Operation: The glass bulb contains a
fluid which expands when exposed to
heat. When the rated temperature is
reached, the fluid expands sufficiently to
shatter the glass bulb, which then allows
the sprinkler to activate & flow water.
WARNING
The K17-231 Upright and Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document, as well as with the
applicable standards of the National Fire
Protection Association, in addition to the
standards of any other authorities
having jurisdiction. Failure to do so may
impair the integrity of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Sprinkler Identification Number
SIN C7151 - Upright
SIN C7251 - Pendent
Approvals
UL & C-UL Listed. FM Approved
(Refer to Tables 1 & 2. The approvals
apply only to the service conditions
indicated in the Design Criteria Section)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
Discharge Coefficient
K = 16.8 GPM/psi1/2 (241,9 LPM/bar1/2)
Temperature Ratings
155o F/68oC, 200oF/93oC, 286°F/141°C
Finishes
Sprinkler: Natural Brass
Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model K17-231
16.8 K-factor
Standard Response
Standard Coverage
Upright & Pendent Glass Bulb Automatic Sprinkler
No. 3-4.0
General
Description
The Central Model K17-231, 16.8
K-factor, Standard Response, Standard
Coverage, Pendent & Upright Sprinklers
are automatic sprinklers of the frangible
bulb type. They are "standard response
- spray sprinklers" which produce a
hemispherical water distribution pattern
below the deflector.
The Model K17-231 Sprinklers are
intended for use in fire sprinkler
systems designed in accordance with
the standard installation rules recog-
nized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on the requirements of the
National Fire Protection Association).
Also, when acceptable to the Authority
Having Jurisdiction, they may be used
with a "Reduced Design Area" as
indicated in Table 2.
The 16.8 K-factor Model K17-231
Sprinklers were subjected to full scale,
high-piled storage, fire tests to qualify
their use in lieu of 5.6 or 8.0 K-factor
standard spray sprinklers for the
protection of high-piled storage.
Higher flow rates can be achieved at
much lower presures with the Model
K17-231 Sprinklers; making their use
highly advantageous in high density
applications, such as the protection of
high-piled storage.
The use of the 16.8 K-factor Model
K17-231Sprinkler also has the advan-
tage of having a specific application
listing, which in some cases can
subsequently reduce the design area
and the overall water demand of a
sprinkler system. Refer to Table 2 for
details.
Technical
Data
CENTRAL K17-231TM 5-01
Standard Spray
Upright &
Pendent
Sprinklers
Physical Characteristics
The Model K17-231 Upright & Pendent
Sprinklers utilize a dezincification
resistant (DZR) bronze frame and a 5
mm bulb. The two-piece button
assembly is brass and copper. The
sprinkler frame orifice is sealed with a
gasketed spring plate (Belleville Seal)
consisting of a beryllium nickel disc
spring that is sealed on both its inside
and outside edges with a TeflonTM
gasket. The compression screw is
bronze, & the deflector is brass.
OBSOLETE
Design
Criteria
Figure 2 - K17-231, Pendent SprinklerFigure 1 - Model K17-231, Upright Sprinkler
Notes:
1. Listed by Underwriters Laboratories, Inc.
2. Listed by Underwriters Laboratories for use in Canada.
3. Approved by Factory Mutual Research Corporation.
The Model K17-231, 16.8 K-factor
Upright and Pendent Sprinklers (Ref.
Table 1) are UL and C-UL Listed as
Standard Response, Standard
Coverage, Spray Sprinklers for use
accordance with current NFPA
standards for the protection of light,
ordinary & extra hazard as well as
storage occupancies. These Area/
Density sprinklers are listed with a
minimum residual (flowing) pressure of
7 psi (0,48 bar).
The Model K17-231, 16.8 K-factor
Upright and Pendent Sprinklers are UL
and C-UL Listed for use, when
acceptable to the Authority Having
Jurisdiction, as "specific application"
sprinklers in accordance with the design
parameters set forth in Table 2 of this
Data Sheet.
The Model K17-231, 16.8 K-factor
Upright Sprinklers (Ref. Table 1) are FM
Approved for use in accordance with
the FM Loss Prevention Data Sheets.
These "Control Mode Area/Density
Sprinklers" are approved with a
minimum residual (flowing) pressure of
7 psi (0,48 bar).
These sprinklers can be used with any
metalic flush or extended escutcheon,
provided the maximum ceiling to top of
sprinkler deflector dimension specified
in NFPA 13 is maintained. These
sprinklers are not listed or approved for
recessed applications.
Table 1 - Laboratory Listings and Approvals
(16.8 K-factor Sprinklers 3/4" NPT)
The Model K17-231 Upright & Pendent
Sprinklers
must be installed in accor-
dance with the following instructions.
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155
°
F/68
°
C to 3/32
inch (2,4 mm) for the 286
°
F/141
°
C
rating.
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). A
SPRINKLER FINISH
Pendent Upright
Temperature Bulb Natural Natural
Rating Color Code Brass Brass
155°F/68°C Red 1,2,3
200°F/93°C Green 1,2,3
286°F/141°C Blue 1,2,3
1,2
1,2
1,2
Installation
maximum of 30 ft.lbs. (40.7 Nm) of
torque is to be used to install 3/4 inch
NPT sprinklers. Higher levels of torque
may distort the sprinkler inlet with
consequent leakage or impairment of
the sprinkler.
Step 1. Upright sprinklers must be
installed only in the upright position and
pendent sprinklers must be installed
only in the pendent position. The
deflector is to be parallel to the ceiling,
roof, or mounting surface, as applicable.
Step 2. With pipe thread sealant applied
to the pipe threads, hand tighten the
sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type 8
Sprinkler Wrench (Ref. Figure 4), With
reference to Figure 1 & 2, the W-Type 8
Sprinkler Wrench is to be applied to the
wrench flats only.
WRENCH
FLAT
ELEVATION VIEW
7/16"
(11,1 mm)
3/4" NPT
2-3/8"
(60,3 mm)
1-3/16"
(30,2 mm)
1-11/16"
(42,9 mm)
1-3/4
(44,5 mm)
WRENCH
FLAT
ELEVATION VIEW
2-3/8"
(60,3 mm)
7/16"
(11,1 mm)
3/4" NPT
OBSOLETE
Temperature Rating: 155°F/68°C
200°F/93°C
286°F/141°C
Hydraulic Design Criteria: The density required is
0.60 gpm/sq. ft. (24,5 mm/min).
Design Area: For wet systems 2000 sq. ft. (186 m2)
and for dry systems use 2600 sq. ft.
(242 m2)
Spacing: Maximum spacing is 100 sq. ft.
(9,3 m2). The maximum distance
between sprinklers is 12'-0" (3,7 m) -
12'-6"(3,8 m) spacing is allowed in
25'-0"(7,6 m) bays. Minimum spacing
is 6'-0" (1,8 m) apart unless
separated by baffles.
Obstructions: NFPA criteria for standard spray
sprinklers.
Type of Storage: Single, double, multiple-row and
portable rack storage (No Solid
Shelves) and solid piled or
palletizied storage.
Commodity: Class I-IV, encapsulated or non-
encapsulated. Group A and B plastics -
cartoned, expanded or unexpanded as
well as exposed, unexpanded.
Maximum Storage Height: 20'-0" (6,1 m)
Clearance: 36" (0,9 m) minimum from deflector
to top of storage.
Max. Ceiling Height in Area of Storage: 25'-0" (7,6 m)
Construction Type: All types - deflector distances per
NFPA 13.
System Type: Wet or dry
Table 2 - K17-231, UL & C-UL Specific Application Guidelines
Figure 3 - Cross Section
Model K17-231, Upright Sprinkler Figure 4 - W-Type 8, Sprinkler Wrench (Part #1068)
SPRINKLER
FRAME
DEFLECTOR
GLASS BULB
OPERATING
ELEMENT
GASKETED
SPRING PLATE
(BELLEVILLE
SEAL)
BUTTON
ASSEMBLY
COMPRESSION
SCREW
WRENCH
RECESS
OBSOLETE
Printed in U.S.A. 5-01
Flow Control
Tyco Fire

