ALPU-ALVR
1. This product is intended for use only on data and DC power
circuits with operating voltages not to exceed 55VDC and
operating currents not to exceed 1A. The Product is UL 497 Listed.
And is appropriate for use as either a primary or secondary
protector.
2. Mounting the ALPU-ALVR (See Diagram): Mount the device as
close to the equipment to be protected as possible using the
provided hardware and the concealed mounting holes. Mount
the unit in the orientation shown, with the marking “UP” facing
upward and the strain reliefs facing the ground.
3. Wiring the ALPU-ALVR
3.1 Removing the Cover: Loosen the 4 captive cover screws
using a Phillips screwdriver and lift off the cover.
3.2 Wiring the Suppressor: Thread a multiconductor cable from
the data source through the strain relief adjacent to the marking
on the PCB labeled Input. Strip back the cable jacket as
needed, then install the conductors into the IDC connectors
labeled Input using the following technique: Lay the wires into
the grooves in the connector, leaving approximately 1/8” of wire
overhanging, and press down firmly with the punch-down tool
provided in the packaging supplies until the wires firmly engage
into the fork terminals. Use the wiring tables in this document
as well as the callouts on the PCB as a guide. Repeat this
procedure for the outgoing multiconductor cable, using the
connectors labeled Output. Tighten the strain reliefs to secure
the cables (DO NOT OVER TORQUE!!). Reinstall the cover.
The ALPU-ALVR is intended to be used with the following
Alvarion Product Families: BreezeMAX; BreezeACCESS VL;
BreezeACCESS 4900; BreezeNET B Series and DS.11 Version 4.
Use the pinout configuration in Table 1.
3.3 Grounding: Connect the external ground lug on the enclosure
to a solid Earth ground. The unit must be grounded for the
suppressor to operate properly!
800.882.9110 or 208.772.8515
niP54-JRnoitcnuF
1+XT
2-XT
3+XR
6-XR
7,4V55+
8,5)NRUTER(V55-
dleihSNIARD
CONCEALED MOUNTING
HOLES
STRAIN RELIEFS ACCEPT
CABLE DIAM. RANGE
0.250" THRU 0.375"
EXTERNAL GND LUG
ACCEPTS 4-14 AWG
(119.1)
Table I