manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tecnocontrol
  6. •
  7. Gas Detector
  8. •
  9. Tecnocontrol Beta SE330K Series User manual

Tecnocontrol Beta SE330K Series User manual

SE330KM Methane Neg.
SE330KG L.P.G.Neg.
SE333KM Methane Pos.
SE333KG L.P.G.Pos.
INSTALLATION INSTRUCTIONS
Use a screwdriver to undo the screw on the right-hand side of the
instrument and lift the cover (Fig 1).
Position the base correctly and fasten it on the built-in 3-module box or on
the wall, using the screws and dowels provided.
GENERAL DESCRIPTION
The Beta SE330K and SE333K gas detectors are methane or LPG control
units with LEDs and a buzzer that warn of the presence of gas in the
room. They are designed to be operated either directly or in remote mode.
The Beta detectors are calibrated to detect gas at 10% of the LEL (Lower
Explosive Limit); this threshold can vary according to environmental
conditions but will not exceed 15% of the LEL within the first five years of
use. The Sensor module must be replaced at the end of these five years or
if the “FAULT” LED turns on.
There is a label on the cover that should state the expiry date (5 years
after the date of installation); this label must be compiled by the person
who installs the detector, at the time of installation.
LEDS AND BUZZER
There are three LEDs on the front of each detector:
- GREEN LED (ON): indicates the instrument is powered.
- YELLOW LED (FAULT) + BUZZER: Indicates the sensor is broken.
- YELLOW LED (FAULT) blinking only: indicates the CO sensor
needs to be replaced.
- RED LED (ALARM): indicates the concentration of gas in the
air is above the alarm threshold.
If the gas sensor is defective, the buzzer will make a noise at a rate of
every two seconds, turning on the yellow LED and relay output.
In the event of an alarm, the red LED turns on and the buzzer and relay are
activated twenty seconds later.
1-4m
30cm
max
L.P.G. gas
detector.
30cm
max
1-4m
Methane gas
detector
ELECTRICAL CONNECTION: POWER SUPPLY
Attention: undertrack cables are required to connect the instrument to the
mains.
The gas detector must be powered at 230 Vac using terminals 1 and 2, or
at 12Vdc using terminals 3 (+) and 4 (-). (Fig. 2).
A circuit breaker must be fitted that is able to disconnect the detector from
the power supply, with a contact distance of at least 3 mm, in accordance
with the European standard IEC EN 60335-1.
Fig.1
INSTALLING THE INSTRUMENT
The instrument MUST BE INSTALLED:
- In the case of Beta SE330KM and Beta SE333KM methane gas detectors,
series Beta model SE330K
series Beta model SE333K
GAS LEAK DETECTOR FOR DOMESTIC USE WITH
INTERCHANGEABLE SENSOR
GENERAL TERMS OF THE GUARANTEE
THIS CERTIFICATE IS THE ONLYDOCUMENT THAT ENTITLES
YOU TO REPAIR OF THE PRODUCT UNDER THE TERMS OF
THE GUARANTEE.
- The product is GUARANTEED for a period of 24 months from the date
of purchase.
- The GUARANTEE does not cover damage caused by tampering,
incorrect or improper use and installation.
- The GUARANTEE is valid only if it is duly compiled.
- In the event of defects covered by the GUARANTEE, the manufacturer
will repair or substitute the product free of charge.
SERVICINGAFTERTHE GUARANTEE PERIOD:
Any repairs after the period of the GUARANTEE will be charged on the
basis of the parts substituted and the cost of labour.
Model Detected gas Logic Power supply
230Vac 50Hz /
12Vdc
12Vdc
230Vac + -
1 2 4
3
Fig.2
at a maximum distance of 30 cm from the ceiling; in the case of Beta
SE330KG and Beta SE333KG LPG gas detectors, at a maximum height of
30 cm above the floor.
- At a distance of between 1 and 4 metres from the gas appliance (cooker,
boiler, etc.). If possible, in every room where there is a gas appliance and,
in the case of multi-storey buildings, at least one on each floor.
CHARACTERISTICS OF THE OUTPUT SIGNAL
The Beta SE330K and SE333K control units have an output relay with
voltage-free contacts; the rating of the contacts is 8A 250Vac/30Vdc.
Sensor module
ZSDM1 METHANE SE330KM/SE333KM
ZSDG1
