TFD-3250
Conventional Optical Smoke + Fixed Heat
Detector (Multisensor)
Installation & Operating Guide
Issue Date: 07/12/2017
Rev:02
Important Warnings
General
✓Before using the device read this manual carefully. Keep it just in case of necessity.
✓Abide all the rules and precautions stated in the manual. Follow all the instructions one by one.
✓Keep the devices away from water and moisture
Conditions
Do not energize the device above or below the given limits of extreme hot or cold conditions,
Temperature: Between -10°C and +70°C
Relative Humidity: %95 RH max
Service
Do not try to fix the device on your own. Removal of cover may end up with electricity shock.
In case of any defect or malfunction, contact with your dealer or with authorized service. All the technical
interventions have to be done by technicians of company.
Malfunctions that require technical service
In case of any malfunction or below conditions contact with your authorized service,
✓When Mains cable or the plug is harmed,
✓Contact of device with a fluid,
✓Exposure of rain and water,
✓Fell down of device or harmed outer cover,
✓Serious performance fall on the device,
✓Depending on the instructions stated in manual, if your device not working properly
Contact with your authorized service in such terms.
Maintenance on your own
Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case of any
defect or malfunction, contact with your dealer or with authorized service. All the technical interventions have
to be done by technicians of company. Device must be cleaned up with a dry fabric. No-chemicals are
allowed for cleaning
Transportation
Device must be carefully transported avoiding all physical bump, stroke and possible fluid entry. Malfunctions
that caused by improper transportation is not under warranty.
Human and Environmental Health
This device contains no chemical or biological elements that could harm human condition.
General Features
✓Advanced smoke detection algorithm that minimizes false alarms
✓The detector is in the A2S class and alarms at 55 ° C in this conditions
✓Rejection of transient signals that can be detected as alarms
✓Adaptive intelligent protection by constantly sampling the environment
✓Dust algorithm and warning to understand that it is getting polluted and unable to detect
✓Easy to clean smoke chamber
✓Ability to connect an remote indicator
✓Two leds used for status indicators
✓15s start time
✓Compatible with TFA-0120 Universal Detector Base
Technical Features
Power Input
18V(min) –30V(max)
Average Current Consumption
30uA (@24V)
Maximum Alarm Current
50mA (@24V) –(470ohm resistance limited)
Maximum External Device Current
10mA (@24V) –(2K2 resistance limited)
Operating Temperature Range
-10C ~ +70C (14F ~ 158F)
Humidity
95% RH (max)
Dimensions (mm)
Ø110, h42
Housing Material
White Color, ABS Plastic
Used Cable Cut
0.4mm ² ~ 1.5mm ²
Weight (incl. Base / excluding base)
183 gr / 125 gr
Startup Time
15 sn
Indicator Leds
Blue Led
Red Led
When the unit is first energized for
15 s, while sampling the
environment
Blinks for 5s period
X
Any error condition
(dust or power failure)
Blinks for 1s period
X
In normal operating condition
Blinks for 20s period
X
In alarm condition
X
It is constantly lit
Terminals
Number 1
Negative (-) power input
Number 2
Negatif(-) input of the remote indicator
Number 3
Positive supply out and Positive (+) input of remote indicator
Number 4
Positive (+) power input
Number 5
Earth connection
Warning: Do not attempt to remove the electronic board from its plastic case. The electronic board is
closed for your safety. Users should avoid from interference.
Mounting and Connection
1. Remove the head of the detector by pulling it upwards (2) by turning it (1) up to the short line in the
direction of the counterclockwise direction as seen from the base.
2. Mount the base using the 2 mounting locations shown.
3. Make the cable connection according to the following diagram. Make a connection with pole 4 + pole and
pole 1 - by taking pole + number 3 from pole 3 of the next detector.
4. Use the 3 (+) and 2 (-) connections for the remote indicator.
5. Replace the detector head. Make sure the line on the head matches the long line on the base
6. Give the detector power from alarm panel. In the absence of an alarm, the LED on the detector indicates
that it is operating with a blue color for approximately 20 seconds. (the first 15 seconds a blue LED lights
up in the detector for 5 seconds).
Test
Smoke Test:
For the smoke test, allow the smoke to enter the smoke detection chamber for at least 1 minute with a
flammable material or a test aerosol. When enough amount of smoke enters the chamber, the LED
illuminates and reports the alarm.
1. Remove the smoke source when the alarm condition is reached.
2. Check that the red LEDs are lit continuously. Reset the detector on the panel.
3. If the detector does not give an alarm within 1 minute, the detector should go to service.
4. The system can be activated after the test has been performed.
Heat Test:
For the detector test it is sufficient to provide air flow at a temperature of about 70 ° C.
1. Open the hot air flow and check the temperature.
2. Hold the hot air into the detector. The detector should give an alarm within 30 seconds.
3. Check that the red LEDs are lit continuously. Reset the detector on the panel.
4. System can be activated after test
1922
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu OSB 1. Cad. İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Ümraniye / İstanbul
17
1922-CPD-0939
EN 54-7:2000; EN 54-7:2000/A1:2002; EN 54-7:2000/A2:2006
Point type smoke detector (Ionization)
EN 54-5:2000; EN 54-5:2000/A1:2002
Point type heat detector
Class A2S
TFD-3250
Technical data: see BİLGİ-TEC-171128-2 held by the manufacturer.
Manufacture
* 2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted
municipal waste in the European Union. For proper recycling, return this product to your local supplier upon
the purchase of equivalent new equipment, or dispose of it at designated collection points. For more
information see: www.recyclethis.info.
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu Organize Sanayi Bölgesi 1. Cadde İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Ümraniye / İstanbul / Türkiye
Telephone: +90 216 455 88 46 Fax: +90 216 455 99 06
Sales: [email protected]
Technical Support: [email protected]

