Some useful DN codes.
For a full list of “DN Codes” please refer to the service manual for the installed equipment or to one of the
”CDL Pocket Handbooks”
ITEM DESCRIPTION
VALUE
03
Network address
When under network control.
00Un/ 0099
06 Stratification control Increases effective return air temperature setting in heating mode (0 to 10K) 0000 to 0010
Floor type
0d
Auto mode
Enable or disable Auto mode 0000 = available
0001 = unavailable
0E
SHRMi only
Used when multiple indoor units are served via a single FS box
0000 = normal 0001= multiple units
0000
0F
Heat Mode
Enable or disable Heat Mode
0000 = available
0001 = unavailable
0000
10 Indoor unit model Must be set when replacing indoor printed circuit board
0000: 1-way cassette (s models)
0003: 1-way cassette (y models)
0014: 4-way compact cassette (600 x 600)
0050: air to air heat exchanger
11 Indoor unit capacity 0000 will generate a (L09) fault
M M R A V
M M
R A V
Air to air heat exchanger Type
0 0 0 1 =
150m3/h
0 0 0 6 =
800m3/h
0 0 0 2 =
250m3/h
0 0 0 7
= 1000m3/h
0 0 0 3 =
350m3/h
0 0 0 8
= 1500m3/h
0 0 0 4 =
500m3/h
0 0 0 9
= 2000m3/h
12 System number
DI/SDI indoor and outdoor units are automatically addressed, this
value may be set manually but it must be done via the wired
controller – on an individual basis. Settings are 0001 to 0030
0001: outdoor unit 1
0002: outdoor unit 2
00Un/ 0099
13 Indoor unit number
Indoor units connected to a common outdoor unit (e.g., twinned
indoor units) will have the same system number - settings are 0001
to 0064. Automatically allocated – but may be manually overridden.
0001: indoor unit 1
0002: indoor unit 2
00Un/0099
14
Group master/slave
Allows selection of master indoor unit within group.
Automatically allocated but may be manually overridden.
0000: single indoor unit 0001: group
master 0002: group slave
ooUn/0099
16 Indoor Fan Indoor fan speed selection. Binary addition. 0015 = all speeds available
auto; 2 = low; 4 = medium; 8 = high
except high static
1E
Dead band - auto
Changeover sensitivity in automatic mode. (1 to 10 k adjustable)
0000: 0 K 0010: 10 K
0003
1F Max. Setting
Cooling mode maximum temperature setting (18 – 29oC)
0018 = 18oC 0020 = 20oC 0029 = 29oC
29 oC
20 Min. Setting Cooling mode minimum temperature setting (18 – 29oC) 0018 = 18oC 0020 = 20oC 0029 = 29oC
18 oC
21 Max. Setting Heating mode maximum temperature setting (18 – 29oC) 0018 = 18oC 0020 = 20oC 0029 = 29oC
29 oC
22 Min. Setting
Heating mode minimum temperature setting (18 – 29oC)
0018 = 18oC 0020 = 20oC 0029 = 29oC
18 oC
23 Max. Setting
Dry mode maximum temperature setting (18 – 29oC)
0018 = 18oC 0020 = 20oC 0029 = 29oC
29 oC
24 Min. Setting
Dry mode minimum temperature setting (18 – 29oC)
0018 = 18oC 0020 = 20oC 0029 = 29oC
18 oC
25 Max. Setting
Auto mode maximum temperature setting (18 – 29oC)
0018 = 18oC 0020 = 20oC 0029 = 29oC
29 oC
26 Min. Setting
Auto mode minimum temperature setting (18 – 29oC)
0018 = 18oC 0020 = 20oC 0029 = 29oC
18 oC
28
Auto restart
Enable or disable 0000: disabled 0001: enabled
0000
2d Modes available Binary addition of modes available.
0015= all modes
1 = fan; 2 = cool; 4 = dry 8 = heat
0015
103 Remote Controller VRF IDU “Up” series. Local remote controller used or not used
0000: Use 0001: Do not use
0000
1FC IDU “U” series IDU Terminating resistance
0000: Off 0001: On
0000