  9. Tyco Fire Product CENTRAL H User manual

Tyco Fire Product CENTRAL H User manual

Fire Protection Association, in addition
to the standards of any other authorities
having jurisdiction. Failure to do so may
impair the integrity of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Sprinkler Identification Number
SIN C3711
Approvals
UL & ULC Listed. FM & NYC Approved
(Refer to Table 1. The approvals apply
only to the service conditions indicated
in the Design Criteria Section)
Maximum Working Pressure
175 psi (12,1 bar)
250 psi (17,3 bar) UL & ULC
Pipe Thread Connection
1/2 inch NPT
Discharge Coefficient
K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
Temperature Ratings
165°F/74°C or 212°F/100°C
Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
The Model H Recessed Pendent
Sprinklers utilize a dezincification resistant
(DZR) bronze frame and a brass deflector.
The waterway is sealed with copper seal
disk, and the fusible assembly is con-
structed of bronze and stainless steel
components.
Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model H Recessed
No. 1-3.0
5.6 K-factor
Standard Response
Standard Coverage
Recessed Pendent Fusible Solder Type Sprinkler
General
Description
The Central Model H, 5.6 K-factor
Recessed Pendent Sprinklers are
automatic sprinklers of the fusible solder
type. They are standard response -
standard orifice spray sprinklers
intended for use in fire sprinkler
systems designed in accordance with
the standard installation rules recog-
nized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on NFPA 13 requirements).
The Central Model H Recessed
Pendent Sprinklers incorporate a center
strut mechanism with a special two-
piece recessed escutcheon assembly
permitting 1/2" of field-adjustment.
Unlike most other recessed sprinklers,
the upper escutcheon support piece is
factory installed on the base of the
sprinkler frame, assuring a Listed
installation. The ceiling escutcheon
plate is easily installed after the
sprinkler is in place either by the
standard “push-on” escutcheon or the
special “thread-on” escutcheon. This
feature allows removal of ceiling panels
for easy access to ceiling equipment
without taking the system out of service
to remove the sprinkler.
Operation: A fusible alloy is sealed into
a bronze actuating rod (center strut) by
a stainless steel ball. When the alloy
melts at its rated temperature, the ball is
forced upward into the center strut,
releasing the two ejectors and operating
the sprinkler.
WARNING
The Model H Recessed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document, as well as with the
applicable standards of the National
Technical
Data
CENTRAL H 2-01
Standard Spray
Recessed
Pendent
Sprinklers
OBSOLETE
MODEL A/H
RECESSED
ESCUTCHEON
DEFLECTOR
SPRINKLER
FRAME
EJECTOR
SPRING
ACTUATING
ROD
CAP SEAL DISK
SUPPORT
CUP
1"
(25,4 mm)
15/16"±
1/4"
(23,8 mm±6,4 mm)
2-3/4"(69,9 mm) Max.
2-1/2" (63,5 mm)Min.
1"±1/4"
(25,4mm ±6,4mm)
3-1/4" (82,6 mm)
WRENCH
FLAT
FACE OF SPRINKLER
FITTING
FINISHED
CEILING
ESCUTCHEON
1"
(25,4 mm)
15/16"±
1/4"
(23,8 mm±6,4 mm)
2-3/4"(69,9 mm) Max.
2-1/2" (63,5 mm)Min.
1"±1/4"
(25,4mm ±6,4mm)
3-1/4" (82,6 mm)
WRENCH
FLAT
FACE OF SPRINKLER
FITTING
FINISHED
CEILING
ESCUTCHEON
Figure 2 - Model H Recessed Sprinkler
with Threaded Escutcheon
Figure 1 - Model H Recessed Sprinkler
with Push-on Escutcheon
Figure 3 - Cross Section
Model H Recessed Sprinkler Figure 4 - Universal Wrench
(Part #1122) Figure 5 - Recessed
Escutcheon Tool
(Part #10654000)
OBSOLETE
SPRINKLER FINISH
Temperature Frame Natural Chrome Polyester
Rating Color Code Brass Plated Coated
165°F/74°C Unpainted
212°F/100°C White
Table 1 - Laboratory Listings and Approvals
Notes:
1. Listed by Underwriters Laboratories, Inc.
2. Listed by Underwriters' Laboratories of Canada.
3. Approved by Factory Mutual Research Corporation.
4. Approved by the City of New York under BSA 375-75-SA
Design
Criteria
The Model H Recessed Pendent Sprinklers are UL, ULC Listed and MEA Approved for use in accordance with current NFPA
standards. The Recessed Pendent Sprinklers are only listed with the Series A/H Recessed Escutcheon Assemblies.
The Model H Recessed Pendent Sprinklers are FM Approved for use in accordance with the FM Loss Prevention Data
Sheets. The Recessed Pendent Sprinklers are only listed with the Series A/H Recessed Escutcheon Assemblies.
The Model H Recessed Pendent Sprinklers are availabe with a two types of support cups, one that accepts a push-on
escutcheon and one that accepts a threaded escutcheons. The recessed escutcheons are manufactured out of a metal or
plastic material that has been specifficaly tested and listed for use with the Model H Recessed Pendent Sprinklers. The
plastic recessed escutcheon is only listed for use with the push-on support cup assembly.
Do not install the Model H Recessed Pendent Sprinklers in ceilings which have positive pressure in the space above.
The Model H Recessed Pendent
Sprinklers
must be installed in accor-
dance with the following instructions.
NOTES
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7 to
14 ft.lbs. (9,5 to 19,0 Nm). A maximum
of 21 ft.lbs. (28,5 Nm) of torque is to be
used to install 1/2 inch NPT sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.
Do not attempt to make up for insuffi-
cient adjustment in the escutcheon plate
by under- or overtightening the sprin-
kler. Readjust the position of the
sprinkler fitting to suit.
Installation Step 1. Pendent sprinklers must be
installed only in the pendent position.
The deflector is to be parallel to the
ceiling, roof, or mounting surface, as
applicable.
Step 2. With pipe thread sealant applied
to the pipe threads, hand tighten the
sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the Universal
Wrench (Ref. Figure 4). With reference
to Figure 1 or 2, the Universal Wrench
is to be applied to the sprinkler wrench
flats only.
After the ceiling has been installed or
the finish coat has been applied, slide
on the Model A/H Recessed Escutcheon
over the Model H Recessed Sprinkler
and push-on or thread on the recessed
escutcheon until its flange comes in
contact with the ceiling.
1,2,3,4 1,2,3,4 1
1,2,3,4 1,2,3,4 1
Installation of the Model A/H Reccesed
Escutcheon can be accomplished by
hand or by using the Recessed
Escutcheon Tool (Ref. Figure 5) and a
telescoping pole assembly. Every
Model H Recessed Escutcheon has 4
tabs on the interior opening of the
escutheon. By matching these tabs to
the corresponding groove on the
Recessed Escutcheon Tool and with
the telescoping pole attached, the
recessed escutcheon can be installed
without the aid of a ladder. Care should
be exercised to assure that the Actuator
Rod and Ejector Springs of the sprinkler
are not dammaged during the installa-
tion of the recessed escutcheon.
OBSOLETE
Printed in U.S.A. 2-01
Flow Control
Tyco Fire

