Tektino RCC-9A User manual

TEKTINO RCC-9A maintenance manual V2.0
i
INDEX
1.Equipment description.....................................................................................................................................................1
Part description...........................................................................................................................................................1
Component layout on manifold..................................................................................................................................2
Pipeline diagram.........................................................................................................................................................3
PCA............................................................................................................................................................................ 4
2.Routine maintenance....................................................................................................................................................... 5
Maintenance of vacuum pump................................................................................................................................... 5
Change drier filter, evacuate drier filter and reset service interval time....................................................................7
Leak test......................................................................................................................................................................8
3.Troubleshooting...............................................................................................................................................................9


TEKTINO RCC-9A maintenance manual V2.0
1
1. Equipment description
Part description
1)Refrigerant gas cylinder 2)Gas cylinder support plate 3) Gas cylinder load cell
4)Oil bottle load cell 5)Oil bottle support 6)Oil bottles
7)Assembly of solenoid valve and
check valve
8)Manifold assembly 1 9)front cover (plastic)
10) Front wheel 11)Compressor 12)Vacuum pump
13
)
Condenser and cooling fan
(optional)
14)Rear wheel 15)Side cover
16)Accessory holder 17)Back cover 18)Upper cover
19)Pressure gauges 20)Manifold 2 21) Drier-filter
1
2
3
4
5
6
7
8
18
9
10
17
16
15
14
11
13
12
20
21
19

TEKTINO RCC-9A maintenance manual
2
Component layout on manifold
MANIFOLD ASSEMBLY 1
MANIFOLD ASSEMBLY2

TEKTINO RCC-9A maintenance manual V2.0
3
Pipeline diagram
EV: Solenoid
LP: Low pressure switch (or pressure sensor, if machine has vacuum leak test function)
HP: High pressure switch
CV: non-return valve

TEKTINO RCC-9A maintenance manual
4
PCA

TEKTINO RCC-9A maintenance manual V2.0
5
2. Routine maintenance
Maintenance of vacuum pump
1) Vacuum pump description
1. Exhaust emission port
2. Suction port
3. Pump oil adding port
4. Oil level vision window
5 Oil discharge port
2) Change vacuum pump oil or add vacuum pump oil
The pump works over 100 hours, or turbidity or emulsion is
found, the oil should be changed. Prepare a container with
capacity bigger than 500ml to hold used oil. OIL No ISO100.
2

TEKTINO RCC-9A maintenance manual
6
Change drier filter, evacuate drier filter and reset service interval time
When a drier filter is replaced, the moisture may enter into equipment pipeline and affects quality of refrigerant
in the equipment tank. Thus it is mandatory to evacuate the drier filter each time a drier filter is replaced.
a) Remove the used drier filter, and mount the new one.
b) By pressing and ENTER key, turn on the machine, the machine requests password to enter distributor
service page:
Up/down arrow: increase/decrease number
Left/right arrow: move digit
Password: 441329
c) Turn off the machine and turn it on again, to check if service interval time has been set successfully. The
machine should be permitted to operate 1200 time again.

TEKTINO RCC-9A maintenance manual V2.0
7
LEAK TEST
Under the following situations, it is possible that the machine has leakage in pipeline connections, thus need to
make leakage test:
1. The refrigerant volume in equipment tank reduces, without operations;
2. Compressor and Solenoids work well, while recovery works too slow or can not work normally;
3. Any operations or equipment maintenance that needs to disconnect and connect the pipelines or adaptors
that may cause leakage. For example, change drier-filter.
There are two methods to make leakage tests: Leakage detector and high pressure test:
1. Leakage test with refrigerant detector: When equipment pipeline is full of refrigerant, for example,
during running recovery, use refrigerant detector to find out the leakage points.
2. High pressure leakage test:
a) Connect Nitrogen generator (In case no nitrogen generator can be found, can use air compressor) to
equipment SUCTION or CHARGE port, and run recovery until it stops with high pressure alarm
b) Block the SUCTION and CHARGE ports with nut caps.
c) Enter “Component test” page by following procedure
P.W.: 111111
d) In “Component test” page, turn on V1, V5, V9, V10, V11 and V12. Wait until the pressure shown in 3
pressure gauges become equal, turn off the equipment.

TEKTINO RCC-9A maintenance manual
8
d) Write down the pressure of each gauge, shut down the equipment. After 4 hours, check pressure of the
three gauges. If any gauge shows more than 0.1 BAR pressure down, means the pipeline related to that
pressure gauge has leakage (refer to pipeline diagram of this manual).
e) Use soapy water to find the exact connection that causes leakage, as pic. 9.
Pic. 9
f) Tighten the connection and make leakage test again.

TEKTINO RCC-9A maintenance manual V2.0
9
3. Main troubleshooting
Ma lf un ctio n Re ason s So lut io n
Low vacuum degree
1. Insufficient vacuum pump oil.
2. Pump oil emulsion, dirty
3. Pump oil inlet plugged.
4. Leakage in pump connection.
5. Components worn out.
1. Add oil to central line
2. Put new oil
3. Clean oil inlet.
4. Check connection
5. Put new pump.
Vacuum pump inject
oil.
1. Excessive oil volume.
2. Entrance pressure too high.
1.Discharge oil to central line
2.Run Recovery function first.
No display
1. Fused (in Power cable connection
box, or PCA)
2. PCA burnt.
3. Power cable loosened.
4. LCD not work
1. Change fuses.
2. Change PCA.
3. Connect power cable reliably.
4. Change LCD.
Recovery does not
stop
1. Leakage in automotive A/C or
equipment pipeline.
2. Compressor not work
Remarks: In winter, it is normal
that recovery takes longer time.
1. Make leakage test. Machine leakage test
with referenc to service manual.
2. Change compressor.
No change in
recovery volume
1. No refrigerant in A/C.
2. Support screw of gas cylinder load
cell not loosened.
3.Gas cylinder load cell not work or
PCA failure.
4.For RCC-6A, hand valves not
opened.
1. Stop recovery.
2. Unsrew the support screw in the bottom of
the weight sensor.
3. Calibrate gas cylinder load cell, or change
the load cell, or change PCA.
4. Open RCC-6A HP/LP hand valves
While auto A/C has
refrigerant,
equipment displays
alarm 005
1. Low pressure switch plug
disconnected from PCA socket.
2. For RCC-6A, hand valves closed
1. Fasten low pressure switch plug.
2. Open RCC-6A HP/LP hand valves
High pressure alarm
004 but gas cylinder
gauge does not show
excessive pressure
value
1. High pressure switch plug
disconnected from PCA socket.
2. Pipeline connecting compressor
exit blocked.
1. Fasten high pressure switch plug.
2. Change compressor exit side hoses.
No charge or slow
charge.
1.Insufficient refrigerant in
equipment
2.System has pressure.
3.Charge solenoid not work.
1. Add refrigerant to 5kg.
2. Run recovery first.
3.Check solenoid No5.

TEKTINO RCC-9A maintenance manual
10
During recovery,
vacuum pump is
pressurized. After
period too much oil
in vacuum pump
The contact between solenoid valve
No.4 and valve base is not well
sealed.
Remove solenoid No.4 from valve base,
clean the solenoid valve and valve base.
During vacuum,
there is suction in old
oil bottle.
The contact between solenoid valve
No.2 and valve base is not well
sealed.
Remove solenoid No.2 from valve base,
clean the solenoid valve and valve base.
Table of contents