
SysTEMM
SENSOR
INSTALLATIoN
AND
MAINTENANCE
INSTRUCTIONS
rech
Intral
Deeiogmrnt
Zan
WFD
Vane-type
Waterflow
Detectors
Prinee
f Sh
aam.
71
0075,
Chi
Teiephone
(29
347800
Fas
(037)
382959
SPECIFICATnONS
Contact Ratings:
higgering Threshold Bandwidth
(Flow
Rate):
Static
Pressure
Rating
Dimensions, Installed:
l0
A
@
125/250
VAC
N
25
A@
24
VDC ---
4 to
10
gpin
See
models listed below
3.5
in
Hx
30
in
W x6.7 in D
Operating
Temperature
Range:
Compatible
Pipe:
Shipping
Weight:
Enclosure Rating:
U.
S.
Patent
Numbers
32°F
to
120°F (0°C
to
49°C)
Steel
water
pipe,
schedule
10
through
40
4 to 7 Ib
(according
to
size)
NEMA Type 4,
as
tested
by
Underwriters
Laboratories,
Inc. (1PS6)
5,213,
3,205
IMPORTANT
INSTALLATmON
GUIDELUNES
Please Read Carefully
And
Save
Before
instaling any waterflow alarm device,
be
thoroughly
farmiliar
with:
This
instructionmanual
contains
important
information
about
the
installation
NFPA
72:
National
Fire
Alarm
Code
and
operation
of
waterlow
detectors.
Purchasers
who install waterflow
detec
tors
for
use by others must leave this manual or a copy of
it
with the user.
NFPA
13:
Installation
of
Sprinkler Systems, Sect.
3.17
NFPA
25:
Inspection.
Testing
and
Maintenance
of
Sprinkler
Systesms,
Sect
5332
Read all instructions carefully before beginning. Follow only those instnuc-
tions that apply to the model you are installing.
Other
appiicable
NFPA
standards,
local
codes,
and
the
requiremenits
of
the
authority having jurisdiction
ACAUTION
NOTE:
Installation
methods
other
than
those listed in this instaliation
manual
Use vane-type
waterlow
detectors in wel-pipe systems only.
Do
NOT
use
Imay
preven!
tihe
device
irom
reporiing
the
Llow
oí
water
in
the
event
the
asso-
them in dry pipe, deluge.
or
preaction systems. The
sudden
inrush
of
water in ciated sprinkier system
is
activated by a ire.
XTan
Sysem Sensor is not responsible
such systems may break the vane or damage the mechanism. for
devices
that
have
been
improperiy
installed, tested,
or
maintained
Do
not use in potentially explosive atmospheres.
Do
not
allow
unused wires
lo
remain
exposed.
1.
Mount the detector where there
is
adequate clearance tor installation and
removaB
and
a clear view
of
it
for inspections. See Figure I for
maunting
dimensions.
2.Locate
the
detector 6
to
7
feet
above
the
floor
to
protect
from
acca
dental damage.
PRINCIPLES OF OPERATION
Vane-type waterflow detectors imount to water-filled pipes in sprinkler systems.
Waterflow in the pipe deflects a vane, which produces a switched
outpul
3.
On
horizontal runs, position the detector
on
the top or side
of
the
pipe.
usually
after
a specilied delay.
All
waterflow detectors have a
pneumatically
controlled mechanical delay mechanism. Delays do
NOT
accuinulate; they
re
set
if the
flow
of water stops before the entire delay has elapsed.
All
switches
actuate
when
the water flow rate is
10
gallons per minute or greater, but will
not actuate
if
the
low
rate is less than 4 gallons per minute. This System
Sen-
sor
installation manual
covers
the
following
watertlow detectors
for
sprinkler
ire
alarm
applications.
Do
not
mount
it
upside
down
because
condensation
may
collect in the
housing
and
impair
thse
operaüon
of
he
detector. For vertical flow appli-
Ccations,
mount
the
detector on
pipe
through which water fiows upward.
Otherwise, the unit
mnay
not operaie properiy.
4.
Mount
the
detector
at
least
6
inches
fron
a
f+itüng
that
changes
the
direc-
tion
of
water tlow
and
no less than 24 inches irom a valve
or
drain.
5.
Be
sure
the
direction-of-low
aToW
matches
the
directOn
of
llow in the pipe.
Pipe
Size
Pipe Max.
Pressure
MOUNTING
INSTRUCTiONS
Model
(inches)
Schedule
Rating
(psig)
1.
Drain
the
pipe.
WFD20
10
thru
40
450
Cut a hole
at
the desired location. Center the hole
in
tbe pipe, às
shown
in
Figure
2,
and
be
sure the hole
is
perpendicular
to
the
center
of
the
pipe. Before drilling. use a punch or scribe
to
mark the
dill
site
to
pre
vent
the
bit
trom
slipping.
If
the
hole
is
off
center,
the
vane
will
bind
gainst
the inside wall of the pipe.
Use
a
dril
or hole saw
to
cut a hole of
the
proper
diameter.
See Table I tor hole size.
WFD25 2.5 10 thru
40
450
WFD30-2
10
thru
40
450
WFD35
3.5
10 thru
400
450
WFD40
10
thru
40
450
WFD50
10 thru
40
450
ACAUTION
When
drilling
the
hole
with
a
hole
saw,
make
certain
that
the
center
ot
the
cut
does nol
remain
in
the
pipe.
WFD60 10 thru 40
450
WFD80
10
thru
40
450
Kemove
burrs and sharp edges
from
the hole. Clean and remove
all
scale
and
toreign
matter
trom
the
inside
ot
the
pipe
lor
one
diameter
on
each
Side
of
the
hole to
ensure
free
movement
of the
vane.
Clean
the
outside
of
the
pipe
to
remove
dirt,
metal
chips,
and
cutting
lubricant.
Maximum Ptressure
Rating
400
psig
as
approved
by
Factory
Mutual
Research.
ACAUTION
Do
NOT
use any
of
the
WFD
models on copper pipe. The clamping 1orces . Seat the gasket against the saddle and mount the delector directly
to
the
the
mounting
bolts may
collapse
the
pipe
sufficiently
to
prevent
the
detector
from
functioning properly.
pipe.
Carefully
roll
the
vane
opposite
the
direction
of
tlow
and
insert
through the hole. Seat the saddle firmly against the pipe
so
that the local-
ng
boss
goes
into
the
hole.
Do
NOT
install
steel
or
iron
pipe
sections
in
copper
piping
for
mounting
waterflow detector. Incompatibility
between
the
dissimilar metals causes b
ustnal
Development
Zone
Province
o1
Shaanxi,
710075,
China
Telephone: (029) 8S387800 Fax: (029) 88332959
metallic corrosion.
D770-01-00C
I56-0459-017C