Products
Ordering Information: When
placing an order, indicate the full
product name. Please specify the
quantity, model, style, orifice size,
temperature rating, type of finish or
coating, and sprinkler wrench. Refer
to price list for complete listing of Part
Numbers.
Teflon is a trademark of the DuPont Corp.
Ordering
Information
The Model H Recessed Pendent
Sprinklers
must be maintained and
serviced in accordance with the
following instructions.
NOTES
Absence of an escutcheon which is
used to cover a clearance hole, may
delay the time to operation in a fire
situation.
Before closing a fire protection
system main control valve for
maintenance work on the fire
protection system it controls,
permission to shut down the
affected fire protection systems
must be obtained from the proper
authorities. All personnel who may
be affected by this action must be
notified.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
shipped or stored where their
temperatures will exceed 100°F/
38°C and they must never be
painted, plated, coated or otherwise
altered after leaving the factory.
Modified sprinklers must be
replaced. Sprinklers that have been
exposed to corrosive products of
combustion, but have not operated,
should be replaced if they cannot
be completely cleaned by wiping the
sprinkler with a cloth or by brushing
it with a soft bristle brush.
Care must be exercised to avoid
damage - before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/
slippage, or the like, must be
replaced.
The owner is responsible for the
inspection, testing, and mainte-
nance of their fire protection system
and devices in compliance with this
document, as well as with the
applicable standards of the National
Fire Protection Association (e.g.,
NFPA 25), in addition to the
standards of any other authorities
having jurisdiction. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a
qualified Inspection Service.
Care &
Maintenance Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and
workmanship when paid for and
properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by Tyco Fire
Products. No warranty is given for
products or components manufactured
by companies not affiliated by owner-
ship with Tyco Fire Products or for
products and components which have
been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained,
modified or repaired in accordance
with applicable Standards of the
National Fire Protection Association,
and/or the standards of any other
Authorities Having Jurisdiction.
Materials found by Tyco Fire Products
to be defective shall be either repaired
or replaced, at Tyco Fire Products'
sole option. Tyco Fire Products neither
assumes, nor authorizes any person
to assume for it, any other obligation
in connection with the sale of products
or parts of products. Tyco Fire
Products shall not be responsible for
sprinkler system design errors or
inaccurate or incomplete information
supplied by Buyer or Buyer's repre-
sentatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSE-
QUENTIAL DAMAGES, INCLUDING
BUT NOT LIMITED TO LABOR
CHARGES, REGARDLESS OF
WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE
POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO
FIRE PRODUCTS' LIABILITY EX-
CEED AN AMOUNT EQUAL TO THE
SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS
OR IMPLIED, INCLUDING WARRAN-
TIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR
PURPOSE.
Limited
Warranty
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product CENTRAL LF User manual

