manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco Fire Product
  6. •
  7. Irrigation System
  8. •
  9. Tyco Fire Product CENTRAL ELO-231 BV User manual

Tyco Fire Product CENTRAL ELO-231 BV User manual

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product CENTRAL EC-25 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL EC-25 User manual

Tyco Fire Product Gem AQUARIUS F990 User manual

Tyco Fire Product

Tyco Fire Product Gem AQUARIUS F990 User manual

Tyco Fire Product Star Luminous S176 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S176 User manual

Tyco Fire Product Star SG S180 User manual

Tyco Fire Product

Tyco Fire Product Star SG S180 User manual

Tyco Fire Product CENTRAL Omega EC-20A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Omega EC-20A User manual

Tyco Fire Product TY300-FRB User manual

Tyco Fire Product

Tyco Fire Product TY300-FRB User manual

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product CENTRAL ELO SW-20 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO SW-20 User manual

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product CENTRAL LF User manual

Tyco Fire Product

Tyco Fire Product CENTRAL LF User manual

Tyco Fire Product CENTRAL B User manual

Tyco Fire Product

Tyco Fire Product CENTRAL B User manual

Tyco Fire Product CC1 User manual

Tyco Fire Product

Tyco Fire Product CC1 User manual

Tyco Fire Product CENTRAL Omega HEC-12EC User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Omega HEC-12EC User manual

Tyco Fire Product Gem DS-1 User manual

Tyco Fire Product

Tyco Fire Product Gem DS-1 User manual

Tyco Fire Product CENTRAL K17-231 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K17-231 User manual

Tyco Fire Product Gem G102 User manual

Tyco Fire Product

Tyco Fire Product Gem G102 User manual

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product CENTRAL K11 ECLH User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K11 ECLH User manual

Tyco Fire Product CENTRAL ELO-231 BVQR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 BVQR User manual

Tyco Fire Product CENTRAL WS User manual

Tyco Fire Product

Tyco Fire Product CENTRAL WS User manual

Tyco Fire Product CENTRAL H-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL H-1 User manual

Tyco Fire Product CENTRAL 3 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL 3 User manual

Popular Irrigation System manuals by other brands

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Reliable F1FR-300 quick start guide

Reliable

Reliable F1FR-300 quick start guide

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Tyco TY-L Series quick start guide

