
6SS-APG010C-EN
Line Sizing, Routing, and Component Selection
Routing
Install the liquid line with a slight slope in the direction of flow so that it can be routed with the
suction line.
A height limitation exists for liquid lines that include a liquid riser because of the loss of subcooling
that accompanies the pressure loss in the height of the liquid column. Figure 2, Figure 3, and
Figure 4, p. 4, depict the permissible rise in the liquid line (without excessive loss of subcooling).
Again, system designs outside the application envelope of the TTA/TWA unit require Trane review.
Insulation
The liquid line is generally warmer than the surrounding air, so it does not require insulation. In
fact, heat loss from the liquid line improves system capacity because it provides additional
subcooling. If the liquid line is routed through a high temperature area, such as an attic or
mechanical room, insulation would be required.
Components
Liquid-line refrigerant components necessary for a successful job may include a filter drier, access
port, solenoid valve, moisture-indicating sight glass, expansion valve(s), and ball shutoff valves.
Figure 5, p. 5, illustrates how to sequence the components properly in the liquid line. Position the
components as close to the indoor unit as possible. Table 3, p. 16, identifies suitable components,
by part number, for each outdoor unit.
Liquid Filter Drier
There is no substitute for cleanliness during system installation. The liquid filter drier prevents
residual contaminants, introduced during installation, from entering the expansion valve and
solenoid valve. All outdoor units have a filter drier pre-installed. However, on the
6-, 7-1/2-, and 10-ton TTA/TWA units, if the refrigerant line length exceeds 80 ft, this filter should be
removed and a new one selected from Table 3, p. 16, and installed close to the indoor unit. Only
units this size require the filter to be moved because of their larger line sizes and greater amount
of introduced contaminants. If choosing a filter other than the one listed in Table 3, p. 16, make sure
its volume, filtering, and moisture-absorbing characteristics are equivalent.
Note that TWA units will require two filters and two check valves due to the reverse flow nature of
a heat pump.
Access Port
The access port located at the (4) TTA/TWA allows the unit to be charged with liquid refrigerant and
is used to determine charge level. This port is usually a Schraeder valve with a core.
Solenoid Valve
In (4) TTA cooling-only split systems, solenoid valves may be used to isolate the refrigerant from
the evaporator during the off cycles. This is only done when the indoor unit is well below the
outdoor unit. The solenoid valve on the TTA unit is a drop solenoid—open when the compressor
is on, and closed when the compressor is off. If used, the solenoid requires code compliant wiring
to the (4) TTA condensing unit. (The solenoid is not shown on the unit wiring diagram.)
Note: Solenoids should not be used on heat pumps due to the reverse flow of the liquid.
Moisture-Indicating Sightglass
A moisture-indicating sightglass should be installed in the main liquid line at the blower coil.
Note: The sole value of the glass is its moisture-indicating ability. Use the Installation manual
charging curves—not the sightglass—to determine proper charge levels.