
(mA)
20Vrms/

30Vrms
Peak Current
(mA)
10.5Vrms/
17Vrms
Inrush Current
(Amps in excess
of Peak)
SS24110ADA
SS24110ADAB 20-30V 210 470/500 - 0 245 400/500 - .080
SS2475ADA
SS2475ADAB 20-30V 170 385/400 - 0 200 320/370 - .040
SS2415ADA
SS2415ADAB 20-30V 75 160/180 - 0 90 275/290 - .020
SS1215ADA
SS1215ADAB 10.5-17V 170 - 360/380 0 200 - 330/380 .020
SS241575ADA
SS241575ADAB 20-30V 93 210/220 -- 0 120 275/290 -- 1.0
SS121575ADA
SS121575ADAB 10.5-17V 225 -- 510/560 0 270 -- 500/530 .020

SS2415ADAA 20-30V 175 360/380 -- 0 200 330/380 -- .020
NOTE: Inrush current du-
ration is less than
20 microseconds
(.00002 seconds).
Table 2. Sound Output and Current Ratings for the MA12/24D:
voltage exceed 33 VDC or be less than 9.6 VDC. Under no cir-
cumstances can a SS12ADA or MASS12ADA series device input
voltage exceed 18.7 VDC or be less than 9.6 VDC (9.6 -
18.7Vrms for full-wave rectified, unfiltered supplies).
Note 3: Measured at 10 feet in an anechoic chamber.
Note 4: Measured in a UL reverberant room.
to either 12 or 24 VDC panels. Models SS2415ADA,
SS2475ADA, SS24110ADA, SS241575ADA, and combina-
tion models incorporating these strobes, require 24 volt
panels. Models SS1215ADA, SS121575ADA,
MASS1215ADA , and MASS121575ADA require 12 volt pan-
els. Panels may have full-wave rectified, unfiltered power
supplies. The strobes produce one flash per second (nomi-
nal) with continuous nominal voltage applied.
The MA12/24D is suitable for outdoor applications (-35°to
66°C) when it is used with a WBB Weatherproof Back Box.
The signaling strobe is rated for 0°to 49°C and is NOT
Technical Manuals Online! - http://www.tech-man.com
D900-01-00 2 I56-650-16
suitable for outdoor use.
The rated light output of the SS2415ADA, SS1215ADA,
SS241575ADA, SS121575ADA, MASS2415ADA,
MASS241575ADA, MASS1215ADA, and MASS121575ADA
is 15 cd (See Figure 1).
The rated light output of the SS2475ADA and
MASS2475ADA is 75 cd (See Figure 1).
The rated light output of the SS24110ADA and
MASS24110ADA is 110 cd (See Figure 1).
NOTE: The light output at 0°viewing angle for SS12/
241575ADA and MASS12/241575ADA models is 75
cd (See Figure 1).
Any one of eight sounds can be selected on the electronic
sounder, as indicated in Table 2. The sound selected deter-
mines the maximum current and sound power output per
device. See Table 1 for these values.
Independent Sounder/Strobe Operation
There may be applications where it is desirable to drive the
sounder and strobe as independent devices. The System
Sensor MASS12/24ADA series sounder/strobes are easily
configured for this capability. The terminal connection for
this application is shown in Figure 6. Independent strobe
operation in a coded system requires a separate uncoded
power supply for the strobe.
Installation
A. General:
Slotted head screws are used to attach each device or
combination of devices to the electrical outlet box.
Phillips head screws are used to attach accessories to the
horn. Refer to Figures 3,4,5, and 6 for wiring methods.
Notes: Do not loop wires under the terminal screw. Wires
connecting the device to the panel must be broken
The Sounder and/or Strobe will not work without power. The sounder/
strobe gets its power from the fire/security panel monitoring the alarm
system. If power is cut off for any reason, the sounder/strobe will not pro-
vide the desired audio or visual warning.
The Sounder may not be heard. The loudness of the sounder meets (or
exceeds) current Underwriters Laboratories’ standards. However, the
sounder may not alert a sound sleeper or one who has recently used drugs
or has been drinking alcoholic beverages. The Sounder may not be heard
if it is placed on a different floor from the person in hazard or if placed too
far away to be heard over the ambient noise such as traffic, air condition-
ers, machinery or music appliances that may prevent alert persons from
hearing the alarm. The Sounder may not be heard by persons who are
hearing impaired.
The Signal Strobe may not be seen. The electronic visual warning signal
that flashes at least once every three seconds meets or exceeds current Un-
derwriters Laboratories’ standard 1971 and uses an extremely reliable xe-
non flash tube. The visual warning signal is suitable for direct viewing and
must be installed within an area where it can be seen by building occu-
pants. The strobe must not be installed in direct sunlight or areas of high
light intensity (over 60 foot candles) where the visual flash might be disre-
garded or not seen. The strobe may not be seen by the visually im-
paired.
The signal strobe may cause seizures. Individuals who have a positive
photic response to visual stimuli with seizures, such as epileptics, should
avoid prolonged exposure to environments in which strobe signals, in-
cluding this strobe, are activated.
System Sensor recommends that the Multi-Alert Sounder and Signal
Strobe always be used in combination so that the risks from any of the
above limitations are minimized.
The signal strobe cannot operate from coded power supplies. Coded
power supplies produce interrupted power. The strobe must have an unin-
terrupted source of dc power in order to operate correctly.
WARNING
The Limitations of Sounder/Strobes
at the device terminal connection in order to main-
tain electrical supervision. Strobe and strobe/
horn combination are designed for wall mount-
ing ONLY.
The sounder is 1-1/4"deep. Back boxes must be 4"
square by at least 1-1/2"deep – 2-1/8"deep is
recommended.
All strobes must be mounted so that the top of the lens is
24 inches (61 cm) below ceilings or as required by the
authority having jurisdiction.
B. Sounder mounting:
1. Surface Mount: (See Fig. 7)
2. Semi Flush Mount: (See Fig. 10 and 13)
3. Flush Mount: (See Fig. 12)
C. Sounder/Strobe combination mounting:
1. Surface Mount : (See Fig. 9)
2. Semi Flush Mount: (See Fig. 10 and 13)
Flush mounting requires the use of the deep box (Part #
BB-D) or equivalent. Determine which of the two device
