  9. Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product Star Luminous S170 User manual

Standard Response
Standard Coverage
Dry Upright Sprinklers
Luminous™ S170, 5 mm Bulb
GENERAL DESCRIPTION
The Star Luminous S170, 5.6 K-Factor, Standard Re-
sponse Dry Upright Sprinklers are glass bulb automatic
sprinklers designed for use where sprinklers and/or a por-
tion of the connecting piping may be exposed to freezing
temperatures (e.g. sprinkler sprigs into unheated attics).
The Luminous S170, 5 mm Bulb, Dry Upright Sprinklers
are “standard response - standard orifice spray sprin-
klers” and are available in a wide range of operating tem-
peratures and order lengths. The Luminous S170 Sprin-
klers are intended for use in fire sprinkler systems
designed in accordance with the standard installation
rules recognized by the applicable Listing or Approval
agency (e.g., UL Listing is based on NFPA 13 require-
ments). They produce a hemispherical water discharge
pattern below the deflector.
WARNINGS
The Luminous S170 Standard Response, Dry Upright
Sprinklers described herein must be installed and main-
tained in compliance with this document, as well as with
the applicable standards of the National Fire Protection
Association, in addition to the standards of any other
authorities having jurisdiction. Failure to do so may impair
the integrity of these devices.
The owner is responsible for maintaining their fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.
The Luminous S170 Standard Response, Dry Upright
Sprinklers must only be installed in fittings that meet the
requirements of the Design Criteria section.
OPERATION
When the Luminous S170 is in service, water is pre-
vented from entering the assembly by the Plug & O-ring
(Ref. Figure 2) in the Inlet of the Sprinkler. The glass Bulb
contains a fluid which expands when exposed to heat.
When the rated temperature is reached, the fluid expands
sufficiently to shatter the glass Bulb, and the Bulb Seat is
released. The compressed Spring is then able to expand
and push the Water Tube as well as the Guide Tube out-
ward. This action simultaneously pulls inward on the
Yoke, withdrawing the Plug & O-ring from the Inlet, which
then allows the sprinkler to activate and flow water.
TECHNICAL DATA
Approvals
UL and ULC Listed. FM Approved.
NYC Approved (MEA 212-98-E).
(Refer to Table A.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6GPM/psi
1/2 (80,6 LPM/bar1/2)
Temperature Ratings
Pendent: 135°F/57°C to 360°F/182°C (Refer to Table A)
Finishes
Sprinkler: Natural Brass, Chrome Plated, White Polyester
Physical Characteristics (Ref. Figure 1)
The Plug and Inlet are brass, and the O-ring is silicone
rubber. The Casing is galvanized carbon steel. The Frame
is bronze, the Deflector is brass, and the Compression
Screw is bronze. The Water Tube is brass, and the Bulb
Seat, Spring, and Yoke are stainless steel. The Guide
Tube sub-assembly is constructed of stainless steel and
brass.
Patents
U.S.A. Patent Number 5,188,185 is applicable to the Lumi-
nous S170 Dry Upright Sprinklers.
DESIGN CRITERIA
The Luminous S170 Dry Sprinklers are to be installed in
the 1 inch NPT outlet of a malleable iron threaded tee fit-
ting per ANSI B16.3 or cast iron threaded tee fitting per
ANSI B16.4 with the end sprinkler fitting on a branch line
to be plugged as shown in Figure 1.
NOTE
Do not install the Luminous S170 into any other type fit-
SIN S3233
Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500 3-01
1-6.2.31
TYCO FIRE PRODUCTS
OBSOLETE
ting without first consulting the Technical Services Depart-
ment. Failure to use the appropriate fitting may result in:
failure of the sprinkler to properly operate due to binding
of the inlet Plug; or, insufficient engagement of the inlet
pipe threads with consequent leakage.
When Dry Sprinklers are to be used in wet pipe sprinkler
systems protecting areas subject to freezing tempera-
tures (e.g., sprinkler sprigs up into attics), consideration
must be given to the appropriate length of the sprinkler
that will prevent freezing of the water in the connecting