Tyco

Tyco TY-L Series quick start guide

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

Victaulic

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

corrosive atmospheres. Consequently, it is
recommended that the end user be
consulted with respect to the suitability of
these corrosion resistant coatings for any
given corrosive environment. The effects
of ambient temperature, concentration of
chemicals & gas/chemical velocity, should
be considered, as a minimum, along with
the corrosive nature of the chemical to
which the sprinklers will be exposed.
Operation: The glass bulb contains a fluid
which expands when exposed to heat.
When the rated temperature is reached,
the fluid expands sufficiently to shatter the
glass bulb, which then allows the sprinkler
to activate & flow water.
WARNING
The ELO-231 BV Upright and Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document, as well as with the
applicable standards of the National Fire
Protection Association, in addition to the
standards of any other authorities having
jurisdiction. Failure to do so may impair the
integrity of these devices.
The owner is responsible for maintaining
their fire protection system and devices in
proper operating condition. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
Sprinkler Identification Number
SIN C5151 - Upright
SIN C5251 - Pendent
SIN C5851 - Upright (1/2" NPT)
Approvals
UL & C-UL Listed. FM & NYC Approved
(Refer to Tables 1 & 2. The approvals
apply only to the service conditions
indicated in the Design Criteria Section)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1/2 inch NPT (Upright only)
3/4 inch NPT
Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model ELO-231 BV
11.2 K-factor
Standard Response
Standard Coverage
Upright & Pendent Glass Bulb Automatic Sprinkler
No. 3-8.0
General
Description
The Central Model ELO-231BV,
11.2 K-factor, Standard Response,
Standard Coverage, Pendent & Upright
Sprinklers are automatic sprinklers of the
frangible bulb type. They are "standard
response - spray sprinklers" which
produce a hemispherical water distribution
pattern below the deflector.
The Model ELO-231 BV Sprinklers are
intended for use in fire sprinkler systems
designed in accordance with the standard
installation rules recognized by the
applicable Listing or Approval agency
(e.g., UL Listing is based on the require-
ments of the National Fire Protection
Association). Also, when acceptable to the
Authority Having Jurisdiction, they may be
used with a "Reduced Design Area" as
indicated in Table 2.
The 11.2 K-factor Model ELO-231 BV
Sprinklers were subjected to full scale,
high-piled storage, fire tests to qualify their
use in lieu of 5.6 or 8.0 K-factor standard
spray sprinklers for the protection of high-
piled storage.
Higher flow rates can be achieved at
much lower presures with the Model
ELO-231 BV Sprinklers; making their use
highly advantageous in high density
applications, such as the protection of
high-piled storage.
The use of the 11.2 K-factor Model
ELO-231BV Sprinkler also has the
advantage of having a specific application
listing, which in some cases can subse-
quently reduce the design area and the
overall water demand of a sprinkler
system. Refer to Table 2 for details.
Wax, lead, or polyester coatings can be
used to extend the life of the copper alloy
components used in Model ELO-231 BV
Sprinklers beyond that which would
otherwise be obtained when exposed to
corrosive atmospheres. Although wax,
lead, and polyester coated sprinklers have
passed the standard corrosion tests of the
applicable approval agencies, the testing
is not representative of all possible
Technical
Data
CENTRAL ELO-231 BV 2-01
Standard Spray
Upright &
Pendent
Sprinklers
Discharge Coefficient
K = 11.2 GPM/psi1/2 (161,39 LPM/bar1/2)
Temperature Ratings
155o F/68oC, 200oF/93oC, 286°F/141°C
Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass
Corrosion Resistant Coatings
White Polyester (UL only)
Wax, Lead & Wax-over-Lead (FM only)
Head Guard & Water Shield:
G-2 (Guard) - Up & Pend.
WSG-2 (Guard & Shield) - Up
WS-2 (Shield) - Pendent
(See Data Sheet 3-11.0 for details)
Physical Characteristics
The Model ELO-231 BV Upright &
Pendent Sprinklers utilize a dezincification
resistant (DZR) bronze frame and a 5 mm
bulb. The two-piece button assembly is
brass and copper. The sprinkler frame
orifice is sealed with a gasketed spring
plate (Belleville Seal) consisting of a
beryllium nickel disc spring that is sealed
on both its inside and outside edges with a
TeflonTM gasket. The compression screw
is bronze, & the deflector is brass.
OBSOLETE
Temperature Rating: 155°F/68°C
200°F/93°C
286°F/141°C
Hydraulic Design Criteria: The density required is
0.60 gpm/sq. ft. (24,5 mm/min).
Design Area: For wet systems 2000 sq. ft. (186 m2)
and for dry systems use 2600 sq. ft.
(242 m2)
Spacing: Maximum spacing is 100 sq. ft.
(9,3 m2). The maximum distance
between sprinklers is 12'-0" (3,7 m) -
12'-6"(3,8 m) spacing is allowed in
25'-0"(7,6 m) bays. Minimum spacing
is 6'-0" (1,8 m) apart unless
separated by baffles.
Obstructions: NFPA criteria for standard spray
sprinklers.
Type of Storage: Single, double, multiple-row and
portable rack storage (No Solid
Shelves) and solid piled or
palletizied storage.
Commodity: Class I-IV, encapsulated or non-
encapsulated. Group A and B plastics -
cartoned, expanded or unexpanded as
well as exposed, unexpanded.
Maximum Storage Height: 20'-0" (6,1 m)
Clearance: 36" (0,9 m) minimum from deflector
to top of storage.
Max. Ceiling Height in Area of Storage: 25'-0" (7,6 m)
Construction Type: All types - deflector distances per
NFPA 13.
System Type: Wet or dry
Table 2 - ELO-231 BV, UL & ULC Specific Application Guidelines
Figure 2 - ELO-231 BV, Pendent SprinklerFigure 1 - Model ELO-231 BV, Upright Sprinkler
1. Listed by Underwriters Laboratories, Inc.
2. Listed by Underwriters Laboratories for use in Canada.
3. Approved by Factory Mutual Research Corporation.
Table 1 - Laboratory Listings and Approvals (11.2 K-factor Sprinklers with 1/2" or 3/4" NPT)
Notes:
4. Approved by Factory Mutual Research Corporation for
maximum 150°F/68°C ambient temperatures.