Tyco Fire Product

Tyco Fire Product CENTRAL LF User manual

Tyco Fire Product CENTRAL A-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A-1 User manual

Tyco Fire Product Star I-LD-2 User manual

Tyco Fire Product

Tyco Fire Product Star I-LD-2 User manual

Tyco Fire Product Star StarMax S102 User manual

Tyco Fire Product

Tyco Fire Product Star StarMax S102 User manual

Tyco Fire Product Star PH-5 User manual

Tyco Fire Product

Tyco Fire Product Star PH-5 User manual

Tyco Fire Product Star Pulsar S195 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar S195 User manual

Tyco Fire Product Star TFP1 User manual

Tyco Fire Product

Tyco Fire Product Star TFP1 User manual

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product Star Quasar Q User manual

Tyco Fire Product

Tyco Fire Product Star Quasar Q User manual

Tyco Fire Product CENTRAL ELO SW-20 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO SW-20 User manual

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product CENTRAL ESLO User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESLO User manual

Tyco Fire Product STAR SIN S3400 SR User manual

Tyco Fire Product

Tyco Fire Product STAR SIN S3400 SR User manual

Tyco Fire Product CENTRAL ELO-231 GB User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 GB User manual

Tyco Fire Product CENTRAL CC1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL CC1 User manual

Tyco Fire Product STAR S160E User manual

Tyco Fire Product

Tyco Fire Product STAR S160E User manual

Tyco Fire Product Gem F895 User manual

Tyco Fire Product

Tyco Fire Product Gem F895 User manual

Tyco Fire Product S1810 User manual

Tyco Fire Product

Tyco Fire Product S1810 User manual

Tyco Fire Product TY300-B Series User manual

Tyco Fire Product

Tyco Fire Product TY300-B Series User manual

Tyco Fire Product CENTRAL RFII Series User manual

Tyco Fire Product

Tyco Fire Product CENTRAL RFII Series User manual

Tyco Fire Product CENTRAL DS-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL DS-1 User manual

Tyco Fire Product Gem F890 User manual

Tyco Fire Product

Tyco Fire Product Gem F890 User manual

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product Star Pulsar S160QR User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar S160QR User manual

Popular Irrigation System manuals by other brands

Tyco ESFR-1 General description

Tyco

Tyco ESFR-1 General description

HD FIRE PROTECT HD 104 quick start guide

HD FIRE PROTECT

HD FIRE PROTECT HD 104 quick start guide

Gardena smart Sensor 19040 manual

Gardena

Gardena smart Sensor 19040 manual

Eden 96998EDAMZ quick start guide

Eden

Eden 96998EDAMZ quick start guide

Autopot 12Pot System Set-up guidelines

Autopot

Autopot 12Pot System Set-up guidelines

Nelson Traveling Sprinkler Assembly and operating instructions

Nelson

Nelson Traveling Sprinkler Assembly and operating instructions

Gardena OS 140 Operator's manual

Gardena

Gardena OS 140 Operator's manual

Bauer Ecostar 6000 operating manual

Bauer

Bauer Ecostar 6000 operating manual

Autopot SmartPot 8 XL Set-up guidelines

Autopot

Autopot SmartPot 8 XL Set-up guidelines

Rehau Firepex Design and installation guide

Rehau

Rehau Firepex Design and installation guide

Rain Bird 7005 Operation guide

Rain Bird

Rain Bird 7005 Operation guide

Reliable F156 Series Bulletin

Reliable

Reliable F156 Series Bulletin

Seametrics EX90 quick start guide

Seametrics

Seametrics EX90 quick start guide

Reliable F3QR manual

Reliable

Reliable F3QR manual

Senju Sprinkler RC-RES manual

Senju Sprinkler

Senju Sprinkler RC-RES manual

Tyco ESFR-17 quick start guide

Tyco

Tyco ESFR-17 quick start guide