holes will be used to attach the device to the box. Mount
the flush plate to the sounder using the other two holes
with two 1-inch phillips head screws and two square
nuts.
D. Strobe mounting:
1. Surface Mount: (See Fig. 8)
2. Semi Flush Mount: (See Fig. 11)
Installation procedures must conform to all applicable
codes and the requirements of the authority having
jurisdiction.
NOTE: The rated output of the sounder is specified at 10
feet. It cannot be assumed that the output will
meet the NFPA standard of 15 dB over ambient
noise at all locations within a room. Additional
sounders may be needed to ensure sound output
level complies with NFPA requirements.
Technical Manuals Online! - http://www.tech-man.com
D900-01-00 3 I56-650-16
LIGHT
0˚
–45˚
45˚
90˚ –90˚
1. Complete field wiring. (See Fig. 5)
2. Screw sounder to box with screw A.
3. Fill remaining holes with screw B.
Degrees % of Rating
0 100
5 - 25 90
30 - 45 75
50 55
55 45
60 40
65 35
70 35
75 30
80 30
85 25
90 25
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
Note: Use uncoded supply only.
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
(-)
INOUT
STROBE
ONLY
(-)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
From
panel or
previous
device
To Next
Device
or EOL
- VDC
+ VDC
MA12/24D
A
B
B
A
BB-STD
A78-1137-03
A78-1137-29
A78-1137-00
A78-2167-00
Figure 1. Vertical and horizontal light distribution:
CLIP
STORAGE CLIPS REMOVED OR
ADDED TO SELECT
DESIRED TONE.
COVER SLOT
TAB A
TAB B
TAB C
FOR STORING UNUSED CLIPS:
SLIDE COVER BACK TO ALIGN COVER SLOT
WITH CLIP STORAGE POST.
SLIDE COVER
FOR CLIP STORAGE
USE A
SMALL-
BLADED
SCREWDRIVER
TO REMOVE
CLIPS
TONE
SELECTION TABS
Figure 2: Figure 3. Multi-alert sounder:
Figure 4. Strobe: Figure 5. Multi-alert sounder and strobe operating in
tandem:
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
+ VDC
– VDC
STROBE
SOUNDER
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
Non-
Coded
Supply
Can Be
Coded
Supply
Caution: Break off P.C.B. Tabs
Figure 6. Multi-alert sounder and strobe operating
independently:
A78-1137-01
Figure 7. Sounder surface mount:
Screw types used in figure 9 to 15
A = 8-32x1-7/16" Slot
B = #8 Sheet Metal Phillips
C = 8-32x1" Phillips
D = #8 Sq. Nut
E = 8-32x5/8" Slot
F = 8-32x2-3/4" Slot
G = 6-32x5/8" Slot
Technical Manuals Online! - http://www.tech-man.com
D900-01-00 4 I56-650-16
© System Sensor 1996
A78-2514-00 A78-2515-00
A78-2516-00
A78-1137-08
C
FF
C
MP-F
MA 12/24D
D
D
BB-D
A
A
B
B
G
G
MA 12/24
MP-SF
Plaster
Ring
Standard
Backbox
A78-1137-11
A78-2517-01
1. Complete field wiring.
2. Screw strobe to box with screw A.
3. Fill remaining holes with screw B.
1. Complete field wiring.
2. Screw sounder/strobe to box with screw A.
3. Fill remaining screw holes with screw B
1. Screw plate to box with screw E.
2. Complete field wiring. (See Fig. 3, 4, 5, and 6)
3. Screw sounder or sounder/strobe
to plate with screw A.
4. Fill remaining holes with screw B.
1. Screw strobe to plate with
screw C.
2. Complete field wiring.
3. Screw strobe plate to box with
screw A.
1. Screw sounder to plate.
2. Complete field wiring.
3. Screw plate sounder to box
with screw F.
1. Plaster ring should be properly mounted to electrical box with
screws supplied with box.
2. Screw plate to plaster ring with screw G.
3. Complete field wiring.
4. Screw sounder/strobe to plate with screw A.
5. Fill remaining holes with screw B.
B
A
AB
Signal Strobe
Standard
Backbox
TOP
MA-12/24D
A
B
B
A
Signal Strobe
Standard
Backbox
Figure 8. Strobe surface mount: Figure 9. Sounder/strobe surface mount:
MP-SF
MA-12/24D
B
B
STANDARD
BACKBOX
A
A
E
E
Figure 10. Sounder or sounder/strobe semi-flush
mount:
MP-SF
Signal Strobe
TOP
STANDARD
BACKBOX
C
C
A
A
Figure 11. Strobe semi-flush mount:
Figure 12. Sounder flush mount (deep box required): Figure 13. Sounder or sounder/strobe semi-flush
mount with plaster ring:
Technical Manuals Online! - http://www.tech-man.com
D900-06-00 1 I56-750-57
SS24ADAS Series Strobes and
MASS24ADAS Series Synchronized
Horn/Strobes for Fire Protective
Signaling Systems
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
General Description
The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the listed appliances. It is recommended that the
installer be familiar with these requirements, with local
codes, and any special requirements of the local fire au-
thority having jurisdiction.
The Multi-Alert sounder and signaling strobe are intended
to be connected to the alarm indicating circuit of a UL-
listed fire alarm control panel and is compatible with DC
line supervision. The electronic sounder can be connected
to either 12 or 24 VDC panels. Models SS2415ADAS,
SS241575ADAS, and combination models incorporating
these strobes, require 24 volt panels. Panels may have full-
wave rectified, unfiltered power supplies. The strobes are
synchronized and flash at a rate of one flash per second
with continuous voltage applied. SS24ADAS, SS24ADA,
MASS24ADAS, and MASS24ADA series devices may be
combined in the same zone.
Model Supply Operating Current from Operating Current from Full-Wave
Voltage Regulated Supply Rectified Unfiltered Supply
Range
SS2415ADAS 20-30V 106 200 5.0/7.0 125 250 5.0/7.0
SS241575ADAS 20-30V 195 350 5.0/7.0 180 395 5.0/7.0
Average Peak Inrush Average Peak Inrush
Operating Current Current Operating Current Current
Current (mA) (Amps) Current (mA) (Amps)
(mA) 20/30 (mArms) 20/30
Vrms Vrms
NOTE: In-rush current du-
ration is less than 20
microseconds
(.00002 seconds).
Table 2. Sound output and current ratings for the MA12/24D:
Sound (Hz) Clips on Current (mA) Output (dBA)
UL (dBA)
Tabs DC Regulated/ (Note 3)
Ratings
(Note 1) FWR Unfiltered (Note 4)
12V 24V 30V 12V 24V 12V 24V
Slow Whoop ABC 21/40 38/56 46/72 85 92 79 85
800 Continuous BC 15/24 28/45 35/55 87 93 79 85
800/1000 Alternating AC 17/32 34/46 43/58 85 92 79 85
2400 Interrupted AB 19/23 35/56 43/64 89 90 79 85
2400 Continuous C 21/31 38/59 46/73 85 94 79 85
