System Sensor B200S User guide

SS-450-000 1 I56-3387-005R
B200S
Intelligent Sounder Base
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
BEFORE INSTALLING
Please read the System Sensor Smoke Detector Application Guide, which pro-
vides detailed information on sensor spacing, placement, zoning, wiring, and
special applications. Copies of this manual are available from System Sensor.
NFPA 72 and NEMA guidelines should be observed.
NOTE: 200 Series sounder bases are not compatible with remote test capable
200 series detectors.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector should be cleaned at
least once a year.
GENERAL DESCRIPTION
The B200S sounder base is used with System Sensor 200-Series sensor heads or
equivalent. For a list of compatible sensors, refer to the System Sensor website
at www.systemsensor.com. Refer to the appropriate manual for more informa-
tion on sensors.
The B200S sounder base was designed specifically to meet the needs of dwell-
ing unit applications. It offers maximum flexibility in configuration and opera-
tion to meet or exceed the requirements of UL268 and UL464.
The sounder base is capable of producing a variety of tone patterns, including
the distinctive three-pulse temporal pattern (ANSI Temporal 3) fire alarm sig-
nal now required by NFPA 72 for commercial and residential applications.
The B200S can be commanded by the Fire Alarm Control Panel to adopt the
address of the attached sensor head, but as a unique device type on the loop.
By using the address, the fire alarm control panel can command an individual
sounder base to activate, or a group of sounders in a suite or other multi-room
configuration. The command set from the panel can be tailored to the specific
event, allowing selection of volume, tone, and group. The device offers two
volume levels: 75 dBA and 85 dBA. The available tones are Continuous, ANSI
Temporal 3, ANSI Temporal 4, and March Time. In addition, some fire alarm
panels will offer the ability to command a custom tone pattern. Refer to the
appropriate fire alarm control panel manual for more information.
In addition, the B200S is equipped with the circuitry to recognize the System
Sensor synchronization protocol, enabling the sounder base to be used as a
component of the general evacuation signal – producing an NFPA 72 compli-
ant Temporal 3 pattern in synchronization with other System Sensor notifica-
tion devices. This requires connection to a power supply capable of generating
the System Sensor synchronization pulses, a FACP NAC output configured to
System Sensor synchronization protocol, or a separate synchronization mod-
ule. In this scenario, the sounder bases will have the ability to synchronize
with other System Sensor horns, horn/strobes, and chimes using the same
power source.
Specifications
Base Diameter: 6.875” (17.46 cm)
Base Height (less sensor): 2.0” (5.08 cm)
Weight: 0.50 lb. (227 gm)
Operating Temperature Range: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com
Operating Humidity Range: 10% to 93% relative humidity (non-condensing)
External Supply Electrical Ratings
External Supply Voltage: 16 to 33 VDC (VFWR)
Standby Current: 500 μA maximum
Alarm Current: 35 mA maximum (at high volume setting)
15 mA maximum (at low volume setting)
SLC Electrical Ratings
SLC Operating Voltage: 15 to 32 VDC
SLC Standby Current: 300 μA maximum
Sound Output
High Volume: Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)
Low Volume: Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)
The sounder base is intended for use with intelligent systems. The sounder
base requires an external 24 VDC power supply. The connections for the
external power supply and the communication loop are isolated to prevent
electrical interaction between them. Refer to the panel manual for maximum
allowable number of units per loop.
NOTE: For NFPA72 Installations, the Temporal 3 tone at high volume should
be used for public mode evacuation. The use of other tone styles and low
volume level will be at the discretion of the local Authority Having Jurisdic-
tion (AHJ).
NOTE: When not used as a supplementary evacuation system, the external 24
VDC supply shall be treated as a component of the main power supply system
and shall fall under the requirements of the main power supply system per
NFPA 72.
WIRING GUIDELINES
All wiring must be installed in compliance with the National Electrical Code
and the local codes having jurisdiction and must not be of such length or wire
size which would cause the base to operate outside of its published specifica-
tions. The conductors used to connect smoke sensors to control panels and
accessory devices should be color coded to reduce the likelihood of wiring
errors. Improper connections can prevent a system from responding properly
in the event of a fire.
Wire sizes up to 12 AWG (2.5 mm2) may be used with the base. The sounder
base will be shipped with the screw terminals set for 14 AWG wiring. If 12
AWG wire is to be used, back out the screws to allow the wire to fit beneath
the clamping plates.For best system performance, the power (+ and -) wires
and the communication circuit wires should be twisted pair or shielded cable
installed in a separate grounded conduit to protect the communication loop
from electrical interference.
I56-3387-005R
This model is compatible with Sytem Sensor Models MDL, MDL3R, MDLW, MDL3W and SYNC-1