Products
Ordering Information: When placing
an order, indicate the full product name.
Please specify the quantity, model,
style, orifice size, temperature rating,
type of finish or coating, and sprinkler
wrench. Refer to price list for complete
listing of Part Numbers.
Teflon is a trademark of the DuPont Corp.
The Model K17-231Upright & Pendent
Sprinklers
must be maintained and
serviced in accordance with the
following instructions.
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system it
controls, permission to shut down the
affected fire protection systems must be
obtained from the proper authorities.
All personnel who may be affected by
this action must be notified.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
shipped or stored where their tempera-
tures will exceed 100°F/38°C and they
must never be painted, plated, coated
or otherwise altered after leaving the
factory. Modified sprinklers must be
replaced. Sprinklers that have been
exposed to corrosive products of
combustion, but have not operated,
should be replaced if they cannot be
completely cleaned by wiping the
sprinkler with a cloth or by brushing it
with a soft bristle brush.
Care must be exercised to avoid
damage - before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb (Ref. Installation Section).
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(e.g., NFPA 25), in addition to the
standards of any other authorities
having jurisdiction. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service.
Care &
Maintenance
Ordering
Information
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed and
maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
Tyco Fire Products. No warranty is
given for products or components
manufactured by companies not
affiliated by ownership with Tyco Fire
Products or for products and compo-
nents which have been subject to
misuse, improper installation, corrosion,
or which have not been installed,
maintained, modified or repaired in
accordance with applicable Standards
of the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Materi-
als found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither
assumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL, INDI-
RECT, SPECIAL OR CONSEQUEN-
TIAL DAMAGES, INCLUDING BUT
NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS'
LIABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR
PURPOSE.
Limited
Warranty
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product Gem F898 User manual