1200 Interrupted B 13/19 23/33 27/41 85 91 75 82
Swept Frequency A 17/24 34/47 43/60 85 92 79 85
Fast Warble NONE 15/27 30/47 38/59 85 92 79 85
Table 1. SS24ADAS Series Electrical Ratings:
Note 1: See Figure 2 for tab clip removal & storage.
Note 2: All models can be powered using full wave rectified unfiltered
supplies. Under no circumstances can SS24ADAS or
MASS24ADAS series devices input voltage exceed 33 VDC or be
less than 16 VDC (18-33Vrms for full-wave rectified, unfiltered
supplies).
Note 3: Measured at 10 feet in an anechoic chamber.
Note 4: Measured in a UL reverberant room.
The MA12/24D sounder is suitable for outdoor applica-
tions (-35°to 66°C) when it is used with a WBB Weather-
proof Back Box. The signaling strobe is rated for 0°to 49°
C and is NOT suitable for outdoor use.
The UL-rated light output of the SS2415ADAS,
SS241575ADAS, MASS2415ADAS, and MASS241575ADAS
is 15 cd (See Figure 1).
NOTE: The light output at 0°viewing angle for
SS241575ADAS and MASS241575ADAS is 75 cd.
Any one of eight sounds can be selected on the electronic
sounder, as indicated in Table 2.
NOTE: SS24ADAS, MASS24ADAS AND MAEH24ADAS
SERIES DEVICES OPERATING IN THE SAME
ZONE WILL NOT BE SYNCHRONIZED IF ENER-
GIZED AT DIFFERENT TIMES (I.E., IF MORE
THAN ONE CONTROLLER IS CONTROLLING THE
SAME ZONE.)
Technical Manuals Online! - http://www.tech-man.com
D900-06-00 2 I56-750-57
The sound selected determines the maximum current and
sound power output per device. SeeTable 2 for these val-
ues.
Independent Sounder/Strobe Operation
There may be applications where it is desirable to drive the
sounder and strobe as independent devices. The System
Sensor MASS12/24ADA series sounder/strobes are easily
configured for this capability. The terminal connection for
this application is shown in Figure 6. Independent strobe
operation in a coded system requires a separate uncoded
power supply for the strobe.
Installation - For Strobe Placement, See NFPA 72,
Chapter 6
A. General: Slotted head screws are used to attach each de-
vice or combination of devices to the electrical outlet
box. Phillips head screws are used to attach accessories
to the horn. Refer to Figures 3,4,5, and 6 for wiring
methods.
NOTES: Do not loop wires under the terminal screw. Wires
connecting the device to the panel must be broken
at the device terminal connection in order to
maintain electrical supervision.
Strobe and strobe/horn combination are de-
signed for wall mounting ONLY.
The sounder is 1-1/4"deep. Back boxes must be 4"
square by at least 1-1/2"deep – 2-1/8"deep box is rec-
ommended.
All strobes must be mounted so that the top of the lens is
24 inches (61 cm) below ceilings or as required by the
authority having jurisdiction.
B. Sounder/Strobe combination mounting:
1. Surface Mount: (See Fig. 10)
2. Semi Flush Mount: (See Fig. 11 and 14)
C. Sounder mounting:
1. Surface Mount : (See Fig. 7)
2. Semi Flush Mount: (See Fig. 11 and 14)
3. Flush Mount (See Fig. 13)
Flush mounting requires the use of the deep box (Part
# BB-D) or equivalent. Determine which of the two
device holes will be used to attach the device to the
box. Mount the flush plate to the sounder using the
other two holes with two 1-inch phillips head screws
and two square nuts.
D. Strobe mounting:
1. Surface Mount: (See Fig. 9)
2. Semi Flush Mount (See Fig.12)
Installation procedures must conform to all applicable
codes and the requirements of the authority having juris-
diction.
NOTE: The rated output of the sounder is specified at 10
feet. It cannot be assumed that the output will
meet the NFPA standard of 15 dB over ambient
noise at all locations within a room. Additional
sounders may be needed to ensure sound output
level complies with NFPA requirements.
The Sounder and/or Strobe will not work without power. The sounder/
strobe gets its power from the fire/security panel monitoring the alarm
system. If power is cut off for any reason, the sounder/strobe will not pro-
vide the desired audio or visual warning.
The Sounder may not be heard. The loudness of the sounder meets (or
exceeds) current Underwriters Laboratories’ standards. However, the
sounder may not alert a sound sleeper or one who has recently used drugs
or has been drinking alcoholic beverages. The Sounder may not be heard
if it is placed on a different floor from the person in hazard or if placed too
far away to be heard over the ambient noise such as traffic, air condition-
ers, machinery or music appliances that may prevent alert persons from
hearing the alarm. The Sounder may not be heard by persons who are
hearing impaired.
The Signal Strobe may not be seen. The electronic visual warning signal
that flashes at least once every three seconds meets or exceeds current Un-
derwriters Laboratories’ standard 1971 and uses an extremely reliable xe-
non flash tube. The visual warning signal is suitable for direct viewing and
must be installed within an area where it can be seen by building occu-
pants. The strobe must not be installed in direct sunlight or areas of high
light intensity (over 60 foot candles) where the visual flash might be disre-
garded or not seen. The strobe may not be seen by the visually impaired.
The signal strobe may cause seizures. Individuals who have a positive
photic response to visual stimuli with seizures, such as epileptics, should
avoid prolonged exposure to environments in which strobe signals, in-
cluding this strobe, are activated.
System Sensor recommends that the Multi-Alert Sounder and Signal
Strobe always be used in combination so that the risks from any of the
above limitations are minimized.
The signal strobe cannot operate from coded power supplies. Coded
power supplies produce interrupted power. The strobe must have an unin-
terrupted source of dc power in order to operate correctly.
Synchronized strobes may not prevent photosensitive reactions to signal
strobes in alarm condition.
WARNING
The Limitations of Sounder/Strobes
