
–10–
EN
◆Tightening connection
Do not apply excessive torque. Otherwise, the nut may
crack depending on the conditions.
▼Tightening torque of flare pipe connections
Pressure of R410A is higher than that of R22.
(Approx. 1.6 times) Therefore, using a torque wrench,
tighten the flare pipe connecting sections which
connect the indoor and outdoor units of the specified
tightening torque.
Incorrect connections may cause not only a gas leak,
but also a trouble of the refrigeration cycle.
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
Tightening with an excessive torque may crack the nut
depending on installation conditions.
Tighten the nut within the specified tightening torque.
◆Piping with outdoor unit
Shape of valve differs according to the outdoor unit.
For details of installation, refer to the Installation
Manual of the outdoor unit.
Airtight test / Air purge, etc.
For airtight test, air purge, addition of refrigerant, and
gas leak check, refer to the Installation Manual
attached to the outdoor unit.
Do not supply power to the indoor unit until the airtight
test and vacuuming are completed. (If the indoor unit is
powered on, the pulse motor valve is fully closed, which
extends the time for vacuuming.)
◆Open the valve fully
Open the valve of the outdoor unit fully.
For details, refer to the Installation Manual attached to
the outdoor unit.
◆Heat insulation process
Apply heat insulation for the pipes separately at liquid
side and gas side.
For the heat insulation to the pipes at gas side, be sure
to use the material with heat-resisting temperature 120
°C or higher.
Using the attached heat insulation material, apply the
heat insulation to the pipe connecting section of the
indoor unit securely without gap.
• Apply the heat insulation to the pipe connecting
section of the indoor unit securely up to the root
without exposure of the pipe. (The pipe exposed to the
outside causes water leak.)
• Wrap heat insulator with its slits facing up (ceiling
side).
(Unit : N•m)
Outer dia. of copper pipe Tightening torque
6.4 mm (dia.) 14 to 18 (1.4 to 1.8 kgf•m)
9.5 mm (dia.) 33 to 42 (3.3 to 4.2 kgf•m)
12.7 mm (dia.) 50 to 62 (5.0 to 6.2 kgf•m)
15.9 mm (dia.) 63 to 77 (6.3 to 7.7 kgf•m)
Work using double spanner
Indoor unit
Union
Heat insulation
pipe
(Accessory)
Flare nut
Heat insulator
of the pipe
Wrap the pipe with the attached heat insulator
without any gap between the indoor unit.
The seam must be faced upward
(ceiling side).
Banding band
(Locally
procured)
7Electrical connection
1. Using the specified wires, ensure to connect the
wires, and fix wires securely so that the external
tension to the wires do not affect the connecting
part of the terminals.
Incomplete connection or fixation may cause a fire,
etc.
2. Be sure to connect earth wire. (grounding work)
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water
pipes, lightning rods or ground wires for telephone
wires.
3. Appliance shall be installed in accordance with
national wiring regulations.
Capacity shortage of power circuit or incomplete
installation may cause an electric shock or a fire.
• If incorrect / incomplete wiring is carried out, it will
cause an electrical fire or smoke.
• Be sure to install an earth leakage breaker that is not
tripped by shock waves.
If an earth leakage breaker is not installed, an electric
shock may be caused.
• Be sure to use the cord clamps attached to the
product.
• Do not damage or scratch the conductive core and
inner insulator of power and system inter connection
wires when peeling them.
• Use the power cord and system inter connection wire
of specified thickness, type, and protective devices
required.
• Never connect 220-240 V power to the terminal blocks
( , , , , etc.) for control wiring.
(Otherwise, the system will fail.)
• For power supply wiring, strictly conform to the Local
Regulation in each country.
• For wiring of power supply of the outdoor units, follow
the Installation Manual of each outdoor unit.
• Perform the electric wiring so that it does not come to
contact with the high-temperature part of the pipe.
The coating may melt resulting in an accident.
• After connecting wires to the terminal blocks, provide
a trap and fix wires with the cord clamp.
• Run the refrigerant piping line and control wiring line in
the same line.
• Do not turn on the power of the indoor unit until
vacuuming of the refrigerant pipes completes.
Power supply wire and
communication wires
specifications
Power supply wire and communication wires are locally
procured.
For the power supply specifications, follow to the table
below. If capacity is little, it is dangerous because
overheat or seizure may be caused.
For specifications of the power capacity of the outdoor
unit and the power supply wires, refer to the Installation
Manual attached to the outdoor unit.
◆Indoor unit power supply
• For the power supply of the indoor unit, prepare the
exclusive power supply separated from that of the
outdoor unit.
• Arrange the power supply, earth leakage breaker,
and main switch of the indoor unit connected to the
same outdoor unit so that they are commonly used.
• Power supply wire specification : Cable 3-core
2.5 mm², in conformity with Design 60245 IEC 57.
▼Power supply
◆Control wiring, Central controller
wiring
• 2-core with polarity wires are used for the Control
wiring between indoor unit and outdoor unit and
Central controller wiring.
• To prevent noise trouble, use 2-core shield wire.
• The length of the communication line means the total
length of the inter-unit wire length between indoor
and outdoor units added with the central control
system wire length.
Power supply 220-240 V ~, 50 Hz
220 V ~, 60 Hz
Power supply switch / Earth leakage breaker or power
supply wiring / fuse rating for indoor units should be
selected by the accumulated total current values of the
indoor units.
Power supply wiring Below 50 m 2.5 mm²
19-EN 20-EN
+00EH99891001_01EN.book Page 10 Monday, May 14, 2012 11:31 AM