L.P.G.SE330KG/SE333KG
Detected gas
Code Beta
LIGHTING DELAYS
After the detector is turned on, the catalytic sensor in the detector takes
about a minute to warm up, during which time the green LED blinks to
indicate the alarm is disabled.
INSTALLATION
Attention: the instrument must be installed and put out of service by a
specialized technician.
Your gas supply and any shut-off devices must be installed in conformity
with the domestic laws in force.
The instrument MUST NOT BE INSTALLED:
- Directly above the sink or gas appliance.
- In small rooms where alcohol, ammonia, spray cylinders or other
substances based on volatile solvents might be used.
- In closed environments or corners where there is no free circulation of
air.
- Near walls or other obstacles that could prevent the flow of gas from the
appliance to the detector, or extractors and fans that could divert the flow
of air.
- In environments where the temperature could exceed 40°C or fall below
– 5°C.
CONNECTION OF THE ELECTRIC VALVE AND
REMOTE SENSORS
The Beta SE330K and SE333K control units each have two terminals (5-
6) active when closed, for connecting the following remote detectors (Fig. 3):
for METHANE gas: model SE195KM or model SE396KM.
for LPG gas: model SE195KG or model SE306KG.
If the remote sensors are not connected to terminals 5 and 6, these must
not be modified, and therefore kept disconnected at all times.
Do not forget that the electric valve must be installed on the gas pipe
outside the room to be controlled as it cannot protect against leaks upstream.
The Beta SE330/SE333 + Beta SE330/SE333 configuration is IMQ
certified.
The other configurations, Beta SE330/SE333 + SE195 K and Beta SE330/
SE333 + SE396K are not IMQ certified.
ATTENTION: If there is a temporary loss of power during operation with
positive logic, the N.C. valve closes automatically and will need to be reset
manually when power is restored.
NEGATIVE LOGIC (SE330K): in this case, the coil of the relay is
kept deactivated (Fig. 6).
It is perfect for N.O. (normally open) electric valves (Fig. 7) or N.C.
(normally closed) electric valves (Fig. 8).
In the event of an alarm, contacts 8 and 9 remain closed until the
alarm stops.
J2 JUMPER IN
“NEGATIVE LOGIC”
POSITION
Fig.5
7 8 9
NC C NA
J2 JUMPER IN
“POSITIVE LOGIC”
POSITION
NA
C
NC
R
R
+
-
1
2
3
5
4
6
7
8
9
SE333K
230Vac/50Hz
EV
Normally close
SE330K
N
A
C
N
C
R
R
+
-
1
2
3
5
4
6
7
8
9
230Vac/50Hz
EV
Normally open
Fig.6
Fig.7
Fig.8
N
A
C
N
C
R
R
+
-
1
2
3
5
4
6
7
8
9
230Vac/50Hz
EV
Normally close
SE330K
EXAMPLE OFAPPLICATION WITH N.C. ELECTRIC VALVE SE333
Fig.4
7 8 9
NA C NC
ELECTRICAL CONNECTION WITH SEVERAL
DETECTORS:
Connection of two detectors with a single electric valve is shown in the
diagrams below. It is possible to connect more than two detectors, repeating
the same connections.
NA
C
NC
R
R
+
-
1
2
3
5
4 6
7
8
9
NA
C
NC
R
R
+
-
1
2
3
54
6
7
8
9
SE330K SE330K
230Vac 50Hz 230Vac 50HzNO GAS GAS EV
Connection with Normally Open manual reset electric valve (with relay
normally deactivated) and a second SE330K detector.
SE330K
SE330K SE330K
12Vdc 12Vdc
NO GAS GAS EV 12Vdc
SE330K SE396K
230Vac - 50Hz 230Vac - 50Hz
Fig. 3 Example of connection of a remote sensor.
The Beta SE396K detector is not IMQ certified but complies fully with
standard IEC UNI EN 50194.
POSITIVE LOGIC – NEGATIVE LOGIC
The Beta SE330K and SE333K gas detector can control an electric valve
using two different logics:
1 – POSITIVE LOGIC (SE333K)
2 – NEGATIVE LOGIC (SE330K)
The J2 JUMPER allows you to select the one required.
N.B. The J2 JUMPER is set by default to NEGATIVE LOGIC (SE330K).
N.O. manual
reset valve
POSITIVE LOGIC (SE333K): in this case, the coil of the relay is
always live (Fig. 4) to ensure the inherent safety of the relay.
It is perfect for N.C. (normally closed) electric valves (Fig. 5).
In the event of an alarm, contacts 7 and 8 remain closed until the
alarm stops.
GUARANTEE CERTIFICATE
TO COMPILE AND SEND IN CASE OF DAMAGE
DEVICE: SE330KM SE330KG SE333KM SE333KG