Technical Manuals Online! - http://www.tech-man.com
D900-06-00 3 I56-750-57
NOTE: ALL STROBES THAT ARE TO BE IN SYNC MUST BE ON THE SAME POWER CIRCUIT.
LIGHT
0˚
–45˚
45˚
90˚ –90˚
A78-1137-00
A78-2167-00
Percent of
Degrees Rating
0 100
5 - 25 90
30 - 45 75
50 55
55 45
60 40
65 35
70 35
75 30
80 30
85 25
90 25
MA12/24D
A
B
B
A
BB-STD
A78-1137-03
(-)
INOUT
STROBE
ONLY
(-)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
From
panel or
previous
device
To Next
Device
or EOL
- VDC
+ VDC
A78-1137-01
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
Note: Use uncoded supply only.
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
A78-1137-29
CLIP
STORAGE CLIPS REMOVED OR
ADDED TO SELECT
DESIRED TONE.
COVER SLOT
TAB A
TAB B
TAB C
FOR STORING UNUSED CLIPS:
SLIDE COVER BACK TO ALIGN COVER SLOT
WITH CLIP STORAGE POST.
SLIDE COVER
FOR CLIP STORAGE
USE A
SMALL-
BLADED
SCREWDRIVER
TO REMOVE
CLIPS
TONE
SELECTION TABS
Figure 2: Figure 3. Multi-alert sounder:
Figure 4. Multi-alert sounder and strobe operating in
tandem:
Figure 5. Strobe:
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
+ VDC
– VDC
STROBE
SOUNDER
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
Non-
Coded
Supply
Can Be
Coded
Supply
Caution: Break off P.C.B. Tabs
Figure 6. Multi-alert sounder and strobe operating
independently:
Figure 7. Sounder surface mount:
Figure 1. Vertical and horizontal light distribution:
Screw types used in
Figures 9 to 15
A = 8-32x1-7/16" Slot
B = #8 Sheet Metal Phillips
C = 8-32x1" Phillips
D = #8 Square Nut
E = 8-32x5/8" Slot
F = 8-32x2-3/4" Slot
G = 6-32x5/8" Slot
Technical Manuals Online! - http://www.tech-man.com
D900-06-00 4 I56-750-57
© System Sensor 1996
1. Screw plate to box with screw E.
2. Complete field wiring. (See Fig. 3,
4, 5, and 6)
3. Screw sounder or sounder/strobe
to plate with screw A.
4. Fill remaining holes with screw B. A78-2517-01
1. Screw strobe to plate with
screw C.
2. Complete field wiring.
3. Screw strobe plate to box with
screw A.
A78-2516-00
1. Plaster ring should be properly mounted to electrical box
with screws supplied with box.
2. Screw plate to plaster ring with screw G.
3. Complete field wiring. (See Fig. 5, 7, and 8)
4. Screw sounder/strobe to plate with A.
5. Fill remaining holes with screw B.
A
A
B
B
G
G
MA 12/24
MP-SF
Plaster
Ring
Standard
Backbox
A78-1137-11
1. Complete field wiring.
2. Screw plate sounder to Box
with screw F. A78-1137-08
C
FF
C
MP-F
MA 12/24D
D
D
BB-D
A78-2515-00
A78-2514-00
Figure 9. Strobe surface mount:
1. Complete field wiring.
2. Screw sounder/strobe to box
with screw A.
3. Fill remaining screw holes with
screw B.
Figure 10. Sounder/strobe surface mount:
MA-12/24D
A
B
B
A
Signal Strobe
Standard
Backbox
1. Complete field wiring.
2. Screw strobe to box with screw A.
3. Fill remaining holes with Screw B.
B
A
AB
Signal Strobe
Standard
Backbox
TOP
MP-SF
MA-12/24D
B
B
STANDARD
BACKBOX
A
A
E
E
MP-SF
Signal Strobe
TOP
STANDARD
BACKBOX
C
C
A
A
Figure 11. Sounder or sounder/strobe semi-flush
mount:
Figure 12. Strobe semi-flush mount:
Figure 13. Sounder flush mount (deep box required): Figure 14. Sounder or sounder/strobe semi-flush
mount with plaster ring:
Technical Manuals Online! - http://www.tech-man.com
D900-11-00 1 I56-759-07
MA12/24EH* Electronic Sounder;
SS12LO, SS12M, SS24LO*, SS24M*
Electronic Strobes; MAEH12LO,
MAEH12M, MAEH24LO*, MAEH24M*
Sounder/Strobes Combined
*ULC models add suffix “A”; available in 24V models only.
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
NOTICE: This manual should be left with the owner/user of this
equipment.
General Description
The National Fire Protection Association has published standards
and recommended practices for the installation and use of the
listed appliances. It is recommended that the installer be familiar
with these requirements, with local codes, and any special re-
quirements of the authority having jurisdiction.
The electronic Multi-Alert sounder and the signaling strobe are in-
tended to be connected to the alarm indicating circuit of a listed
fire alarm control panel. Both are compatible with DC line super-
vision. The model MA12/24EH is suitable for connection to either
a 12 or 24 volt panel. Models SS24LO, SS24M, MAEH24LO and
MAEH24M require 24 volt panels; models SS12LO, SS12M,
Sound (Hz) Clips on Tabs Current (mA) ( Note 1) Output (dBA) UL (dBA)
( Note 4) DC Regulated/ (Note 2) Ratings
FWR Unfiltered (Note 3)
12V 24V 30V 12V 24V 12V 24V
Fast Whoop ABC 21/40 38/56 46/72 85 92 79 85
800 Continuous BC 15/24 28/45 35/55 87 93 79 85
800/1000 Fast-Dual AC 17/32 34/46 43/58 85 92 79 85
Chirp AB 19/23 35/56 43/64 89 90 79 85
2400 Continuous C 21/31 38/59 46/73 85 94 79 85
Bell B 13/19 23/33 27/41 85 91 75 82
Laser A 17/24 34/47 43/60 85 92 79 85
Electro-Mechanical NONE 15/27 30/47 38/59 85 92 79 85
Model Supply Operating Operating Current Peak Minimum Output
Voltage Current from from Rectified Current @ 100% Viewing
Regulated Supply Unfiltered Supply Angle (see Fig. 3)
(VDC) (mA) (mA, RMS) (mA) (Candela)
SS12LO 12-17 50 80 550 1.5
SS24LOA 22.5-30 (.22@-35oC)
SS12M 12-17 180 300 440 15
SS24MA 22.5-30 (5.9 @-35oC)
SS24LO 22.5-30 25 45 225 1.5
(.22@-35oC)
SS24M 22.5-30 75 125 450 15
(5.9 @-35oC)
Table 2. Sound output and current ratings for the MA12/24EH:
Table 1. SS12/24 electrical and light ratings:
Note 4: See Figure 4 for tab clip removal & storage.
Note 5: All horn or combination strobe models can be powered
using full wave rectified unfiltered supplies.
Under no circumstances can the
input voltage:
for the SS24 or MAEH24 exceed
33 VDC or be less than 18 VDC.
for the SS12 or MAEH12 ex-
ceed 18.7 VDC or be less than
9.6 VDC.
for the MA12/24EH exceed 33
VDC or be less than 9.6 VDC.
Note 1: With 1.5 cd strobes add 50 mA @ 12V, 25 mA @ 24V.
With 15 cd strobes add 180 mA @ 12V, 75 mA @ 24V.
Note 2: Sound output measured in anechoic room at 10 feet.
Note 3: Sound output measured in UL reverberant room.
MAEH12LO and MAEH12M require 12 volt panels. Horn, strobe,
