manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco Fire Product
  6. •
  7. Irrigation System
  8. •
  9. Tyco Fire Product CENTRAL Omega Prohibitor QR User manual

Tyco Fire Product CENTRAL Omega Prohibitor QR User manual

This manual suits for next models

1

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product Gem F917 User manual

Tyco Fire Product

Tyco Fire Product Gem F917 User manual

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product CENTRAL ESFR-25 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-25 User manual

Tyco Fire Product Star Stealth S112 User manual

Tyco Fire Product

Tyco Fire Product Star Stealth S112 User manual

Tyco Fire Product Gem F916 User manual

Tyco Fire Product

Tyco Fire Product Gem F916 User manual

Tyco Fire Product CENTRAL BV4 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV4 User manual

Tyco Fire Product TY300-FRB User manual

Tyco Fire Product

Tyco Fire Product TY300-FRB User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product Gem F890 User manual

Tyco Fire Product

Tyco Fire Product Gem F890 User manual

Tyco Fire Product CENTRAL GB User manual

Tyco Fire Product

Tyco Fire Product CENTRAL GB User manual

Tyco Fire Product CENTRAL B User manual

Tyco Fire Product

Tyco Fire Product CENTRAL B User manual

Tyco Fire Product Star SuperNova S126 User manual

Tyco Fire Product

Tyco Fire Product Star SuperNova S126 User manual

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product Star Galaxy SG User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SG User manual

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product Star Pulsar ESFR-25 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar ESFR-25 User manual

Tyco Fire Product Star Celeste S150 User manual

Tyco Fire Product

Tyco Fire Product Star Celeste S150 User manual

Tyco Fire Product CENTRAL ELO-16 GB FR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-16 GB FR User manual

Tyco Fire Product Star TFP1 User manual

Tyco Fire Product

Tyco Fire Product Star TFP1 User manual

Tyco Fire Product Gem F892 User manual

Tyco Fire Product

Tyco Fire Product Gem F892 User manual

Tyco Fire Product CENTRAL 3 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL 3 User manual

Tyco Fire Product CENTRAL ELOC User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELOC User manual

Tyco Fire Product Star Luminous S176 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S176 User manual

Popular Irrigation System manuals by other brands

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Reliable F1FR-300 quick start guide

Reliable

Reliable F1FR-300 quick start guide

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Tyco TY-L Series quick start guide