Serial number (s.n.)_________________________________________
DEALER
Stamp: Date of purchase:
_____/_____/_____
USER
Surname and name _________________________________________
Address _____________________________________ n°__________
Postcode ________________ Town/city ________________________
Telephone_________________________________________________
Connection with 12 Vdc Normally Open manual reset electric valve (with
relay normally deactivated) and a second SE330K detector.
ROUTINE TESTING
You are advised to ask the installer to give the detector a general test at
least once a year.
IMPORTANT: Do not use pure gas, such as that in a lighter,
directly on the sensor since the sensor could be irremediably
damaged.
OPERATION TEST
In the case of the Beta SE330K and SE333K models, before carrying out
the operation test, open the cover under the three LED lights (Fig. 9) with
a flat-headed screwdriver.
Fig.9
When this is done, it is possible to test operation of the instrument by
pressing and holding the little TEST button on the Sensor module (Fig.
10) of the Beta SE330K and SE333K control unit for at least 2 seconds,
or the button on the card of the Beta SE396K remote detector, if connected,
for at least 30 seconds.
All the LEDs turn on and the buzzer and relay output are activated for 5
seconds.
Fig.10
You will then need to re-engage the electric valve connected to the output
of the gas detector (if present).
SENSOR MODULE
Detected gas
ZSDM1 Methane SE330/SE333KM
ZSDG1 L.P.G. SE330/SE333KG
Code Model
N.B. Make sure the code of the new Sensor module
matches the code on the Sensor module to be replaced.
1_Turn off the detector, unplug it
from the mains and use a
screwdriver to lever off the little
cover under the three LEDs (Fig.
11).
2_Undo the two screw
fasteners on the Sensor
module to be replaced (Fig. 12).
Fig.12
Fig.11
N
A
C
N
C
R
R
+
-
1
2
3
5
4
6
7
8
9
N
A
C
N
C
R
R
+
-
1
2
3
5
4
6
7
8
9
230Vac 50Hz 230Vac 50HzNCGAS GAS EV
SE333K SE333K
SE333K
12Vdc 12Vdc
NC GAS GAS EV 12Vdc N.C.
SE333K SE333K
Connection with Normally Closed manual reset electric valve (with relay
normally activated) and a second SE333K detector.
Connection with 12 Vdc Normally Closed manual reset electric valve (with
relay normally activated) and a second SE333K detector.
LOWER EXPLOSIVE LEVEL (L.E.L.)
You need to use a calibration cylinder with sample gas to test correct
operation of the sensor.
If you wish to recreate the dangerous conditions the gas sensor is meant
to protect against, do not use the gas of normal domestic appliances. Our
detectors are calibrated at 10% of the LEL (lower explosive level).
Here is a simple explanation: as an example, a kitchen measures 3 metres
in width, 4 metres in length and 3 metres in height.
- The volume of the kitchen is equivalent to 4 x 3 x 3, and therefore 36 m³
or 36,000 litres.
There is a dangerous mix when methane accounts for 5% of the volume of
the kitchen.
- This 5% is called the LEL (lower explosive limit).
- In this case, 5% of 36,000 litres is 1800 litres (LEL).
- Our detectors, being IMQ certified, are activated at 10% of the LEL and
therefore at 10% of 1800 litres which, in this case, is 180 litres, AT ONE
TENTH OF THE LOWER EXPLOSIVE LIMIT (LEL).
Taking into account the fact that a domestic hob has a nozzle a few tenths
of a millimetre in length and that the pressure is just a few millibars, it would
take several hours to produce 180 litres of methane (and trigger the sensor).
Even if the nozzle is larger, the very particular and strong odour of methane
would make it impossible for anyone in the room not to notice and realise
the serious danger, even when the amount of methane in the room is too
little to cause an explosion.
REPLACING THE SENSOR
N.B. The Sensor module must be replaced by a specialized
technician.
The sensor module should be replaced no more than TWICE, for a
total product life-span of 15 years.
Replace the Sensor module if the “FAULT” LED starts blinking, or by the
expiry date on the label on the cover.