or combination strobe models may be used with panels that have
full wave rectified, unfiltered supplies. The MA12/24EH sounder
and MAEH12/24 sounder/strobes are suitable for outdoor appli-
cations (–35°C to 66°C) when used with a Weatherproof Back
Box (Model WBB) as tested by UL. In Canada, rigid steel conduit
must be used when installing the Weatherproof Back Box. Light
output for the SS12LO, SS24LO, MAEH12LO and MAEH24LO is
1.5 cd min @100% viewing angle. Light output for the SS12M,
SS24M, MAEH12M, and MAEH24M is 15 cd min @100% viewing
angle (See Figure 3).
There are eight different sounds which can be selected on the
electronic sounder by adding or removing tab clips (see Figure 4).
The sound selected will determine the maximum current and
sound power output per device. See Table 2 for these values.
Technical Manuals Online! - http://www.tech-man.com
D900-11-00 2 I56-759-07
To calculate battery requirements, use current values shown on
page 1. It should be noted, however, that there is an in-rush cur-
rent associated with strobe power-up. This information may be
used in consideration of fuse selection. This in-rush current, as
can be seen in Figure 1 for the 12V strobe, typically peaks at 3A
and drops to nominal in 600
µ
S. For the 24V strobe, as shown in
Figure 2, the in-rush current typically peaks at 7.0A, then drops to
nominal in 800
µ
S.
Independent Sounder/Strobe Operation
There may be applications where it is desirable to drive the
sounder and strobe as independent devices. The System Sensor
sounder/strobe combination model MAEH12 or MAEH24 is easily
configured for this feature. The terminal connection for this appli-
cation is shown in the wiring diagram Figure 8. It must be noted
that for this particular operation the PC TABS must be broken off.
Independent strobe operation in a “coded” system requires a
separate “non-coded” power supply for the strobe.
Figure 1. 12V strobe in-rush current:
Figure 2. 24V strobe in-rush current:
1A/div
200
µ
S/div
1A/div
200
µ
S/div
Installation
A. General:
Slotted head screws are used to attach each device or combina-
tion of devices to the electrical outlet box. Phillips head screws
are used to attach accessories to the horn. Refer to Figures 5, 6,
7 and 8 for wiring methods.
CAUTION
Do not loop wires under the terminal screw. Wires connecting the
device to the panel must be broken at the device terminal connec-
tion in order to maintain electrical supervision.
The sounder is 1-1/4"deep. Back boxes should be 4"square by 1-
1/2"deep minimum; 2-1/8"deep is recommended.
B. Sounder/Strobe combination mounting:
Determine the two holes which will be used to mount the
sounder/strobe combination to the electrical outlet box. Use
the remaining holes to attach the strobe to the sounder with
two phillips head screws.
1. Surface Mount: (See Figure 11)
2. Semi Flush Mount: (See Figures 12 and 15)
C. Sounder mounting:
1. Surface Mount : (See Figure 9)
2. Semi Flush Mount: (See Figures 12 and 15)
3. Flush Mount: (See Figure 14)
Flush mounting requires the use of the deep box BB-D or
equivalent. Determine which of the two holes will be used to
attach the device to the box. Mount the flush plate to the
sounder using the two 1-5/16-inch phillips head screws and
two square nuts through the remaining two holes.
D. Strobe mounting:
1. Surface Mount: (See Figure 10)
2. Semi Flush Mount: (See Figure 13)
Installation procedures must conform to appropriate agency re-
quirements including but not limited to the following:
NFPA 72, NEC ART. 760 ET.AL., CAN/ULC-S524, CEC PART 1 SEC
32 (ULC models have suffix "A").
CAUTION
The rated output of the sounder is specified at 10 feet. It should
not be assumed that the output will meet the NFPA requirement
of 15 dB over ambient noise at all locations within a room. Addi-
tional sounders may be needed to ensure sound output level com-
plies with NFPA requirements.
The sounder and/or strobe will not work without power. The sounder/
strobe gets its power from the fire/security panel monitoring the alarm
system. If power is cut off for any reason, the sounder/strobe will not pro-
vide the desired audio or visual warning.
The sounder may not be heard. The loudness of the sounder meets (or
exceeds) current Underwriters Laboratories’ standards. However, the
sounder may not alert a sound sleeper or one who has recently used drugs
or has been drinking alcoholic beverages. The sounder may not be heard if
it is placed on a different floor from the person in hazard or if placed too
far away to be heard over the ambient noise such as traffic, air condition-
ers, machinery or music appliances that may prevent alert persons from
hearing the alarm. The sounder may not be heard by persons who are
hearing impaired.
The signal strobe may not be seen. The electronic visual warning signal
uses an extremely reliable xenon flash tube. It flashes at least once every
three seconds and exceeds current Underwriters Laboratories standards
for private mode viewing. The visual warning signal is suitable for direct
viewing and must be installed within an area where it can be seen by
building occupants. The strobe must not be installed in direct sunlight or
areas of high light intensity (over 60 foot candles) where the visual flash
might be disregarded or not seen. The strobe may not be seen by the visu-
ally impaired and is not intended to meet American Disabilities Act (ADA)
requirements.
The signal strobe may cause seizures. Individuals who have positive
photic response to visual stimuli with seizures, such as persons with epi-
lepsy, should avoid prolonged exposure to environments in which strobe
signals, including this strobe, are activated.
The signal strobe cannot operate from coded power supplies.Coded
power supplies produce interrupted power. The strobe must have an unin-
terrupted source of dc power in order to operate correctly. System Sensor
recommends that the sounder and signal strobe always be used in combi-
