  9. Teknim TWD-1850 Instruction Manual

Teknim TWD-1850 Instruction Manual

Release Date: 13/12/2021
Rev:02
Warnings
General
✓Read this manual with care before operating the device and keep it for further reference.
✓Comply with all warnings and measures provided in the manual. Follow all respective operation and usage
instructions.
✓Keep the devices away from water and moisture.
Environmental Conditions
Do not operate the device in extremely hot and cold environments other than the following conditions.
Temperature: Between -10°C and +55°C
Relative Humidity: Max. 95% RH
Service
Do not attempt to repair the device on your own, you may be exposed to electric shock in case you open the
device enclosure.
Contact your dealer or authorized service provider in case of a malfunction. Technical interventions to the
device must be carried out by a qualified technician from an authorized service provider.
Failures That Require Service Intervention
Contact your authorized service provider or installer in case of a failure or in following cases.
✓If the power line or power plug is damaged,
✓Any liquid leaking or a foreign substance entering the device,
✓Any exposure to water or rain,
✓Dropping the device or damaging the enclosure,
✓If there is significant performance change in the device,
✓If the device is not operating normally according to the operating instructions in this user manual
Please call your service provider as incorrect operations may cause further malfunctions.
What You Can Do On Your Own
Do not attempt to repair the device on your own, you may be exposed to electric shock in case you open the
device enclosure. Contact your dealer or authorized service provider in case of a malfunction. Technical
interventions to the device must be carried out by trained technical personnel of authorized service. The device
must be cleaned with a dry cloth. No chemical substances must be used for cleaning purposes.
Handling and Transportation
The device should be handled carefully so that it is not exposed to shocks and liquid ingress. Damages that
may occur during incorrect transportation are not covered by the warranty.
Human and Environment Health
This device does not contain any chemical or biological substance that may harm human health.
General Features
✓TLPWAN low power consumption, two-way safe and stable wireless communication protocol
✓Advanced smoke detection algorithm minimizing false alarms
✓Advanced heat detection algorithm with two NTC
✓Rejection of transient signals that can be detected as alarms.
✓Adaptive protection by continuously sampling the respective environment.
✓Easy to clean smoke chamber.
✓Pollution algorithm and warning.
✓Low battery warning.
✓Tamper warning.
✓Two LEDs for 360° status indication.
✓15sec. starting time
✓Three different sensitivity settings adjustable on the control panel.
✓Selection of different operation modes through the control panel (for addressable) or through coordinator
(for conventional)
Technical Specifications
Communication Distance
(via Coordinator or Router)
Up to 500 m (open space)
Operating Frequency
868 MHz
Operating Frequency Channels
10
Output Power
14 dBm (25 mW)
Average Consumption
25uA (@3V)
Battery
2xCR123A (3 Vdc)
Battery Life
Up to 8 years (up to 4 years if single battery is used)
Smoke Alarm Levels (aprx.)
H: 0.12, M: 0.15, L: 0.18 dB/m
Temperature Operating Modes
A2S, A2R
Operating Temperature Range
-10C ~ 55C (14F ~ 131F)
Humidity
95% RH
Size (mm) –base included
Ø110, h48
Housing Material
White Color, ABS Plastic
Weight (base incl. / base excl.)
183 gr / 125 gr
Starting Time
15 sec.
TWD-1850
TLPWAN Wireless Multi Detector
Installation & User Manual
Warning: Do not attempt to take the board out of its enclosure protection. It is sealed for your safety.
Users must avoid intervention.
TWD-1850
Wireless Multi Detector
Installation & User Manual
Connection/Test Button
CR123A Battery Housing
Tamper Switch
Programming Connector
Indicator LEDs
Condition
Led Signal Pattern
Any error situation
(Pollution, Tamper etc.)
Green LED blinks once in every 10 seconds
Device in normal operation mode
Green LED blinks once in every 20 seconds
Alarm mode
Red LED blinks once in every 2 seconds
Low battery warning
Orange LED blinks once in every 20 seconds
Network connection-disconnection
Result of the operation
Green LED blinks twice in every 2 seconds
Affirmative, green LED lights for 3 seconds
Not Affirmative, red LED lights for 3 seconds
Connection Quality
Connection Quality is Good; Green LED blinks 3 times
Connection Quality is Medium; Green LED blinks 2 times
Connection Quality is Poor; Green LED blinks once
No Connection; Red LED blinks once
Network Connection Procedure
In order for a device to join the network, that device must not have been included in any network before.
Whether the device has joined any network or not can be determined by the link test. Follow the steps below
for connecting the device to a network.
1. The connection permission on the coordinator or on the router must be on before the device is
connected to a network. Turn on the connection permission on the coordinator or on the router.
2. Press long (for 5 seconds) on the “Connection/Test” button located under the device.
3. The device will start the connection procedure automatically. This procedure takes about 20 to 60
seconds. The green LED will blink twice every 2 seconds during the procedure.
4. At the end of the procedure, the green LED will light for 3 seconds if the connection procedure is
successful, and the red LED will light for 3 seconds if the connection procedure is not successful.
Disconnection Procedure
Disconnection of the device from the network can be done both on the coordinator and on the device. Follow
the steps below for disconnecting the device from a network.
1. Press long (for 5 seconds) on the “Connection/Test” button located under the device.
2. The device will start the disconnection procedure automatically. The green LED will light for 3 seconds
at the end of the procedure.
Link Test
It is possible to measure the link quality between the device and the connected coordinator or router. For this,
press shortly on the “Connection/Test” button located under the device. If the device is connected to a network,
the LEDs will light as noted below at the end of the procedure:
Link Quality (RSSI)
LED Signal Pattern
RSSI > -60 dBm
Connection Quality is Good; Green LED blinks 3 times
-60 dBm > RSSI > -75 dBm
Connection Quality is Medium; Green LED blinks 2 times
-75 dBm > RSSI > -90 dBm
Connection Quality is Poor; Green LED blinks once
-90 dBm > RSSI
No Connection; Red LED blinks once
Heat Test
Providing an air flow having a temperature of 70°C will be enough to carry out the detector test.
1. Turn on the hot air flow and check temperature.
2. Blow the hot air into the device. The device must produce the alarm in 30 sec.
3. Check if the red LEDs light. Reset the detector from the panel after the test completed.
Smoke Test
For the smoke test, let the smoke enter the smoke detection chamber for at least 1 minute with the test
aerosol. LED lights will indicate the alarm when sufficient amount of smoke enters into the chamber.
1. Remove the smoke source when the alarm condition is reached.
2. Check if the red LEDs light. Reset the detector from the control panel.
3. If the detector does not generate an alarm within 1 minute, it should be sent to the service provider
for technical observation.
4. The system can be activated after the test is completed.
1922
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu OSB 1. Cad. İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Umraniye / Istanbul
21
1922-CPR-1595
EN 54-7:2018
Point Smoke Detectors (Scattered Light)
EN 54-5:2017+A1:2018
Point Heat Detectors
EN 54-25:2008, EN 54-25:2008/AC:2010, EN 54-25:2008/AC:2012
Components Using Radio Links
TWD-1850
Manufacturer
*In compliance with AEEE regulations. This product is manufactured with recyclable and reusable high quality
parts and materials. Do not dispose of the product together with domestic or other wastes at the end of its
service lifetime. Take it to a drop-off point for the recycling of electrical and electronic devices.
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu Organize Sanayi Bölgesi 1. Cadde İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Umraniye / Istanbul / Turkey
Phone Number: +90 216 455 88 46 Fax: +90 216 455 99 06
www.teknim.com
sales@bilgielektronik.com.tr
destek1@bilgielektronik.com.tr
Warning: After adding the device to the network, proceed the link test at the location of the device will
work. If there is no connection in the link test, the system will not work properly. In this case, change
the location of the device.
Warning: If no LED lights at the end of the Link Test, this means the device is not connected to any
coordinator or router.