Replace the label on the cover stating the expiry date (5 years after the
date of installing the new sensor module); this label must be compiled by
the person who installs the detector at the time of replacing the sensor
module.
TECHNICAL CHARACTERISTICS
- Power supply 230Vac, 50 Hz / 12 Vcc 2.5W
- Power consumption 20mA max
- Operation temperature -10°C…. +40°C
- Relative humidity 30%…. 90% RH
- Alarm threshold at 10% of the LEL (lower explosive limit) of the gas.
- Warming up period after the instrument is switched on:
about 1 minute
- Acoustic level of buzzer: 85 dB (A) at 1 metre
- Electronic self-diagnosis with signal to indicate malfunction.
- Rated to IP42
- Remote unit input
- Conforms to standard IEC UNI EN 50194
ATTENTION! In the event of an alarm:
1) Put out all naked flames.
2) Close the valve on the gas meter or LPG cylinder.
3) Do not turn any of the lights on or off; do not use any electrical
appliances or devices.
4) Open the doors and windows to increase ventilation in the
room.
If the alarm stops, find the cause and take appropriate action.
If the alarm continues and you cannot find and eliminate the
cause of the leak, vacate the premises and, when you are
outside, contact the gas emergency service.
WARNING
Remove any dust on the surface of the instrument with a cloth. Do not
attempt to open or dismount the gas detector since this could result in
electric shock and damage to the product. Bear in mind that the sensor is
also sensitive to commonly used products such as sprays, detergents,
alcohol, glue and paint. These products can contain substances which, in
high quantities, could trigger the sensor and cause false alarms.
It is advisable to ventilate the room when using these products.
Do not forget that the detector cannot detect leaks outside the room in
which it is installed or leaks in the walls or under the floor. The gas (methane
or LPG) contains an additive that gives it an unpleasant odour, to make it
easy to detect by smell. If a ring on a gas hob is left on without being lit,
even for several minutes, the amount of gas will not be sufficient to trigger
the alarm of the detector (even though it can be clearly smelt). In fact, the
amount of gas in the room could be under the alarm threshold.
The detector does not work when there is a power cut.
dis.0134152a cod.2.710.2335 Made in Italy
Tecnocontrol Srl via Miglioli, n°47 20090 Segrate (Milano) Italy
Tel. +39 02 26922890 Fax +39 02 2133734
www.tecnocontrol.it E-mail: [email protected]
After the instrument is turned on, the catalytic sensor in the detector takes
about a minute to ‘warm up’, during which time the green LED blinks to
indicate the sensor is warming up and the detector is not operational.
3_Remove the Sensor
module to be replaced (Fig.
13).
4_Check the new Sensor
module is compatible with
the one to be replaced (if
the sensor module is not
compatible, the YELLOW
LED and BUZZER turn on)
and carefully insert the 4
connectors in the correct
place.
5_Fasten the Sensor module with the
two screws and close the cover, first
inserting the two tabs at the bottom
(Fig. 15). The instrument can now be
turned on.
Fig.14
Fig.13
Fig.15
TO BE COMPILED BY THE INSTALLER:
Date of installation ________________________________________
Date of replacement ______________________________________
Attention: the detector must be replaced 15 years after the
date of installation on this voucher
Site of installation _________________________________________
Serial number (s.n.) _______________________________________
(Written on the inside of the plastic container).
Date of initial replacement of sensor module:____________________
Date of second replacement of sensor module:__________________
Attention: the entire detector must be replaced five years
after second replacement of the sensor module.
Stamp
Signed ________________
La Tecnocontrol s.r.l. reserves the right to make any aesthetic or functional modification to the without prior notice at any time.