nation so that the risks from any of the above limitations are minimized.
WARNING
The Limitations of Sounder/Strobes
Technical Manuals Online! - http://www.tech-man.com
D900-11-00 3 I56-759-07
Light output vs.
viewing angle
A78-1593-00 A78-2167-00
A78-1137-00 A78-2467-01
A78-1137-01
A78-1137-03E
MA12/24EH
A
B
B
A
BB-STD
1. Complete Field Wiring. (See Fig. 5)
2. Screw Sounder to Box with A.
3. Fill Remaining Holes with Screw B.
F
I
R
E
60% 60%
100%100% 100%
(REF)
7%
60% 60%
7%
Figure 3.
CLIP
STORAGE CLIPS REMOVED OR
ADDED TO SELECT
DESIRED TONE.
COVER SLOT
TAB A
TAB B
TAB C
FOR STORING UNUSED CLIPS:
SLIDE COVER BACK TO ALIGN COVER SLOT
WITH CLIP STORAGE POST.
SLIDE COVER
FOR CLIP STORAGE
USE A
SMALL-
BLADED
SCREWDRIVER
TO REMOVE
CLIPS
TONE
SELECTION TABS
Figure 4:
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
Figure 5. Multi-alert sounder:
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
+–
Figure 6. Strobe only (SS series only):
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
Note: Use uncoded supply only.
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
Figure 7. Multi-alert sounder and strobe operating in
tandem:
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
+ VDC
– VDC
STROBE
SOUNDER
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
Non-
Coded
Supply
Can Be
Coded
Supply
Caution: Break off P.C.B. Tabs
Figure 8. Multi-alert sounder and strobe operating
independently:
Figure 9. Sounder surface mount:
A78-1137-29
Screw types used in Figures 9 to 15
A = 8-32x1-7/16" Slot
B = #8 Sheet Metal Phillips
C = 8-32x1-5/16" Phillips
D = #8 Square Nut
E = 8-32x5/8" Slot
F = 8-32x2-3/4" Slot
G = 6-32x5/8" Slot
Technical Manuals Online! - http://www.tech-man.com
D900-11-00 4 I56-759-07
© System Sensor 1996
A78-1137-04 A78-1137-15E
1. Screw strobe to plate with screw C.
2. Complete field wiring. (See Fig. 6)
3. Screw strobe plate to box with screw A.
A78-1137-17A78-1137-26E
1. Complete field wiring. (See Fig. 6)
2. Screw strobe to box with screw A.
3. Fill remaining holes with screw B.
1. Screw strobe to sounder with screw B.
2. Complete field wiring. (See Fig. 7 & 8)
3. Screw sounder/strobe to box with screw A.
A
B
B
G
G
MA 12/24EH
MP-SF
Plaster
Ring
Standard
Backbox
A
1. Fasten MP-F plate to sounder with screw C and nut D.
2. Complete field wiring. (See Fig. 5)
3. Screw plate sounder to box with screw F.
1. Plaster ring should be properly mounted to electrical box with
screws supplied with box.
2. Screw plate to plaster ring with screw G.
3. Complete field wiring. (See Fig. 5, 7, and 8)
4. Screw sounder or sounder/strobe to plate with screw A.
5. Fill remaining holes with screw B.
A78-1137-08E A78-1137-20E
C
FF
C
MP-F
MA 12/24EH
D
D
BB-D
1. Screw plate to box with screw E.
2. Complete field wiring. (See Fig. 5,7, and 8)
3. Screw sounder or sounder/strobe to plate with screw A.
4. Fill remaining holes with screw B.
BB-STD
B
A
A
B
Signal Strobe
Figure 10. Strobe surface mount:
MA12/24EH
BB-STD
A
B
B
A
Signal Strobe
Figure 11. Sounder/strobe surface mount:
STANDARD
BACKBOX
E
MP-SF
MA 12/24EH
EB
BA
A
Figure 12. Sounder or sounder/strobe semi-flush
mount:
BB-STD
MP-SF
C
C
A
A
Signal Strobe
Figure 13. Strobe semi-flush mount:
Figure 14. Sounder flush mount (deep box required): Figure 15. Sounder or sounder/strobe semi-flush
mount with plaster ring:
Technical Manuals Online! - http://www.tech-man.com
D900-10-00 1 I56-760-07
SS12/24ADA* Series Strobes and
MAEH12/24ADA* Series Horn/Strobes
for Fire Protective Signaling Systems
*ULC models add suffix "A"; available only in 24V, 15 cd
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Sound (Hz) Clips on Tabs Current (mA) Output (dBA) UL (dBA) Ratings
( Note 1) DC Regulated/ (Note 3) (Note 4)
FWR Unfiltered
12V 24V 30V 12V 24V 12V 24V
Fast Whoop ABC 21/40 38/56 46/72 85 92 79 85
800 Continuous BC 15/24 28/45 35/55 87 93 79 85
800/1000 Fast Dual AC 17/32 34/46 43/58 85 92 79 85
Chirp AB 19/23 35/56 43/64 89 90 79 85
2400 Continuous C 21/31 38/59 46/73 85 94 79 85
Bell B 13/19 23/33 27/41 85 91 75 82
Laser A 17/24 34/47 43/60 85 92 79 85
Electro-Mechanical NONE 15/27 30/47 38/59 85 92 79 85
Note 1: See Figure 3 for tab clip removal & storage.
Note 2: All models can be powered using full wave rectified unfiltered
supplies. Under no circumstances can SS24ADA or
MAEH24ADA series devices input voltage exceed 33 VDC or be
less than 16 VDC (16-33Vrms for full-wave rectified, unfiltered
supplies). Under no circumstances can the MA12/24EH input
NOTICE: This manual should be left with the owner/user of this
equipment.
General Description
The National Fire Protection Association has published standards
and recommended practices for the installation and use of the
listed appliances.It is recommended that the installer be familiar
with these requirements, with local codes, and any special re-
quirements of the local fire authority having jurisdiction.
The Multi-Alert sounder and signaling strobe are intended to be
connected to the alarm indicating circuit of a UL-listed fire alarm
control panel. Both are compatible with DC line supervision. The
electronic sounder can be connected to either 12 or 24 VDC pan-
Model Supply
Voltage
Range
Operating Current from Regulated Supply Operating Current from Full-Wave Rectified Unfiltered
Supply
Average
Operating
Current
Peak
Current
(mA)
20/30V
Peak
Current
(mA)
10.5V/17V
Inrush
Current
(mA in
access of
Peak)
Average
Operating
Current
(mArms)
Peak Current
(mA)
20Vrms/
30Vrms
Peak Current
(mA)
10.5Vrms/
17Vrms
Inrush Current
(Amps in excess
of Peak)
SS24110ADA
SS24110ADAB 20-30V 210 470/500 - 0 245 400/500 - .080
SS2475ADA
SS2475ADAB 20-30V 170 385/400 - 0 200 320/370 - .040
SS2415ADA
SS2415ADAB 20-30V 75 160/180 - 0 90 275/290 - .020
SS1215ADA
SS1215ADAB 10.5-17V 170 - 360/380 0 200 - 330/380 .020
SS241575ADA
SS241575ADAB 20-30V 93 210/220 -- 0 120 275/290 -- 1.0
SS121575ADA
SS121575ADAB 10.5-17V 225 -- 510/560 0 270 -- 500/530 .020

