
3
Step 4. Hand tighten the sprinkler
into the fitting. Use an Omega HEC
sprinkler wrench to tighten the
assembly into the fitting. A leak tight
joint requires the application of only
7-14 ft.-lbs.
(9.5 to 19.0 Nm)
of torque.
A tangential force of 14-28 lbs.
(62.3
to 124.5 N)
delivered through a 6"
(150
mm)
long rachet handle will deliver
adequate torque. Torque levels over
21 ft.-lbs
(28.6 Nm)
may distort the
orifice seal, resulting in leakage.
Step 5. To install the escutcheon
plate, align it with and press it over
the sprinkler body until the outer edge
of the escutcheon meets the
mounting surface.
Do not over or under tighten the
sprinkler to compensate for
inaccurate escutcheon plate
adjustment.
Caution: Special care must be
taken when installing with a CPVC
system. Sprinklers must be installed
after the CPVC manufacturer's
recommended setting time for the
primer and cement to ensure that
neither accumulate within the
sprinkler.
Special care must be taken when
installing with a copper system.
Sprinklers must be installed only after
the inside of the sprinkler nipple and
associated fittings have been wire
brushed to remove any flux. Residual
flux can cause corrosion and in
extreme cases can impair proper
sprinkler operation.
Installation In the event of a thread leak,
remove the unit, apply new pipe joint
compound or tape, and reinstall.
Installation Sequence
Step 1. The unit must be installed in
the horizontal position.
Step 2. The face of the sprinkler
fitting should be installed 5/8"±1/8"
(15.9 mm
±
3.2 mm
) behind the finished
wall line. Adjustments are made via
the adjustable sliding escutcheon
plate to compensate for variations in
the fittings.
Do not use the escutcheon plate to
hold the unit in position. The
sprinkler will function properly, only
when the system piping is anchored
to the building structure. Otherwise,
reaction forces from system initiation
could alter the sprinkler alignment
and disrupt the distribution pattern.
Step 3. Use only a non-hardening
pipe joint compound or Teflon* tape.
Apply to the male threads only.
Model HEC-12EC Sprinklers must
be installed in accordance with
current NFPA 13 Standards.
Deviations from these requirements
and standards or any alteration to the
sprinkler itself will void any warranty
made by Central Sprinkler Company.
In addition, installation must also
meet local government provisions,
codes, and standards as applicable.
The system piping must be properly
sized to insure the minimum required
flow rate from the sprinkler.
Prior to installation, check for
proper model, style, orifice size, and
temperature rating. Install sprinklers
after the piping is in place to avoid
mechanical damage; replace any
damaged unit. Wet pipe systems
must be protected from freezing.
Upon completion of the installation,
the system must be tested per
recognized standards.
Design
Data
Coverage Area Minimum "A"
Width Throw Flow Deflector Distance Temperature
(pressure) Below Ceiling Rating
16' x 16' 26 gpm (21.6 psi) 4" - 12" 145oF/63oC;160oF/71oC
(4.9m) (4.9m) 98.5 Lpm (1.5 bar) (101.6 - 304.8 mm)
16' x 18' 29 gpm (26.8 psi) 4" - 6" 145oF/63oC
(4.9m) (5.5m) 109.9 Lpm (1.8 bar) (101.6 - 152.4 mm)
16' x 18' 30 gpm (28.7 psi) 4" - 12" 145oF/63oC
(4.9m) (5.5m) 113.7 Lpm (2.0 bar) (101.6 - 304.8 mm)
Care &
Maintenance
Sprinklers must be handled
carefully. They must not be
transported or stored where ambient
temperatures may exceed 100°F/
38°C. For best results, store them in
a cool, dry location in the original
shipping package.
Do not install sprinklers that have
been dropped or visibly damaged.
Sprinklers must never be painted,
coated, plated, or altered in any other
way from manufactured condition or
they may not function properly. Any
* Teflon is a trademark of the DuPont Corp.
Design Requirements — Extended Coverage Quick Response Applications
In Extended Coverage Quick Response Applications, the Model HEC-12EC Sprinklers
are listed for installation in light hazard occupancies only.
Coverage Area Minimum "A"
Width Throw Flow Deflector Distance Temperature
(pressure) Below Ceiling Rating
16' x 16' 29 gpm (26.8 psi) 4" - 6" 160oF/71oC
(4.9m) (4.9m) 109.9 Lpm (1.8 bar) (101.6 - 152.4 mm)
16' x 18' 30 gpm (28.7 psi) 4" - 12" 160oF/71oC
(4.9m) (5.5m) 113.7 Lpm (2.0 bar) (101.6 - 304.8 mm)
16' x 20' 32 gpm (32.7 psi) 4" - 6" 160oF/71oC
(4.9m) (6.1m) 121.3 Lpm (2.3 bar) (101.6 - 152.4 mm)
Design Requirements — Extended Coverage Applications
In Extended Coverage Applications, the Model HEC-12EC Sprinklers are listed for
installation in light hazard occupancies only.