5. Approved by the City of New York under MEA 466-92-E Vol II.
* Upright Only
CENTRAL
1-7/8
(47,6 mm)
WRENCH
FLAT
ELEVATION VIEW
2-13/16"
(71,4 mm)
7/16"
(11,1 mm)
1/2" or
3/4" NPT
WRENCH
FLAT
ELEVATION VIEW
7/16"
(11,1 mm)
3/4" NPT
2-7/8"
(73,0 mm)
1-3/16"
(30,2 mm)
1-11/16"
(42,9 mm)
SPRINKLER FINISH
Pendent and Upright
Temperature Bulb Natural Chrome Polyester Lead Wax Wax Over
Rating Color Code Brass Plated Coated Coated Coated Lead Coated
155°F/68°C Red
200°F/93°C Green
286°F/141°C Blue
1,2,3,5 1,2,3,5 1,2,3*,5 3 3 3
1,2,3,5 1,2,3,5 1,2,3*,5 3 3 3
1,2,3,5 1,2,3,5 1,2,3*,5 3 4 4
OBSOLETE
Design
Criteria
Figure 3 - Cross Section
Model ELO-231 BV, Upright Sprinkler Figure 4 - W-Type 3, Sprinkler Wrench (Part #1073)
The Model ELO-231 BV, 11.2 K-factor
Upright and Pendent Sprinklers (Ref.
Table 1) are UL and C-UL Listed and
NYC Approved (MEA 466-92-E Vol II) as
Standard Response, Standard Coverage,
Spray Sprinklers for use accordance with
current NFPA standards for the protection
of light, ordinary & extra hazard as well as
storage occupancies. These Area/Density
sprinklers are listed with a minimum
residual (flowing) pressure of 7 psi (0,5
bar) for non-storage occupancies and 10
psi (0,7 bar) for storage occupancies.
The Model ELO-231 BV, 11.2 K-factor
Upright and Pendent Sprinklers are UL
and C-UL Listed for use, when acceptable
to the Authority Having Jurisdiction, as
"specific application" sprinklers in
accordance with the design parameters
set forth in Table 2 of this Data Sheet.
The Model ELO-231BV, 11.2 K-factor
Upright and Pendent Sprinklers (Ref.
Table 1) are FM Approved for use in
accordance with the FM Loss Prevention
Data Sheets. These "Control Mode Area/
Density Sprinklers" are approved with a
minimum residual (flowing) pressure of 10
psi (0,7 bar).
These sprinklers can be used with any
metalic flush or extended escutcheon,
provided the maximum ceiling to top of
sprinkler deflector dimension specified in
NFPA 13 is maintained. These sprinklers
are not listed or approved for recessed
applications.
NOTE
Inquiries concerning the appropriateness
of polyester coated sprinklers for a given
corrosive environment should be
submitted to the attention of the Technical
Services Department. Polyester coated
sprinklers are not suitable for use in open
sprinkler applications.
The Model ELO-231 BV Upright &
Pendent Sprinklers
must be installed in
accordance with the following instructions.
NOTES
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of liquid
from the bulb. With the sprinkler held
horizontally, a small air bubble should be
present. The diameter of the air bubble is
approximately 1/16 inch (1,6 mm) for the
155
°
F/68
°
C to 3/32 inch (2,4 mm) for the
286
°
F/141
°
C rating.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7 to
14 ft.lbs. (9,5 to 19,0 Nm). A maximum of
21 ft.lbs. (28,5 Nm) of torque is to be used
to install 1/2 inch NPT sprinklers. A leak
tight 3/4 inch NPT sprinkler joint should be
obtained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of
30 ft.lbs. (40.7 Nm) of torque is to be used
to install 3/4 inch NPT sprinklers. Higher
levels of torque may distort the sprinkler
inlet with consequent leakage or impair-
ment of the sprinkler.
Step 1. Upright sprinklers must be
installed only in the upright position and
pendent sprinklers must be installed only
in the pendent position. The deflector is to
be parallel to the ceiling, roof, or mounting
surface, as applicable.
Step 2. With pipe thread sealant applied
to the pipe threads, hand tighten the
sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type 3
Sprinkler Wrench (Ref. Figure 4), except
that an 8 or 10 inch adjustable Crescent
wrench is to be used for wax coated
sprinklers. With reference to Figure 1 & 2,
both the W-Type 3 Sprinkler Wrench and
the adjustable Crescent wrench are to be
applied to the wrench flats only.
When installing wax coated sprinklers with
the adjustable Crescent wrench, addi-
tional care needs to be exercised to
SPRINKLER
FRAME
DEFLECTOR
GLASS BULB
OPERATING
ELEMENT
GASKETED
SPRING PLATE
(BELLEVILLE
SEAL)
BUTTON
ASSEMBLY
COMPRESSION
SCREW
Installation
prevent damage to the wax coating on the
sprinkler wrench flats or frame arms and,
consequently, exposure of bare metal to
the corrosive environment. The jaws of the
wrench should be opened sufficiently wide
to pass over the wrench flats without
damaging the wax coating. Before wrench
tightening the sprinkler, the jaws of the
wrench are to be adjusted to just contact
the sprinkler wrench flats. After wrench
tightening the sprinkler, loosen the wrench
jaws before removing the wrench.
After installation, the sprinkler wrench flats
and frame arms must be inspected and
the wax coating retouched (repaired)
whenever the coating has been damaged
and bare metal is exposed. The wax
coating on the wrench flats can be
retouched by gently applying a heated 1/8
inch diameter steel rod to the areas of wax
that have been damaged, to smooth it
back over areas where bare metal is
exposed.
NOTES
Only retouching of the wax coating applied
to the wrench flats and frame arms is
permitted, and the retouching is to be
performed only at the time of the initial
sprinkler installation.
The steel rod should be heated only to the
point at which it can begin to melt the wax,
and appropriate precautions need to be
taken, when handling the heated rod, in
order to prevent the installer from being
burned.
If attempts to retouch the wax coating with
complete coverage are unsuccessful,
additional wax can be ordered in the form
of a wax block. Care should be exercised
to assure that the proper rated tempera-
ture wax block is ordered. Only the
correct temperature wax is to be used,
and retouching of wrench flats and frame
arms is only permitted at the time of initial
sprinkler installation. With the steel rod
heated as previously described, touch the
rod to the area requiring additional wax
with the rod angled downward, and then
touch a portion of the wax block to the rod
approximately one-half inch away from the
area requiring retouching. The wax will
melt and run down onto the sprinkler.
OBSOLETE
Printed in U.S.A. 2-01
Flow Control
Tyco Fire