pipes due to conduction. When the temperature surround-
ing the wet pipe sprinkler system is maintained at a mini-
mum temperature of 40°F/4°C, the following are the mini-
mum recommended lengths between the face of the
sprinkler fitting and the outside surface of the protected
area (i.e., length exposed to minimum ambient of
40°F/4°C):
•12 inches (300 mm) when the temperature within the
protected area is -20°F/-29°C
•18 inches (450 mm) when the temperature within the
protected area is -40°F/-40°C
•24 inches (600 mm) when the temperature within the
protected area is -60°F/-51°C
For protected area temperatures between those given
above, the minimum recommended length from the face
of the fitting to the outside of the protected area may be
determined by interpolating between the indicated values.
STAR SPRINKLER
Page 2 1-6.2.31
SPRINKLER FINISH
Temperature
Rating
Bulb
Color Code
Natural
Brass
Chrome
Plated
135°F/57°C
155°F/68°C
175°F/79°C
Red
Yellow
Orange
SIN S3233
“A” Order Length:
5 to 48 inches
(127,0 to 1219,2 mm)
1, 2, 3, 4
Notes:
1. Listed by Underwriters Laboratories, Inc.
2. Listed by Underwriters’ Laboratories of Canada.
3. Approved by Factory Mutual Research Corporation.
4. Approved by the City of New York under MEA 212-98-E.
TABLE A
LUMINOUS S170 STANDARD RESPONSE (SR)
DRY UPRIGHT SPRINKLER
LABORATORY LISTINGS AND APPROVALS
1, 2, 3, 4
1, 2, 3, 4
200°F/93°C
286°F/141°C
Green
Blue
1, 2, 3, 4
1, 2, 3, 4
360°F/182°C Mauve 1, 2, 3, 4
Polyeter
(All
Colors)
1, 2, 4
1, 2, 4
1, 2, 4
1, 2, 4
1, 2, 4
1, 2, 4
FIGURE 1
LUMINOUS S170 SR DRY UPRIGHT SPRINKLER
FIGURE 2
LUMINOUS S170 SR DRY UPRIGHT SPRINKLER
ASSEMBLY
TOP OF
DEFLECTOR
ORDER LENGTH
"A" (UPRIGHT)
FACE OF
SPRINKLER
FITTING
REQUEST)
5" (127.0 mm) MINIMUM
IN 1/4" INCREMENTS
48" (1.22 m) MAXIMUM
1" NPT
(ISO 7/1 ON
SPECIAL
(REFER TO DESIGN
CRITERIA SECTION)
SPRINKLER FITTING
WRENCH
FLAT
WATER
TUBE
BULB
GUIDE
TUBE
VENT HOLE
INSERT
PLUG &
DEFLECTOR
INLET
YOKE
1" NPT
SPRING
FRAME
CASING
BULB
5mm
SEAT
O-RING
OBSOLETE
INSTALLATION
The Luminous S170 must be installed in accordance with
the following instructions:
NOTES
The Luminous S170 must only be installed in fittings that
meet the requirements of the Design Criteria section.
Do not install any bulb type sprinkler if the bulb is
cracked or there is a loss of liquid from the bulb. With the
sprinkler held horizontally, a small air bubble should be
present. The diameter of the air bubble is approximately
1/16 inch (1,6 mm) for the 135°F/57°C rating to 1/8 inch
(3,2 mm) for the 360°F/182°C rating.
A leak tight 1 inch NPT sprinkler joint should be obtained
withatorqueof20to30ft.lbs.(26,8to40,2Nm).Higher
levels of torque may distort the sprinkler inlet with conse-
quent leakage or impairment of the sprinkler.
1. The sprinkler must be installed only in the upright posi-
tion.
2. With pipe thread sealant applied to the pipe threads,
hand tighten the sprinkler into the sprinkler fitting.
3. Wrench tighten the sprinkler by wrenching on the Cas-
ing with a pipe wrench.
CARE AND MAINTENANCE
The Luminous S170 must be maintained and serviced in
accordance with the following instructions:
NOTES
Before closing a fire protection system main control valve
for maintenance work on the fire protection system which
it controls, permission to shut down the affected fire pro-
tection systems must be obtained from the proper authori-
ties and all personnel who may be affected by this action
must be notified.
It is recommended that the piping connected to Dry Sprin-
klers be periodically checked to assure that proper pitch
and drainage is in accordance with the minimum require-
ments of the National Fire Protection Association if the
piping is subject to freezing temperatures.
A Vent Hole is provided in the Bulb Seat (Ref. Figure 2)
to indicate if the Dry Sprinkler is remaining dry. Evidence
of leakage from the Vent Hole is an indication that there
may be weepage past the O-ring seal and, therefore, it is
an indication that the sprinkler needs to be removed for
determining the cause of leakage (e.g. an improper instal-
lation or an ice plug). The fire protection system control