Tyco

Tyco TY-L Series quick start guide

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

Victaulic

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

2-98
PRO-QR
Omega
Prohibitor™QR
Institutional Pendent & Sidewall
Automatic Sprinklers
Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Product
Description
The Omega Prohibitor™ QR series
of automatic sprinklers have been
specifically designed for use in
institutional occupancies, such as
correctional facilities and mental health
facilities, where the occupants may
attempt to employ the fire sprinklers for
the purpose of self-inflicted injury.
Both pendent and horizontal sidewall
styles of Prohibitor™ QR sprinklers are
recessed into the mounting surface.
Only a small portion of the heat
collecting fin assembly and the tip of
the deflector on the horizontal sidewall
project into the protected space. The
fin assembly has an average break-
away load of 68 lbs. (30.8 kg), and a
maximum break-away load of 85 lbs.
(38.6 kg) Unlike other institutional
sprinklers, the escutcheon plate and
optional closure plates are firmly
attached to the recessed sprinkler body
with tamper resistant retaining screws.
The Omega Prohibitor™ QR
sprinklers are designed with an
aesthetically pleasing, low profile
silhouette. They operate five to six
times faster than standard sprinklers
and offer a high degree of protection
for human life. They feature a spray
pattern that has been shown to be
effective in the control or
extinguishment of fire.
The Model C-1A PRO QR is a
pendent style sprinkler Listed for quick
response applications. The Model
HEC-12 PRO QR is a horizontal
sidewall sprinkler Listed for quick
response sidewall applications with the
deflector positioned 4"(101.6 mm) to
12"(304.8mm) below the ceiling.
For all Models of Prohibitor™ QR
sprinklers, an optional 41⁄2" diameter x
1⁄8" (114.3 mm x 3.2 mm) thick security
closure plate is available for use where
additional security is warranted. The
security closure plate fits between the
base of the escutcheon and the
mounting surface.
For all Models of Prohibitor™ QR
sprinklers, an optional 35⁄8" (92.1mm)
diameter light gauge escutcheon
closure plate is available, for use
where the wall or ceiling penetration is
greater than the recommended 21⁄4"
(57.2 mm) diameter. The escutcheon
closure plate fits between the base of
the escutcheon and the mounting
surface.
For all Models of Prohibitor™ QR
sprinklers, the optional Ident-A-Fire™
feature is available to provide an alarm
signal upon activation of the sprinkler.
Please see the Central Sprinkler
Corporation Ident-A-Fire™ bulletin.
All Prohibitor™ QR sprinklers are
available in two standard finishes,
chrome and brass plated. Their
mating escutcheon and closure plates
are available in three standard fin-
ishes, brass, chrome and white, with
additional special finishes available.
(Note: The Prohibitor™ QR Sprinklers
are also available for standard com-
mercial spacing and response time
with a smaller heat fin design. See the
appropriate Central bulletins.)
Operation: A fusible alloy pellet is
compressed with a bearing disc into a
copper housing by a ball plunger. Heat
is absorbed by the heat collecting fins
and conducted to the alloy pellet. At
the rated temperature the alloy melts,
causing the ball plunger to drop,
freeing balls from the retaining groove.
This movement allows system water
pressure to force the orifice sealing
mechanism and deflector assembly
open. Water is then discharged in a
designed flow pattern.
1⁄2"(12.7mm)
Orifice
Pendent or
Horizontal
Sidewall
Automatic
Sprinklers
No. 6-5.0
Security Closure Plate
(optional)
OBSOLETE
2
Tamper-proof Socket (Part #160-07-00)
Figure 2 — HEC-12 PRO QR
Figure 1 — C-1A PRO QR
Note: The special tamper-proof socket must be used for installation or removal of the tamper-resistant retaining screws.
Decorative Escutcheon Closure
Plate
(optional)
Omega HEC Sprinkler Wrench
(Part #15932000) use for pend. & S/W
Rigid Support Collar with Bolt
(Part #162-018-01)
1/2"
Branch Line Fitting
Rigid Support Collar
With Hex Bolt (To
prevent movement of
the sprinkler away
from the finished
ceiling1" (25 mm) N.P.T.
Steel Nipple
Finished Ceiling
Closure Plate (Optional)
Escutcheon
Tamper-Resistant
Retaining Screw
3/8" (10 mm)
2 3/4" (69.9 mm)
Diamter
Retaining
Collar
3/4" (20 mm)
(12.7 mm)
17/16" ±1/16"
(36.5mm ±1.6mm)
No Closure Plate
1 3/8" ±1/16"
(34.9mm ±1.6mm)
Escutcheon Closure Plate
1 5/16" ±1/16"
(33.3mm ±1.6mm)
Security Closure Plate
2 1/4"
(57.2mm)
Diameter
Hole in Ceiling
2 1/2"
(63.5mm)
Escutcheon
4 1/2"
(114.3mm)
Dia.Security Closure Plate
3 5/8"
(92.1mm)
Dia.Escutcheon Closure Plate
Note: The special tamper-proof socket must be used for installation or removal of the tamper-resistant retaining screws.
Finished Ceiling
Finished Wall
Rigid Support Collar with Hex
Bolt (to prevent movement of
sprinkler head away from
finished wall surface)
Retaining
Collar
Branch
Line Fitting
1" (25 mm) N.P.T. Steel Nipple
1" x 1/2" N.P.T. Reducer
(25 mm x 15 mm)
Escutcheon
Tamper-Resistant
Screw