Products
Ordering Information: When placing
an order, indicate the full product
name. Please specify the quantity,
model, style, orifice size, temperature
rating, type of finish or coating, and
sprinkler wrench. Refer to price list for
complete listing of Part Numbers.
Teflon is a trademark of the DuPont Corp.
The Model ELO-231BV Upright &
Pendent Sprinklers
must be main-
tained and serviced in accordance with
the following instructions.
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system it
controls, permission to shut down the
affected fire protection systems must be
obtained from the proper authorities.
All personnel who may be affected by
this action must be notified.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
shipped or stored where their tempera-
tures will exceed 100°F/38°C and they
must never be painted, plated, coated
or otherwise altered after leaving the
factory. Modified sprinklers must be
replaced. Sprinklers that have been
exposed to corrosive products of
combustion, but have not operated,
should be replaced if they cannot be
completely cleaned by wiping the
sprinkler with a cloth or by brushing it
with a soft bristle brush.
Care must be exercised to avoid
damage - before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb (Ref. Installation Section).
Frequent visual inspections are
recommended to be initially performed
for wax, lead, and/or polyester coated
sprinklers, after the installation has
been completed, to verify the integrity
of the wax, lead, and/or polyester
coating. Thereafter, annual inspections
per NFPA 25 should suffice; however,
instead of inspecting from the floor
level, a random sampling of close-up
visual inspections should be made, so
as to better determine the exact
sprinkler condition and the long term
integrity of the wax, lead, and/or
polyester coating, as it may be affected
by the corrosive conditions present.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(e.g., NFPA 25), in addition to the
standards of any other authorities
having jurisdiction. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
Care &
Maintenance
Ordering
Information
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed and
maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
Tyco Fire Products. No warranty is
given for products or components
manufactured by companies not
affiliated by ownership with Tyco Fire
Products or for products and compo-
nents which have been subject to
misuse, improper installation, corrosion,
or which have not been installed,
maintained, modified or repaired in
accordance with applicable Standards
of the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Materi-
als found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither
assumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL, INDI-
RECT, SPECIAL OR CONSEQUEN-
TIAL DAMAGES, INCLUDING BUT
NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS'
LIABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR
PURPOSE.
Limited
Warranty
OBSOLETE