valve must be closed and the system drained before re-
moving the sprinkler.
Sprinklers which are found to be leaking or exhibiting vis-
ible signs of corrosion must be replaced.
Automatic sprinklers must never be shipped or stored
where their temperatures will exceed 100°F/38°C and
they must never be painted, plated, coated or otherwise
altered after leaving the factory. Modified sprinklers must
be replaced. Sprinklers that have been exposed to corro-
sive products of combustion, but have not operated,
should be replaced if they cannot be completely cleaned
by wiping the sprinkler with a cloth or by brushing it with a
soft bristle brush.
Care must be exercised to avoid damage to the sprinklers
— before, during, and after installation. Sprinklers dam-
aged by dropping, striking, wrench twist/slippage, or the
like, must be replaced. Also, replace any sprinkler that
has a cracked bulb or that has lost liquid from its bulb.
(ref. Installation Section Note).
The owner is responsible for the inspection, testing, and
maintenance of their fire protection system and devices in
compliance with this document, as well as with the appli-
cable standards of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the standards of any
other authorities having jurisdiction. The installing contrac-
tor or sprinkler manufacturer should be contacted relative
to any questions.
It is recommended that automatic sprinkler systems be in-
spected, tested, and maintained by a qualified Inspection
Service.
STAR SPRINKLER
1-6.2.31 Page 3
OBSOLETE
LIMITED WARRANTY
Products manufactured by Tyco Fire Products are war-
ranted solely to the original Buyer for ten (10) years
against defects in material and workmanship when paid
for and properly installed and maintained under normal
use and service. This warranty will expire ten (10) years
from date of shipment by Tyco Fire Products. No warranty
is given for products or components manufactured by
companies not affiliated by ownership with Tyco Fire Prod-
ucts or for products and components which have been
subject to misuse, improper installation, corrosion, or
which have not been installed, maintained, modified or re-
paired in accordance with applicable Standards of the Na-
tional Fire Protection Association, and/or the standards of
any other Authorities Having Jurisdiction. Materials found
by Tyco Fire Products to be defective shall be either re-
paired or replaced, at Tyco Fire Products’ sole option.
Tyco Fire Products neither assumes, nor authorizes any
person to assume for it, any other obligation in connec-
tion with the sale of products or parts of products. Tyco
Fire Products shall not be responsible for sprinkler sys-
tem design errors or inaccurate or incomplete information
supplied by Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI-
ABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UN-
DER ANY OTHER LEGAL THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES,
INCLUDING BUT NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT SHALL TYCO FIRE
PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL
TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF
ANY AND ALL OTHER WARRANTIES EXPRESS OR IM-
PLIED, INCLUDING WARRANTIES OF MERCHANT-
ABILITY AND FITNESS FOR A PARTICULAR PUR-
POSE.
ORDERING PROCEDURE
Please Specify:
Luminous S170, 5.6 K-Factor, SR Dry Upright
Sprinkler (#3233)
Dry sprinklers are furnished based upon Order Length
as measured from the top of the deflector to the face of
the sprinkler fitting in which the individual sprinkler is to
be installed. After the measurement is taken, round it to
the nearest 1/4 inch increment.
Please refer to Figure 1 for available “A” Order Lengths.
Refer to Price List for complete listing of Part Numbers
with respect to temperature ratings, finishes, order
lengths, etc.
STAR SPRINKLER
Page 4 1-6.2.31
7071 S. 13th Street • Suite 103
Oak Creek, WI 53154
www.starsprinkler.com
PRINTED IN U.S.A. 3-01
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product Star Galaxy SG-RES User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SG-RES User manual

