1. General Information
Model L1512D LED luminaires are suitable for use in
the following hazardous (classified) areas as defined
by the National Electrical Code (NEC) and Canadian
Electrical Code (CEC):
lClass I, Division 1, Groups B, C, D
lClass I, Division 2, Groups A, B, C, D
lClass II, Division 1, Groups E, F, G
lWet Locations (UL 1598)
Refer to the luminaire nameplate for specific
classification information, maximum ambient
temperature suitability and corresponding operating
temperature (T-Code).
Model L1512D LED luminaire is designed for using in
indoors and outdoors environment.
Rated Voltage (DCOB): 120/277/347/480 Vac,
50 & 60 Hz
Rated Voltage (DOB): 120/277 Vac,
50 & 60 Hz
Ambient Temperate Range:
-25°C ~ +40°C (CID1:T5, CID2:T3, CIID1 :T4A)
-25°C ~ +55°C (CID1:T4A, CID2:T3, CIID1:T4)
WARNING
uTo avoid the risk of fire, explosion or electric shock, this product should be installed, inspected and
maintained by a qualified electrician only, in accordance with all applicable codes and regulations.
uTo avoid electric shock:
üBe certain electrical power is OFF before and during installation and maintenance.
üLuminaire must be supplied by a wiring system required by the NEC and CEC for the specific
hazardous locations with an equipment grounding conductor.
uTo avoid explosion:
üMake sure that the supply voltage is the same as the luminaire voltage.
üDo not install where the marked operating temperatures exceed the ignition temperature of the
hazardous atmosphere.
üDo not operate in ambient temperatures above those indicated on the luminaire nameplate.
üAll gasket seals must be clean and undamaged.
üBefore dismounting, electrical power to the luminaire must be turned off. Keep tightly closed
when in operation.
uTo avoid burning hands, ensure the luminaire is cool when performing maintenance.
uThe internal grounding terminal shall be used as the equipment grounding means and the external
terminal is only a supplemental bonding connection.
u“WARNING: To prevent ignition of Group B atmospheres conduit runs must have a sealing fitting
connected within 9 inches of the luminaire”.
uMounting Orientation – Lens horizontal Facing Down or Lens Facing Down 45° from vertical.