SS2415ADAA 20-30V 170 360/380 -- 0 200 330/380 -- .020
Table 1. SS12/24ADA Series electrical ratings:
NOTE: In-rush current dura-
tion is less than 20 microsec-
onds (.00002 seconds).
els. Models SS2415ADA, SS2475ADA, SS24110ADA,
SS241575ADA, and combination models incorporating these
strobes, require 24 volt panels. Models SS1215ADA,
SS121575ADA, MAEH1215ADA, and MAEH121575ADA require
12 volt panels. Panels may have full-wave rectified, unfiltered
power supplies. The strobes produce one flash per second (nomi-
nal) with continuous nominal voltage applied.
The MA12/24EH is suitable for outdoor applications (-35°to 66°
C) when it is used with a WBB Weatherproof Back Box. The sig-
naling strobe is rated for 0°to 49°C and is NOT suitable for out-
door use.
The rated light output of the SS2415ADA, SS1215ADA,
Table 2. Sound output and current ratings for the MA12/24EH:
voltage exceed 33 VDC or be less than 9.6 VDC. Under no cir-
cumstances can a SS12ADA or MAEH12ADA series device input
voltage exceed 18.7 VDC or be less than 9.6 VDC (9.6 - 18.7
Vrms for full-wave rectified, unfiltered supplies).
Note 3: Measured at 10 feet in an anechoic chamber.
Note 4: Measured in a UL reverberant room.
Technical Manuals Online! - http://www.tech-man.com
D900-10-00 2 I56-760-07
SS241575ADA, SS121575ADA, MAEH2415ADA,
MAEH1215ADA, MAEH241575ADA, and MAEH121575ADA
is 15 cd (See Figure 1).
The rated light output of the SS2475ADA and
MAEH2475ADA is 75 cd (See Figure 1).
The rated light output of the SS24110ADA and
MAEH24110ADA is 110 cd (See Figure 1).
NOTE: The 15/75 cd strobes have been measured to be 75
cd @ 0°viewing angle (see Figure 1).
Any one of eight sounds can be selected on the electronic
sounder, as indicated in Table 2.
The sound selected determines the maximum current and
sound power output per device. See Table 2 for these
values.
Independent Sounder/Strobe Operation
There may be operations where it is desirable to drive the
sounder and strobe as independent devices. The System
Sensor MAEH12/24ADA series sounder/strobes are easily
configured for this capability. The terminal connection for
this application is shown in Figure 6. It must be noted that
for this particular operation the PC TABS must be broken
off. Independent strobe operation in a coded system re-
quires a separate uncoded power supply for the strobe.
Installation - For Strobe Placement, See NFPA 72,
Chapter 6
A. General:
Slotted head screws are used to attach each device or
combination of devices to the electrical outlet box.
Phillips head screws are used to attach accessories to the
horn. Refer to Figures 2,4,5, and 6 for wiring methods.
The Sounder and/or Strobe will not work without power. The sounder/
strobe gets its power from the fire/security panel monitoring the alarm
system. If power is cut off for any reason, the sounder/strobe will not pro-
vide the desired audio or visual warning.
The Sounder may not be heard. The loudness of the sounder meets (or
exceeds) current Underwriters Laboratories’ standards. However, the
sounder may not alert a sound sleeper or one who has recently used drugs
or has been drinking alcoholic beverages. The Sounder may not be heard
if it is placed on a different floor from the person in hazard or if placed too
far away to be heard over the ambient noise such as traffic, air condition-
ers, machinery or music appliances that may prevent alert persons from
hearing the alarm. The Sounder may not be heard by persons who are
hearing impaired.
The Signal Strobe may not be seen. The electronic visual warning signal
that flashes at least once every three seconds meets or exceeds current Un-
derwriters Laboratories’ standard 1971 and uses an extremely reliable xe-
non flash tube. The visual warning signal is suitable for direct viewing and
must be installed within an area where it can be seen by building occu-
pants. The strobe must not be installed in direct sunlight or areas of high
light intensity (over 60 foot candles) where the visual flash might be disre-
garded or not seen. The strobe may not be seen by the visually im-
paired.
The signal strobe may cause seizures. Individuals who have a positive
photic response to visual stimuli with seizures, such as epileptics, should
avoid prolonged exposure to environments in which strobe signals, in-
cluding this strobe, are activated.
System Sensor recommends that the Multi-Alert Sounder and Signal
Strobe always be used in combination so that the risks from any of the
above limitations are minimized.
The signal strobe cannot operate from coded power supplies. Coded
power supplies produce interrupted power. The strobe must have an unin-
terrupted source of dc power in order to operate correctly.
WARNING
The Limitations of Sounder/Strobes
Notes: Do not loop wires under the terminal screw. Wires
connecting the device to the panel must be broken
at the device terminal connection in order to main-
tain electrical supervision. Strobe and strobe/
horn combination are designed for wall mount-
ing ONLY.
The sounder is 1-1/4"deep. Back boxes must be 4"
square by at least 1-1/2"deep – 2-1/8"deep is recom-
mended.
All strobes must be mounted so that the top of the lens is
24 inches (61 cm) below ceilings or as required by the
authority having jurisdiction.
B. Sounder/Strobe combination mounting:
1. Surface Mount: (See Fig. 9)
2. Semi Flush Mount: (See Fig. 10 and 13)
C. Sounder mounting:
1. Surface Mount : (See Fig. 7)
2. Semi Flush Mount: (See Fig. 10 and 13)
3. Flush Mount: (See Fig. 12)
Flush mounting requires the use of the deep box (Part #
BB-D) or equivalent. Determine which of the two device
holes will be used to attach the device to the box. Mount
the flush plate to the sounder using the other two holes
with two 1-inch phillips head screws and two square
nuts.
D. Strobe mounting:
1. Surface Mount: (See Fig. 8)
2. Semi Flush Mount: (See Fig. 11)
Installation procedures must conform to all applicable
codes and the requirements of the authority having juris-
diction.
NOTE: The rated output of the sounder is specified at 10
feet. It cannot be assumed that the output will
meet the NFPA standard of 15 dB over ambient
noise at all locations within a room. Additional
sounders may be needed to ensure sound output
level complies with NFPA requirements.
Technical Manuals Online! - http://www.tech-man.com
D900-10-00 3 I56-760-07
A78-1137-00A78-2167-00
A78-1137-01
A78-1137-03E
A78-1137-29
1. Complete field wiring.(See Fig. 4)
2. Screw sounder to box with screw A.
3. Fill remaining holes with screw B.
MA12/24EH
A
B
B
A
BB-STD
LIGHT
0˚
–45˚
45˚
90˚ –90˚
PERCENT OF
DEGREES RATING
0 100
5 - 25 90
30 - 45 75
50 55
55 45
60 40
65 35
70 35
75 30
80 30
85 25
90 25
Figure 1. Vertical and horizontal light distribution:
Figure 2. Strobe only:
CLIP
STORAGE CLIPS REMOVED OR
ADDED TO SELECT
DESIRED TONE.
COVER SLOT
TAB A
TAB B
TAB C
FOR STORING UNUSED CLIPS:
SLIDE COVER BACK TO ALIGN COVER SLOT
WITH CLIP STORAGE POST.
SLIDE COVER
FOR CLIP STORAGE
USE A
SMALL-
BLADED
SCREWDRIVER
TO REMOVE
CLIPS
TONE
SELECTION TABS
Figure 3:
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
Figure 4. Multi-alert sounder:
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
Note: Use uncoded supply only.
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
Figure 5. Multi-alert sounder and strobe operating in
tandem:
From
panel or
previous
device
To Next
Device
or EOL
– VDC
+ VDC
+ VDC
– VDC
STROBE
SOUNDER
(–)
INOUT
STROBE
ONLY
(–)
INOUT (+)
INOUT
STROBE
ONLY
(+)
INOUT
Non-
Coded
Supply
Can Be
Coded
Supply
Caution: Break off P.C.B. Tabs
Figure 6. Multi-alert sounder and strobe operating
independently:
Figure 7. Sounder surface mount:
Screw types used in figures 7 to 13
A = 8-32x1-7/16" Slot
B = #8 Sheet Metal Phillips
C = 8-32x1-5/16" Phillips
D = #8 Square Nut
E = 8-32x5/8" Slot
F = 8-32x2-3/4" Slot
G = 6-32x5/8" Slot
Technical Manuals Online! - http://www.tech-man.com
D900-10-00 4 I56-760-07
© System Sensor 1996
A78-2514-00 A78-2515-01E
1. Screw strobe to sounder with screw B.
2. Complete field wiring. (See Fig. 5 & 6)
3. Screw sounder/strobe to box with screw A.
1. Complete field wiring. (See Fig. 2)
2. Screw strobe to box with screw A.
3. Fill remaining holes with screw B.
1. Screw strobe to plate with screw C.
2. Complete field wiring. (See Fig. 2)
3. Screw strobe plate to box with screw A. A78-2516-01
A78-2517-02E
1. Screw plate to box with screw E.
2. Complete field wiring. (See Fig.4, 5, and 6)
3. Screw sounder or sounder/strobe to plate with screw A.
4. Fill remaining holes with screw B.
1. Fasten MP-F plate to sounder with
screws C and nuts D.
2. Complete field wiring. (See Fig. 4)
3. Screw plate sounder to box with
screw F.
C
FF
C
MP-F
MA 12/24EH
D
D
BB-D
A78-1137-08E
1. Plaster ring should be properly mounted to electrical box with
screws supplied with box.
2. Screw plate to plaster ring with screw G.
3. Complete field wiring. (See Fig. 4, 5, and 6)
4. Screw sounder/strobe to plate with screw A and fill remaining
holes with screw B.
A
B
B
G
G
MA 12/24EH
MP-SF
Plaster
Ring
Standard
Backbox
A
A78-1137-21E
B
A
AB
Signal Strobe
Standard
Backbox
TOP
MA12/24EH
B
B
A
Signal Strobe
Standard
Backbox
A
MP-SF
MA-12/24EH
B
BA
A
E
E
MP-SF
Signal Strobe
TOP
STANDARD
BACKBOX
C
C
A
A
Figure 8. Strobe surface mount: Figure 9. Sounder/strobe surface mount:
Figure 10. Sounder or sounder/strobe semi-flush
mount:
Figure 11. Strobe semi-flush mount:
Figure 12. Sounder flush mount (deep box required): Figure 13. Sounder or sounder/strobe semi-flush
mount with plaster ring:
Technical Manuals Online! - http://www.tech-man.com