This manual suits for next models

5

Other Tecnocontrol Gas Detector manuals

Tecnocontrol SE182PM User manual

Tecnocontrol

Tecnocontrol SE182PM User manual

Tecnocontrol SE237E Series User manual

Tecnocontrol

Tecnocontrol SE237E Series User manual

Tecnocontrol TS293P Series User manual

Tecnocontrol

Tecnocontrol TS293P Series User manual

Tecnocontrol SE193K Series User manual

Tecnocontrol

Tecnocontrol SE193K Series User manual

Tecnocontrol TS282PM User manual

Tecnocontrol

Tecnocontrol TS282PM User manual

Tecnocontrol TS293IM User manual

Tecnocontrol

Tecnocontrol TS293IM User manual

Tecnocontrol SE192K Series User manual

Tecnocontrol

Tecnocontrol SE192K Series User manual

Tecnocontrol SE237P Series User manual

Tecnocontrol

Tecnocontrol SE237P Series User manual

Tecnocontrol SE296KM User manual

Tecnocontrol

Tecnocontrol SE296KM User manual

Tecnocontrol SE138K User manual

Tecnocontrol

Tecnocontrol SE138K User manual

Tecnocontrol TS282E Series User manual

Tecnocontrol

Tecnocontrol TS282E Series User manual

Tecnocontrol TS293PM User manual

Tecnocontrol

Tecnocontrol TS293PM User manual

Tecnocontrol SE126K User manual

Tecnocontrol

Tecnocontrol SE126K User manual

Tecnocontrol SE137EO User manual

Tecnocontrol

Tecnocontrol SE137EO User manual

Tecnocontrol SE148K User manual

Tecnocontrol

Tecnocontrol SE148K User manual

Tecnocontrol TS220E Series User manual

Tecnocontrol

Tecnocontrol TS220E Series User manual

Tecnocontrol TS292KM User manual

Tecnocontrol

Tecnocontrol TS292KM User manual

Tecnocontrol TS220E User manual

Tecnocontrol

Tecnocontrol TS220E User manual

Tecnocontrol TS293PM User manual

Tecnocontrol

Tecnocontrol TS293PM User manual

Tecnocontrol TS292P User manual

Tecnocontrol

Tecnocontrol TS292P User manual

Tecnocontrol SE221KM User manual

Tecnocontrol

Tecnocontrol SE221KM User manual

Tecnocontrol SE296KM User manual

Tecnocontrol

Tecnocontrol SE296KM User manual

Tecnocontrol SE192KM User manual

Tecnocontrol

Tecnocontrol SE192KM User manual

Tecnocontrol TS282IF User manual

Tecnocontrol

Tecnocontrol TS282IF User manual

Popular Gas Detector manuals by other brands

WIKA GPD-1000 operating instructions

WIKA

WIKA GPD-1000 operating instructions

BW Technologies GasAlertClip Extreme H2S instruction sheet

BW Technologies

BW Technologies GasAlertClip Extreme H2S instruction sheet

Milesight GS101 user guide

Milesight

Milesight GS101 user guide

Evikon E2632 user manual

Evikon

Evikon E2632 user manual

isweek AS8900 manual

isweek

isweek AS8900 manual

multicomp pro MP780969 user manual

multicomp pro

multicomp pro MP780969 user manual

IMR EX660 user manual

IMR

IMR EX660 user manual

Sensitron SMART S Installation and user manual

Sensitron

Sensitron SMART S Installation and user manual

Eastern Energy JL269 LED manual

Eastern Energy

Eastern Energy JL269 LED manual

MSA MGS-550 operating manual

MSA

MSA MGS-550 operating manual

PEMTECH PT2000/H Series Operator's manual

PEMTECH

PEMTECH PT2000/H Series Operator's manual

Evikon PluraSens E2618-NH3-E user manual

Evikon

Evikon PluraSens E2618-NH3-E user manual

Halma SENSITRON SMART3-R LITE manual

Halma

Halma SENSITRON SMART3-R LITE manual

S&S Northern MERLIN CO DETECTOR X Installation operation & maintenance

S&S Northern

S&S Northern MERLIN CO DETECTOR X Installation operation & maintenance

RKI Instruments GX-3R Pro Operator's manual

RKI Instruments

RKI Instruments GX-3R Pro Operator's manual

Emerson MRLDS-450 quick start guide

Emerson

Emerson MRLDS-450 quick start guide

ABB N9611-21 Instruction and use manual

ABB

ABB N9611-21 Instruction and use manual

Hydro Instruments GA-170 Operation and maintenance manual

Hydro Instruments

Hydro Instruments GA-170 Operation and maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.