Tyco Fire Product

Tyco Fire Product Gem F898 User manual

Tyco Fire Product Gem G102 User manual

Tyco Fire Product

Tyco Fire Product Gem G102 User manual

Tyco Fire Product CENTRAL BV User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV User manual

Tyco Fire Product Star PH-2 User manual

Tyco Fire Product

Tyco Fire Product Star PH-2 User manual

Tyco Fire Product RAPID RESPONSE LFII Series User manual

Tyco Fire Product

Tyco Fire Product RAPID RESPONSE LFII Series User manual

Tyco Fire Product CENTRAL BV4-QREC User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV4-QREC User manual

Tyco Fire Product Star SuperNova S124 User manual

Tyco Fire Product

Tyco Fire Product Star SuperNova S124 User manual

Tyco Fire Product Gem F895 User manual

Tyco Fire Product

Tyco Fire Product Gem F895 User manual

Tyco Fire Product Gem F892QR User manual

Tyco Fire Product

Tyco Fire Product Gem F892QR User manual

Tyco Fire Product Star E User manual

Tyco Fire Product

Tyco Fire Product Star E User manual

Tyco Fire Product Star Pulsar ESFR-1 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar ESFR-1 User manual

Tyco Fire Product Star LD-2 User manual

Tyco Fire Product

Tyco Fire Product Star LD-2 User manual

Tyco Fire Product Gem F916 User manual

Tyco Fire Product

Tyco Fire Product Gem F916 User manual

Tyco Fire Product CENTRAL ELO-16 GB User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-16 GB User manual

Tyco Fire Product Star StarMax S102 User manual

Tyco Fire Product

Tyco Fire Product Star StarMax S102 User manual

Tyco Fire Product Gem F938 User manual

Tyco Fire Product

Tyco Fire Product Gem F938 User manual

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product TY-B Series User manual

Tyco Fire Product

Tyco Fire Product TY-B Series User manual

Tyco Fire Product Gem F685 User manual

Tyco Fire Product

Tyco Fire Product Gem F685 User manual

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product CENTRAL GB User manual

Tyco Fire Product

Tyco Fire Product CENTRAL GB User manual

Tyco Fire Product CENTRAL Omega EC-20A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Omega EC-20A User manual

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product Star SG-R User manual

Tyco Fire Product

Tyco Fire Product Star SG-R User manual

Popular Irrigation System manuals by other brands

Tyco LFII Series quick start guide

Tyco

Tyco LFII Series quick start guide

Viking VK514 Technical data

Viking

Viking VK514 Technical data

Tyco Rapidresponse LFII Series quick start guide

Tyco

Tyco Rapidresponse LFII Series quick start guide

Viking MICROFAST VK350 Technical data

Viking

Viking MICROFAST VK350 Technical data

Netafim SPINNET Handbook

Netafim

Netafim SPINNET Handbook

Tyco TY2235 Operation

Tyco

Tyco TY2235 Operation

TOOLCRAFT 1561111 operating instructions

TOOLCRAFT

TOOLCRAFT 1561111 operating instructions

Reliable G VELO Pendent Bulletin

Reliable

Reliable G VELO Pendent Bulletin

Viking V-HIP Technical data

Viking

Viking V-HIP Technical data

Gardeners Snip-n-Spray manual

Gardeners

Gardeners Snip-n-Spray manual

AQUAJOE SJI-OMS20-RM instructions

AQUAJOE

AQUAJOE SJI-OMS20-RM instructions

sunjoe AQUAJOE AJ-IST72ZM manual

sunjoe

sunjoe AQUAJOE AJ-IST72ZM manual

Reliable F1FR LO Series Bulletin

Reliable

Reliable F1FR LO Series Bulletin

Gardena T 200 operating instructions

Gardena

Gardena T 200 operating instructions

Hunter Hydrawise HC-1200M owner's manual

Hunter

Hunter Hydrawise HC-1200M owner's manual

Tyco FASTFLEX YN25 manual

Tyco

Tyco FASTFLEX YN25 manual

Tyco EC-5 Series quick start guide

Tyco

Tyco EC-5 Series quick start guide

Orbit 57071 Installation manual & users manual

Orbit

Orbit 57071 Installation manual & users manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.