SS-450-000 2 I56-3387-005R
Make wire connections by stripping about 3/8” of insulation from the end of
the wire. Then, slide the bare end of the wire under the appropriate clamping
plate (See Figure 1), and tighten the clamping plate screw. Do NOT loop the
wire under the clamping plate (See Figure 2) The wiring diagram for a typical
2-wire intelligent system is shown in Figure 4.
For system monitoring - for terminals 2, 3, 4, and 5, do not use looped wire
under terminals. Break wire run as shown in Figure 2 to provide monitoring
of connections.
B200S TERMINALS
No. Function
1. Not Used
2. Positive (+) Comm. Line In and Out
3. Negative (-) Comm. Line In and Out
4. External Supply Positive (+)
5. External Supply Negative (-)
6. Remote Annunciator
MOUNTING
Mount the B200S mounting plate directly to an electrical box. The plate will
mount directly to 4˝ square (with and without plaster ring), 4˝ octagon, 3 1/2˝
octagon, single gang or double gang junction boxes.
1. Connect field wiring to terminals, as shown in Figure 1 and 2.
2. Attach the mounting plate to the junction box as shown in Figure 3.
3. To mount the sounder base, hook the tab on the sounder base to the groove
on the mounting plate.
4. Then, swing the sounder base into position to engage the pins on the
product with the terminals on the mounting plate.
5. Secure the sounder base by tightening the mounting screws.
6. Install a compatible smoke sensor as described in the installation manual
for the sensor.
TAMPER RESISTANT FEATURE
NOTE: Do not use the tamper-resist feature if the removal tool is to be used.
This detector base includes a tamper-resist feature that prevents its removal
from the base without the use of a tool. To activate this feature, break the tab
from the detector base as shown in Figure 6A. Then, install the detector. To
remove the detector from the base once the tamper-resist feature has been
activated, insert a small-bladed screwdriver into the slot from the top and
press down on the lever (see Figure 6B). This allows the detector to be rotated
counterclockwise for removal. The tamper-resist feature can be defeated by
breaking and removing the plastic lever from the base. However, this prevents
the feature from being used again.
TESTING AND MAINTENANCE
Sensors and bases must be tested after installation and as an integral part of a
periodic maintenance program. Test the B200S as follows:
NOTE: Before testing, notify the proper authorities that the smoke sensor
system is undergoing maintenance and, therefore, will be temporarily out of
service. Disable the system undergoing maintenance to prevent unwanted
alarms.
1. Via the fire alarm control panel, command the individual B200S to activate
using the associated sensor address. That sounder base should sound in
approximately five seconds.
2. Via the fire alarm control panel, command all B200S sounder bases to acti-
vate using group communication to all associated addresses. All devices on
the loop should sound, and if a temporal tone is commanded, the tones can
be synchronized to each other.
NOTE: Synchronization requires a power supply capable of producing the Sys-
tem Sensor synchronization pulses.
When performing maintenance on connected smoke sensors, carefully note
the location and address of each removed sensor. When re-installed, the
B200S will confirm that address of the sensor matches the address stored in
the sounder base memory. If there is a mismatch, this will be communicated
to the fire alarm control panel and the sounder base can be commanded to
chirp at regular intervals until the correct head is installed.
If a replacement head is installed or address changes are required, the mis-
match may be resolved at the panel by commanding the B200S sounder base
to re-enter its address learning mode and adopting the address of the new
sensor.
FIGURE 3: MOUNTING
FIGURE 2: C0471-07
C0473-00
C0891-07
FIGURE 1:
1
2
34
5
6
CAUTION