Other Teknim Security Sensor manuals

Teknim TWD-1850 Instruction Manual

Teknim

Teknim TWD-1850 Instruction Manual

Teknim TVSD143 User manual

Teknim

Teknim TVSD143 User manual

Teknim TWD-1850 Instruction Manual

Teknim

Teknim TWD-1850 Instruction Manual

Teknim TWM-1885 Instruction Manual

Teknim

Teknim TWM-1885 Instruction Manual

Teknim TWM-3885 Instruction Manual

Teknim

Teknim TWM-3885 Instruction Manual

Teknim TFD-1271 Instruction Manual

Teknim

Teknim TFD-1271 Instruction Manual

Teknim TFD-3240 Troubleshooting guide

Teknim

Teknim TFD-3240 Troubleshooting guide

Teknim TFD-1260A Instruction Manual

Teknim

Teknim TFD-1260A Instruction Manual

Teknim ATP545 User manual

Teknim

Teknim ATP545 User manual

Teknim TSD-5150 User manual

Teknim

Teknim TSD-5150 User manual

Teknim TFD-1270A Instruction Manual

Teknim

Teknim TFD-1270A Instruction Manual

Teknim TFD-1261 Instruction Manual

Teknim

Teknim TFD-1261 Instruction Manual

Teknim TFD-1260 Instruction Manual

Teknim

Teknim TFD-1260 Instruction Manual

Popular Security Sensor manuals by other brands

Pinlock 70 Maintenance Instruction

Pinlock

Pinlock 70 Maintenance Instruction

IKEA tradfri manual

IKEA

IKEA tradfri manual

Extech Instruments EzFlex EZ40 user guide

Extech Instruments

Extech Instruments EzFlex EZ40 user guide

GE Baker Hughes Reuter-Stokes Flame Tracker... Operation and maintenance manual

GE

GE Baker Hughes Reuter-Stokes Flame Tracker... Operation and maintenance manual

SGB VLX Ex Series Documentation

SGB

SGB VLX Ex Series Documentation

LED Group Robus quick start guide

LED Group

LED Group Robus quick start guide

Duratool D03056 quick start guide

Duratool

Duratool D03056 quick start guide

Atlantic Ultraviolet Zenith operation & maintenance

Atlantic Ultraviolet

Atlantic Ultraviolet Zenith operation & maintenance

Setsquare SET-DOL-RJ installation instructions

Setsquare

Setsquare SET-DOL-RJ installation instructions

National Instruments USB-5683 Specifications

National Instruments

National Instruments USB-5683 Specifications

Aeotec MULTISENSOR 6 user guide

Aeotec

Aeotec MULTISENSOR 6 user guide

Qazqa Motion V CL 14W LED PIR manual

Qazqa

Qazqa Motion V CL 14W LED PIR manual

STEINEL professional MD-8 ECO COM1 manual

STEINEL

STEINEL professional MD-8 ECO COM1 manual

Omron Sti F3SJ-E N25 Series user manual

Omron

Omron Sti F3SJ-E N25 Series user manual

MSA Ultima OPIR-5 Alignment Guide

MSA

MSA Ultima OPIR-5 Alignment Guide

ADA INSTRUMENTS Wall Scanner 120 Prof operating manual

ADA INSTRUMENTS

ADA INSTRUMENTS Wall Scanner 120 Prof operating manual

LZR H100 manual

LZR

LZR H100 manual

Sanlien Palert Hardware System Installation Instruction

Sanlien

Sanlien Palert Hardware System Installation Instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.