1/2" (12.7 mm)
Deflector
Distance
4"-12"
( 101.6 mm to 304.8 mm)
3/4"
2 3/4"
Dia.
3/8"
ClosurePlate(Optional)
1/4"±1/16"
(6.4mm±1.6mm)
1 7/16"±1/16"
(36.5mm±1.6mm)
No Closure Plate
1 3/8"±1/16"
(34.9mm±1.6mm)
Escutcheon Closure Plate
1 3/8"±1/16"
(34.9mm±1.6mm)
Security Closure Plate
2 1/4"
(57.2mm)
Diameter
Hole in Wall
2 1/2"
(63.5mm)
Escutcheon
4 1/2"
(114.3mm)
Dia. Security Closure Plate
3 5/8"
(69.9mm)
Dia. Escutcheon Closure Plate
OBSOLETE
3
Design Requirements - Quick Response Commercial Applications
The Model C-1A PRO QR Pendent Sprinklers are listed for standard cover-
age areas and standard flow requirements as specified in the current NFPA 13.
The sprinklers must be installed in the pendent position.
The Model HEC-12 PRO QR Horizontal Sidewall Sprinklers are intended for
standard coverage areas and standard flow and pressure requirements as
specified in the current NFPA 13 for light and ordinary hazard occupancies. The
sprinklers must be installed in the horizontal sidewall position, from 4" to 12"
(101.6 mm to 304.6 mm) below the ceiling.
with the rigid support collar to prevent
movement of the sprinkler away from
the finished surface (see installation
diagrams, page 2).
Step 3. Use only a non-hardening
pipe joint compound or Teflon* tape.
Apply to the male threads only.
Step 4. Hand tighten the sprinkler
into the fitting. Use a Central Omega
HEC sprinkler wrench to tighten the
unit into the fitting. A leak tight joint
requires the application of only 7 to
14 ft.-lbs. (9.5 to 19.0 Nm) of torque.
A tangential force of 14 to 28 lbs.
( 62.3 to 124.5 N) delivered through a
6"(150mm)longhandlewilldeliver
adequate torque. Torque levels over
21 ft.-lbs ( 28.6 Nm) may distort the
orifice seal, resulting in leakage.
Step 5. During installation of the
sprinkler, check the alignment of
retaining collar holes with final
orientation of sprinkler escutcheon.
Step 6. Test the system prior to
installing the ceiling or wall
escutcheons to avoid backing-out and
reinstalling the retaining screws and/
or closure plates.
Step 7. To install the escutcheon
plate (and closure plate if applicable),
align it (them) with and press it (them)
over the sprinkler body until the outer
edge of the escutcheon (or closure
plate) meets the mounting surface.
Do not over or under tighten the
sprinkler to compensate for
inaccurate escutcheon plate
adjustment.
Step 8. Install the tamper resistant
retaining screws through the
escutcheon and into the retaining
*Teflon is a trademark of the DuPont Corp.
All Prohibitor™ QR sprinklers must
be installed in accordance with
current NFPA 13 and the U.L Listing
requirements described in this
brochure. Deviations from these
requirements and standards, or any
alteration to the sprinkler itself, will
void any warranty made by Central
Sprinkler Corporation. In addition,
installation must also meet local
government provisions, codes, and
standards as applicable.
The system piping must be properly
pipe scheduled or hydraulically
calculated to ensure the proper flow
rate at the sprinkler.
Prior to installation, check for
proper model, style, orifice size, and
temperature rating. Install sprinklers
after the piping is in place to avoid
mechanical damage; replace any
Installation
damaged unit. Wet pipe systems
must be protected from freezing.
Upon completion of the installation,
the system must be tested per
recognized standards.
Testing must be performed with the
sprinklers installed, but should be
done prior to installing the ceiling or
wall escutcheons to avoid backing-
out and reinstalling the retaining
screws and/or closure plates.
In the event of a thread leak,
remove the unit, apply new pipe joint
compound or tape, and reinstall.
Installation Sequence
Step 1. The pendent style sprinklers
must be installed in the pendent
position. The sidewall style sprinklers
must be installed in the horizontal
position 4" to 12" (101.6mm to
304.8 mm) below ceiling.
Step 2. Install the steel nipple into
the branch line fitting, then slide the
rigid support collar over the nipple
prior to installing the 1" x 1⁄2" (25 mm x
15mm) NPT reducer. The face of the
sprinkler fitting should be installed:
(a) 17⁄16" ±1⁄16" behind the finished
wall or ceiling line, if no closure
plate is utilized. (36.5 mm
±1.6 mm)
(b) 13⁄8" ±1⁄16" behind the finished
wall or ceiling line, if the light-
gauge, decorative escutcheon
closure plate is utilized. (34.9
mm ±1.6 mm)
(c) 15⁄16" ±1⁄16" behind the finished
wall or ceiling line, if the
security closure plate is
utilized( 33.3 mm ±1.6 mm)
The sprinkler nipple may be fitted
Model: C-1A PRO QR Pendent
HEC-12 PRO QR
Horizontal Sidewall
Orifice Size: 1⁄2"
(12.7 mm)
K Factor:
C-1A PRO QR: 5.6
(80.8 metric)
HEC-12 PRO QR: 5.6
(80.8 metric)
Thread Size: 1⁄2"
(15 mm)
N.P.T.
Temperature Rating: 160°F/71°C
Approvals: U.L., U.L.C.,
MEA (46-92-E Vol. III)
MaximumWorkingPressure:
175psi(12.1bar)
Factory Hydro Test:
100% at 500 psi (34.5 bar)
StandardFinishes:
Sprinkler: brass, chrome plated
Escutcheon: brass, chrome plated,
and white painted
