Status Information
RECTIFIER START ! : Rectifier started to operate.
INVERTER START ! : Inverter started to operate.
MAINT SWITCH ON ! : Maintenance Bypass Switch is on.
MANUEL BYPASS ! : Load manually transferred to grid.
STATUS ALARM ! : Alarm status message on the lower line means alarm status situation is temporary
STATUS NORMAL ! : UPS operates normally.
EMERGENCY STOP ! : Emergency shut-off button is pressed.
WAITING SYNC ! : Inverter operated I am waiting for grid synchronization to transfer the load.
STATUS FAULT ! : Failure status is permanent.
STATUS WARNING ! : Warning status message on the lower line is a warning system functioning but, Caution!
CLOSE BATT.CB ! : UPS waits opening of accumulator switch.
3.4 Special situations while remote monitoring panel operates
•If panel's communication with UPS interrupts, all values coming from UPS will be seen as "! ! ! ” for 10
seconds and panel will give audio warning as very short "beep" with one minute breaks.
•Short "beep" button voice is given in every press on panel buttons.
•When the panel voice is turned-off on the menu, panel's audio alarm will be prevented. If a different
alarm occurs, panel voice will be opened automatically.
4. POSSIBLE FAILURES
•If electricity is not supplied to panel when the supply cable is plugged, supply cable may be failed. The
socket which the cable is plugged in may be failed. Main card transformer of remote monitoring panel
may be failed.
•All connections made with UPS but if communication interrupted alarm is given on the remote
monitoring panel screen;
oControl whether the selected communication interface is correct. RS232 / RS485
communication ports are different.
oCable may be failed. Plug the cable to a PC that you are sure of having functional com port
directly with UPS and try with T-mom software. If not functional, try with another CC05 cable.
oIf you are sure about the cable soundness and communication error is still available, a problem
may be available in the main card of remote monitoring panel. Inform the service.
•UPS Communication is available but if measured values are false or various values cannot be read;
oIn this case, see the communication status of UPS from the "Alarms Menu".
UPS: 232 Tout P1 etc. messages will be seen. In this case, UPS's software version
will be incompatible. UPS software should be in TX100 or TX300 communication protocol.