Other Teknim Security Sensor manuals

Teknim TFD-1271 Instruction Manual

Teknim

Teknim TFD-1271 Instruction Manual

Teknim TFD-1261 Instruction Manual

Teknim

Teknim TFD-1261 Instruction Manual

Teknim TFD-1260 Instruction Manual

Teknim

Teknim TFD-1260 Instruction Manual

Teknim TFD-3250 Troubleshooting guide

Teknim

Teknim TFD-3250 Troubleshooting guide

Teknim TFD-1260A Instruction Manual

Teknim

Teknim TFD-1260A Instruction Manual

Teknim TWM-1885 Instruction Manual

Teknim

Teknim TWM-1885 Instruction Manual

Teknim TVSD143 User manual

Teknim

Teknim TVSD143 User manual

Teknim TSD-5150 User manual

Teknim

Teknim TSD-5150 User manual

Teknim TWD-1850 Instruction Manual

Teknim

Teknim TWD-1850 Instruction Manual

Teknim ATP545 User manual

Teknim

Teknim ATP545 User manual

Teknim TWM-3885 Instruction Manual

Teknim

Teknim TWM-3885 Instruction Manual

Teknim TFD-1270A Instruction Manual

Teknim

Teknim TFD-1270A Instruction Manual

Teknim TFD-3240 Troubleshooting guide

Teknim

Teknim TFD-3240 Troubleshooting guide

Popular Security Sensor manuals by other brands

Wieland Gesis KNX P CO installation manual

Wieland

Wieland Gesis KNX P CO installation manual

CAMDEN CM-RQE70A installation instructions

CAMDEN

CAMDEN CM-RQE70A installation instructions

PCB Piezotronics IMI SENSORS EX641B70D Installation and operating manual

PCB Piezotronics

PCB Piezotronics IMI SENSORS EX641B70D Installation and operating manual

AJAX LeaksProtect manual

AJAX

AJAX LeaksProtect manual

Maxwell 25850 user manual

Maxwell

Maxwell 25850 user manual

nest 06C user guide

nest

nest 06C user guide

Smoke Guard M2500 Smoke Operation & maintenance manual

Smoke Guard

Smoke Guard M2500 Smoke Operation & maintenance manual

NA-DE 10951 quick start guide

NA-DE

NA-DE 10951 quick start guide

QubicaAMF 400288005 installation manual

QubicaAMF

QubicaAMF 400288005 installation manual

Schmidt SS 20.651 Instructions for use

Schmidt

Schmidt SS 20.651 Instructions for use

TUYA PIR313-Z-TY quick start guide

TUYA

TUYA PIR313-Z-TY quick start guide

jablotron JA-187P quick start guide

jablotron

jablotron JA-187P quick start guide

IFM Electronic efector300 SM7100 operating instructions

IFM Electronic

IFM Electronic efector300 SM7100 operating instructions

Agatec SmartRod user manual

Agatec

Agatec SmartRod user manual

Nivel System RD700 DIGITAL instruction manual

Nivel System

Nivel System RD700 DIGITAL instruction manual

schmersal RSS 36-D-ST5 manual

schmersal

schmersal RSS 36-D-ST5 manual

SICK deTem2 Core operating instructions

SICK

SICK deTem2 Core operating instructions

Angstrom MoneyChecker 6700 Operation instructions

Angstrom

Angstrom MoneyChecker 6700 Operation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.