Tyco Fire Product Star DS-1 Series User manual

Tyco Fire Product

Tyco Fire Product Star DS-1 Series User manual

Tyco Fire Product CENTRAL Royal Flush GB4-EC User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Royal Flush GB4-EC User manual

Tyco Fire Product CENTRAL BV User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV User manual

Tyco Fire Product SIN S1800 User manual

Tyco Fire Product

Tyco Fire Product SIN S1800 User manual

Tyco Fire Product CENTRAL BV-QR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-QR User manual

Tyco Fire Product Gem F892 User manual

Tyco Fire Product

Tyco Fire Product Gem F892 User manual

Tyco Fire Product Gem TFP1 User manual

Tyco Fire Product

Tyco Fire Product Gem TFP1 User manual

Tyco Fire Product CENTRAL GB-LO 17/32 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL GB-LO 17/32 User manual

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product Star Pulsar ESFR-25 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar ESFR-25 User manual

Tyco Fire Product ESFR-22 User manual

Tyco Fire Product

Tyco Fire Product ESFR-22 User manual

Tyco Fire Product CENTRAL GB User manual

Tyco Fire Product

Tyco Fire Product CENTRAL GB User manual

Tyco Fire Product CENTRAL ELO-231 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 User manual

Tyco Fire Product CENTRAL K17-231 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K17-231 User manual

Tyco Fire Product Star Stealth S240 User manual

Tyco Fire Product

Tyco Fire Product Star Stealth S240 User manual

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product Star E User manual

Tyco Fire Product

Tyco Fire Product Star E User manual

Tyco Fire Product CENTRAL H User manual

Tyco Fire Product

Tyco Fire Product CENTRAL H User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product Star S190 User manual

Tyco Fire Product

Tyco Fire Product Star S190 User manual

Tyco Fire Product TY-B Series User manual

Tyco Fire Product

Tyco Fire Product TY-B Series User manual

Popular Irrigation System manuals by other brands

Reliable RFC30 quick start guide

Reliable

Reliable RFC30 quick start guide

Viking HORIZON MIRAGE Technical data

Viking

Viking HORIZON MIRAGE Technical data

Komet KPS operating instructions

Komet

Komet KPS operating instructions

Orbit 58322 Assembly and operating instructions

Orbit

Orbit 58322 Assembly and operating instructions

Orbit Voyager quick start guide

Orbit

Orbit Voyager quick start guide

Johnson Controls tyco WS manual

Johnson Controls

Johnson Controls tyco WS manual

Gardena AquaContour automatic 8133 operating instructions

Gardena

Gardena AquaContour automatic 8133 operating instructions

Reliable F3-80 Dry Pendent manual

Reliable

Reliable F3-80 Dry Pendent manual

Reliable F1FR80VdS Series Bulletin

Reliable

Reliable F1FR80VdS Series Bulletin

Eden PRO TURBO quick start guide

Eden

Eden PRO TURBO quick start guide

SNOWJOE AquaJoe AJ-IS10WB instructions

SNOWJOE

SNOWJOE AquaJoe AJ-IS10WB instructions

Viking FREEDOM VK467 Technical data

Viking

Viking FREEDOM VK467 Technical data

claber MULTIPLA AC 230/24 V LCD user manual

claber

claber MULTIPLA AC 230/24 V LCD user manual

Perrot Hydra M Maintenance and operating instructions

Perrot

Perrot Hydra M Maintenance and operating instructions

Reliable F3-80 Series manual

Reliable

Reliable F3-80 Series manual

Tyco rapidresponse RSV-1 quick start guide

Tyco

Tyco rapidresponse RSV-1 quick start guide

Reliable F1FR LO Series Bulletin

Reliable

Reliable F1FR LO Series Bulletin

Reliable G5-56 Dry manual

Reliable

Reliable G5-56 Dry manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.