FIGURE 4: WIRING DIAGRAM
FIGURE 5: SYNCHRONIZATION DIAGRAM (FOR MDL SERIES SYNC MODULES ONLY)
SS-450-000 3 I56-3387-005R
(+) SLC
(–) SLC
(–) POWER
(+) POWER
U.L. LISTED COMPATIBLE
CONTROL PANEL
UL LISTED 24V
POWER SUPPLY
WITH SYSTEM SENSOR
SYCHRONIZATION OUTPUT
OPTIONAL SOUNDER INTERCONNECT
CLASS A OPTIONAL WIRING
FIRST
SOUNDER
BASE
SECOND
SOUNDER
BASE
NTH
SOUNDER
BASE
NOT
USED
SLC +
EXT –
EXT +
RA
SLC –
NOT
USED
SLC +
EXT –
EXT +
RA
SLC –
NOT
USED
SLC +
EXT –
EXT +
RA
SLC –
(+) (+) (+)
(–) (–) (–)
E
O
L
THESE DEVICES COULD ALSO BE POWERED BY A FACP NAC OUTPUT
CONFIGURED TO SYSTEM SENSOR SYNCHRONIZATION PROTOCOL OR
A SEPERATE SYNCHRONIZATION MODULE MAY BE USED TO PROVIDE
THE SYNCHRONIZATION PULSES
/
/
SEE POWER
SUPPLY MANUAL
FOR EOL RESISTOR
VALUE. EOL RESIST
OR
MAY NO
T BE NEEDED
FOR CLASS A WIRING
.
E
O
L
/
/
HORN HORNHORN/STROBE
C0474-07
C1090-00
NOTE: The wiring diagram below represents the most common wiring configurations. Please consult your FACP manufacturer for panel-specific wiring configu-
rations and special cases.
Additional Audible Visible devices may be connected to the same power supply or the the NAC output of the Fire Alarm Control Panel (FACP) to provide a syn-
chronized communication of the alarm signal.
NOTE: Wiring shown for System Sensor MDL Series Sync Module. For additional wiring configurations, see your sync module manual.
FACP #1
+
–
+
–
+
–
+
–
+
–
+
–
+
–
EOL
(1)
}
}
}
}
HORN
CONTROL
ZONE 1
IN
ZONE 2
IN
SLAVE
IN
+
–
+
–
+
–
+
–
}
}
}
}
ZONE 1
OUT
ZONE 2
OUT
NAC
SLAVE IN
SLAVE
OUT
TEMP JUMP OFF
NAC 1
}
B+
B–
NAC 2
}
B+
B–
NAC 3
}
B+
B–
TO NEXT DEVICE
OR EOL (1)
TO NEXT DEVICE
OR EOL (1)
2 STYLE Y ZONES
(CLASS B)
MASTER
SOUNDER
BASE
SOUNDER
BASE
OPTIONAL

SS-450-000 4 I56-3387-005R
©2012 System Sensor
System Sensor warrants its enclosed smoke detector base to be free from defects in mate-
rials and workmanship under normal use and service for a period of three years from date
of manufacture. System Sensor makes no other express warranty for this smoke detector
base. No agent, representative, dealer, or employee of the Company has the authority to
increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of the smoke
detector base which is found to be defective in materials or workmanship under normal
use and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System Sensor, Returns
THREE-YEAR LIMITED WARRANTY
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a
note describing the malfunction and suspected cause of failure. The Company shall not
be obligated to repair or replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date of manufacture.
In no case shall the Company be liable for any consequential or incidental damages for
breach of this or any other Warranty, expressed or implied whatsoever, even if the loss
or damage is caused by the Company’s negligence or fault. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation
or exclusion may not apply to you. This Warranty gives you specific legal rights, and you
may also have other rights which vary from state to state.
Please refer to insert for the Limitations of Fire Alarm Systems
PLASTIC LEVER
BREAK TAB AT
DOTTED LINE BY
TWISTING TOWARD
CENTER OF BASE.
USE SMALL-BLADED
SCREWDRIVER TO
PUSH PLASTIC LEVER
IN DIRECTION OF
ARROW.
SLOT
C0144-00
C1082-00
FIGURE 6A:
FIGURE 6B:
Table of contents
Other System Sensor Marine Equipment manuals

System Sensor
System Sensor B501BH-2 User manual

System Sensor
System Sensor B501BHT-2 User manual

System Sensor
System Sensor B200S User manual

System Sensor
System Sensor LASS-WSS-NC User manual

System Sensor
System Sensor EBS User manual

System Sensor
System Sensor B200S-LF-WH User manual

System Sensor
System Sensor ExitPoint PF24V User manual

System Sensor
System Sensor B401BH-2 User manual

System Sensor
System Sensor B501BHT-2 User manual

System Sensor
System Sensor L Series Technical specifications