Escutcheon Closure: brass,
chrome plated,
white painted
Security Closure: chrome plated,
brass plated and
white painted
Length: 23⁄8"
(60.3 mm)
Width: 2"
(50.8 mm)
Weight: 6.8 oz.
(193 grams)
Technical
Data Design
Data
OBSOLETE
©1998 Central Sprinkler Company
Printed in U.S.A.
collar, thereby drawing the
escutcheon (and closure plate) tight
against the mounting surface. The
tamper resistant retaining screws can
only be installed or removed with the
special tamper-proof socket.
Caution: Special care must be taken
when installing with a CPVC system
to ensure that no primer or cement
accumulates within the sprinkler.
Special care must be taken when
installing with a copper system.
Sprinklers must be installed only after
the inside of the sprinkler drop and
associated fittings have been wire
brushed to remove any flux.
Residual flux can cause corrosion
and in extreme cases can impair
proper sprinkler operation.
qualified inspection service. Length
of time between such inspections can
vary due to accessibility, ambient
atmosphere, water supply, and site
activity.
Do not attempt to reassemble or
otherwise reuse a sprinkler that has
operated. Replace any sprinkler
exhibiting corrosion or damage;
always use new sprinklers of the
same type and temperature rating as
replacements.
Because the discharge pattern is
critical to protection of life and
property, nothing should be hung or
attached to the sprinkler unit that
would disrupt the pattern. Such
obstructions must be removed. In the
event that construction has altered
the original configuration, additional
sprinklers may need to be installed to
maintain protection level.
Do not attempt to replace sprinklers
without first removing the fire protec-
tion system from service. Be certain
to secure permission from all
Authori-
ties Having Jurisdiction
, and notify all
personnel who may be affected
during system shutdown. A fire watch
during maintenance periods is a
recommended precaution.
To remove the system from service
mode, first refer to the system
operating guide and valve instruc-
tions. Drain water and relieve
pressure in the pipes. Remove the
existing unit and install the replace-
ment, using only the special sprinkler
wrench. Be certain to match model,
style, orifice, and temperature rating.
A fire protection system that has
been shut off after activation should
be returned to service immediately.
Inspect the entire system for damage
and replace or repair as necessary.
Sprinklers that did not operate but
were subjected to corrosive elements
of combustion or excessive tempera-
tures should be inspected, and
replaced if need be. The
Authority
Having Jurisdiction
will detail mini-
mum replacement requirements and
regulations.
Guarantee: Central Sprinkler
Company will repair and/or replace
any product found to be defective in
material or workmanship within a
period of one year from date of
shipment. Please refer to the current
Price List for further details of the
warranty.
OrderingInformation: When
placing an order, indicate the full
product name. Please specify the
quantity, model number, style, orifice
size,temperaturerating,sprinkler
finish, escutcheon finish, closure
plate(s)andfinish,andsprinkler
wrench.
Forspecialpaintedescutcheon
finishes, it is advisable to provide
quick-drypaintpreferablyin a lacquer
basefinishtoensurepropercolor
duplication. Without such a guide,
CentralSprinklerCompanycannotbe
responsibleforacceptablecolor
matching.
AvailabilityandService: Central
sprinklers, valves, accessories, and
otherproductsareavailable
throughouttheU.S.andCanada,and
internationally,throughanetworkof
CentralSprinklerCompanydistribution
centers. You may write directly to
CentralSprinklerCompanyorcall
(215)362-0700forthedistributor
nearestyou.
Patents: TheOmegaProhibitor™
QRAutomaticSprinklersare protected
underU.S.PatentNo.4,491,182.
Additionalpatentsarepending.
ConversionTable:
1 inch = 25.400 mm
1 foot = 0.3048 m
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 Kpa
=0.0689bar
= 0.0703 kg/cm2
1 U.S. gallon = 3.785 dm3
= 3.785 liters
Conversionsareapproximate.
Ordering
Information
PRO-QR3
Care &
Maintenance
Sprinklers must be handled care-
fully. They must not be transported
or stored where ambient tempera-
tures may exceed 100oF/38oC. For
best results, store them in a cool, dry
location in the original shipping
package.
Do not install sprinklers that have
been dropped or visibly damaged.
Sprinklers must never be painted,
coated, plated, or altered in any other
way from manufactured condition or
they may not function properly. Any
sprinklers altered in such a manner
must be replaced.
The owner is responsible for the
proper working condition of all fire
protection devices and accessories.
The NFPA Standard 25 entitled,
“Inspection, Testing and Maintenance
of Water-Based Fire Protection
Systems”
contains guidelines and
minimum maintenance requirements.
Furthermore, the local
Authority
Having Jurisdiction
may have addi-
tional regulations and requirements
for maintenance, testing, and inspec-
tion that must be obeyed.