– 18 –
TROUBLESHOOTING GUIDE
REMOTE CONTROLLER
「ON
」
POWER TIMER OPERATION
(green) (yellow) (green)
NO
NO
NO
NO
NO
NO
OFF OFF OFF
ON OFF ON
ON
OR
OFF OFF
FLASHING FLASHING
OFF
FLASHING
NO ROTATION
SLOW ROTATION
YES YES
YES YES
YES YES
YES YES
YES YES
YES YES
YES YES
YES
NO
NO
NOT COOL ENOUGH
NOT COOL ENOUGH
NOT DRAIN ENOUGH
COOLAIR DOESN'T
COME OUT
(OPERATING IN
HEATING MODE)
TAN FAN REPEATED
"OPERATION STOP"
NOISE
outdoor unit stops before
reaching set up temp.
POWER SUPPLY check the plug inserted into the outlet and the power supply
REMOTE CONTROL
FUSE (3.15A)
FUSE (3.15A)
PCB (RECEIVER & DISPLAY)
if the battery is dead or failure in remote controller
change to new one
check the fuse by eyes or cheak the electric continuity by tester
other than described above [how to operate emergency operation test
operation]
OFF OFF OFF
FLASHING
OFF OFF
FLASHING
ON ON
"POWER LAMP" GREEN ON
LOUVER
「
OPEN
」
SENSOR, TEMP. ROOM
"OPERATION LAMP" GREEN ON
TAG FAN ROTATING
COMPRESSOR IS WORKING
OPERATING IN DRY MODE
OPERATING IN COOLING MODE
REMOTE CONTROLLER
「
OFF
」
COMPRESSOR
TAN FAN STOP
TAG FAN
"OPERATION LAMP" OFF
"POWER LAMP" OFF
LOUVER
「
CLOSE
」
STOP
SENSOR, TEMP. HEAT EXCHANGER
SENSOR, TEMP. ROOM
MOTOR, LOUVER
SENSOR, TEMP. ROOM
SETTING TEMPERATURE
SENSOR, TEMP. ROOM
COMPRESSOR
PREVENTION FOR FREEZING
MIS-WIRING
PCB (MAIN CONTROLLER)
CAPACITOR, TAG FAN MOTOR
TAG FAN MOTOR
PCB (MAIN CONTROLLER)
CAPACITOR, TAG FAN MOTOR
TAG FAN MOTOR
DROP VOLTAGE
BY DROP VOLTAGE
DEFECTIVE WIRING CONTACTS
EXCESS GAS
CAPACITOR, COMPRESSOR
COMPRESSOR LOCKING
PREVENTION FOR OVERHEATING RELAY
MIS-WIRING
CUTTING OFF CT
COMPRESSOR BREAKDOWN
MIS-WIRING
SHORT CIRCUIT OF WIRINGS
SENSOR, TEMP. HEAT EXCHANGER
4-WAY VALVE
FILTER IS CHOKED
SENSOR, TEMP. ROOM
SENSOR, TEMP. HEAT EXCHANGER
PLACE OF INSTALLATION
PLACE OF INSTALLATION
EXCESS GAS
COMPRESSOR BREAKDOWN
SHORTAGE OF GAS
PLACE OF INSTALLATION
TANGENTIAL FAN
PIPE
LOUVER POSITION
SHORTAGE OF GAS
MIS-INSTALLATION
DRAINAGE
TAN FAN MOTOR
MIS-WIRING
SHORT CIRCUIT OF WIRINGS
check the resistance by tester [see table 1]
check the resistance by tester [see table 2]
check the resistance between two terminals [see fig.2,table 3]
check the resistance by tester [see table 2]
adjust proper temperature in remote controller
check the resistance by tester [see table 2]
check the restarting operation of compressor, after passing 3 minute
check the resistance of sensor (temp. heat exchanger)
[see table 1]
check the wiring order
if the scale of the tester swings instantly to "zero
Ω
" and does
not move back to "infinity", capacitor for TAG fan motor should
be replaced [NOTE.1]
other than described above
if the scale of the tester swings instantly to "zero
Ω
" and does not
move back to "infinity" TAG fan motor should be replaced [NOTE.1]
other than descrived above
check proper voltage of power supply and use an exclusive power supply
check proper voltage of power supply and use an exclusive power supply
check by eyes
check the pressure of gas [check
「
performance curve diagram
」
]
if the scale of the tester swings instantly to "zero
Ω
" and does not
move back to "infinity", capacitor for compressor should be replaced
[NOTE.1]
other than described above
leak of gas, or cut off prevention for overheating relay
check the wiring order
change PCB(main controller)
other than described above
other than described above
check by eyes and clean it
check the resistance by tester [see table 2]
check the resistance by tester [see table 1]
check the blockage of air outlet of TAN
check the blockage of air inlet & air outlet of TAG
check the pressure of gas [check
「
performance curve diagram
」
]
other than described above
check the pressure of gas [check
「
performance curve diagram
」
]
check the blockage of air inlet & air outlet of TAG
check by eyes after power off. turn by hands and check noise
check by eyes around the pipes with any obstacles
level louver position
check the pressure of gas [checkk
「
performance curve diagram
」
]
check the level of TAN
check the drain pipe is stopped up
if DC5V is achieved between black and brown lead wiring of fan
motor, while no voltage of pulse between white and black wiring,
then TAN fan motor should be replaced
check the voltage between 2 and 3 in terminal [see fig. 6]
check the voltage between 2 and 4 in terminals [see fig.5]
check the voltage between 2 and 4 in terminals [see fig.5]
check the wiring between 2 and 3 in terminal (not turning TAG fan)
MOTOR, TAN FAN check the voltage by tester [see fig 3]
check the fuse by eyes or cheak the electric continuity by tester
FLASHING
[NOTE.1] Measure the resistance by changing the pole of the tester by turns.
OFF
FLASHING
1 〜4 Terminal Number on Terminal Block of TAG. (outdoor unit)★
ON
FLASHING
OFF
FLASHING FLASHING
check the voltage between 2 and 3 in terminal [see fig. 6]
check the wiring between 2 and 3 in terminal (not turning TAG fan)
check the resistance by tester [see table 1]
TAN FAN ROTATING
DRY & COOLING OPERATION