This manual suits for next models

8

Other System Sensor Marine Equipment manuals

System Sensor B200S-LF User manual

System Sensor

System Sensor B200S-LF User manual

System Sensor B200S User manual

System Sensor

System Sensor B200S User manual

System Sensor B501BHT-2 User manual

System Sensor

System Sensor B501BHT-2 User manual

System Sensor ExitPoint PF24 User manual

System Sensor

System Sensor ExitPoint PF24 User manual

System Sensor B501BHT-2 User manual

System Sensor

System Sensor B501BHT-2 User manual

System Sensor B501BH-2 User manual

System Sensor

System Sensor B501BH-2 User manual

System Sensor B200S-LF-WH User manual

System Sensor

System Sensor B200S-LF-WH User manual

System Sensor B401BH-2 User manual

System Sensor

System Sensor B401BH-2 User manual

System Sensor L Series Technical specifications

System Sensor

System Sensor L Series Technical specifications

System Sensor B200S User guide

System Sensor

System Sensor B200S User guide

System Sensor ExitPoint PF24V User manual

System Sensor

System Sensor ExitPoint PF24V User manual

System Sensor SpectrAlert Advance User manual

System Sensor

System Sensor SpectrAlert Advance User manual

System Sensor LASS-WSS-NC User manual

System Sensor

System Sensor LASS-WSS-NC User manual

System Sensor EBS User manual

System Sensor

System Sensor EBS User manual

Popular Marine Equipment manuals by other brands

RS Aqua WaveRadar Rex Series Faq

RS Aqua

RS Aqua WaveRadar Rex Series Faq

Alula RE616 manual

Alula

Alula RE616 manual

Federal Signal Corporation G-SND instruction manual

Federal Signal Corporation

Federal Signal Corporation G-SND instruction manual

Bennett BOLT Rocker BRC4000 Installation and quick start manual

Bennett

Bennett BOLT Rocker BRC4000 Installation and quick start manual

Dual Electronics Corporation MXD25 Installation & owner's manual

Dual Electronics Corporation

Dual Electronics Corporation MXD25 Installation & owner's manual

Raymarine ST60 Tridata quick start guide

Raymarine

Raymarine ST60 Tridata quick start guide

Elkron TM24-B manual

Elkron

Elkron TM24-B manual

MAX PROP WHISPER 5 BLADES manual

MAX PROP

MAX PROP WHISPER 5 BLADES manual

KVH Industries TracVision R6 DX Replacement instructions

KVH Industries

KVH Industries TracVision R6 DX Replacement instructions

Lowrance LFG-460 Installating and operation manual

Lowrance

Lowrance LFG-460 Installating and operation manual

E2S D1xS2FDC024-A instruction manual

E2S

E2S D1xS2FDC024-A instruction manual

Furuno MD-550 Operator's manual

Furuno

Furuno MD-550 Operator's manual

Kongsberg EM series instruction manual

Kongsberg

Kongsberg EM series instruction manual

CoastKey Master FOB user manual

CoastKey

CoastKey Master FOB user manual

Seastar Solutions HA6523 installation instructions

Seastar Solutions

Seastar Solutions HA6523 installation instructions

Pertronic PS1400 installation instructions

Pertronic

Pertronic PS1400 installation instructions

Scanstrut Scanpod Deck Pod installation instructions

Scanstrut

Scanstrut Scanpod Deck Pod installation instructions

Pfannenberg PD 2100-LED -M installation manual

Pfannenberg

Pfannenberg PD 2100-LED -M installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.