General
Description
The Model ESFR-1 Sprinklers (Ref.
Figure 1) are “Early Suppression Fast
Response Sprinklers” having a nomi-
nal K-factor of 14.0. They are suppres-
sion mode sprinklers, and their use is
especially advantageous as a means
of eliminating the use of in-rack sprin-
klers, when protecting high-piled stor-
age.
TheModelESFR-1isprimarilyde-
signed for use with storage of most
encapsulated or non-encapsulated
common materials including cartoned
unexpanded plastics to 35 ft. (10,7 m)
high. In addition, the protection of
some storage arrangements of roll pa-
per and rubber tires can be consid-
ered.
Applications for the Model ESFR-1
Sprinklers are expanding beyond the
current recognized installation stand-
ards. For information regarding re-
search fire tests that may be accept-
able to an Authority Having
Jurisdiction (e.g., flammable liquids,
aerosols, etc.), please contact the
Technical Services Department.
WARNINGS
The Model ESFR-1 Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction (e.g., FM Global). Fail-
ure to do so may impair the integrity of
these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Sprinkler
Identification
Numbers
SIN TY6226 - (Pendent K=14.0)
TY6226 ia a redesignation for C6226,
G8440, aand S8000.
Technical
Data
Approvals
UL and ULC Listed.
FM and LPC Approved.
(UL and ULC Listings, as well as FM
Approvals, only apply to the service
conditions indicated in the Design Cri-
teria section.)
NYC under MEA 356-01-E.
VdS Approved; however, the use of the
ESFR-1 is required to be agreed upon
by the VdS for each application.
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT or ISO 7-R3/4
Discharge Coefficient
K = 14.0 GPM/psi1/2
(201,6 LPM/bar1/2)
Temperature Ratings
165°F/74°C or 214°F/101°C
Finish
Natural Brass
Physical Characteristics
Frame ............. Brass
Deflector............Bronze
Compression Screw . . . . . . . . .
............ StainlessSteel
Hook.............. Monel
Strut.............. Monel
Link Assembly . . . . Solder, Nickel
Button .............Bronze
SealingAssembly...........
. . . . . . Beryllium Nickel w/Teflon*
EjectionSpring ........Inconel
Patents
U.S.A. Patent Numbers 4,580,729
and 4,893,679 may be applicable to
the Model ESFR-1. Other patents are
pending.
Page 1 of 4 TFP318
FEBRUARY, 2002
Model ESFR-1
Early Suppression Fast Response Pendent Sprinklers
14.0 K-factor
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Customer Service/Sales:
Tel: (215) 362-0700 / (800) 523-6512
Fax: (215) 362-5385
TFP318 (3-2.2)
OBSOLETE
Operation
The fusible link assembly is comprised
of two link halves that are joined to-
gether by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate activating the sprinkler and
flowing water.
Design
Criteria
UL AND C-UL LISTING CRITERIA
The Model ESFR-1 (SIN TY6226)
Sprinklers are UL and C-UL Listed as
“Early Suppression Fast Response
Sprinklers” for installation per NFPA 13
or other applicable NFPA standards up
to a maximum ceiling height of 40 ft.
(12,2 m).
FM APPROVAL CRITERIA
The Model ESFR-1 (SIN TY6226)
Sprinklers are FM Approved as “Early
Suppression Fast Response Sprin-
klers” for installation per the applicable
FM Loss Prevention Data Sheets up to
a maximum ceiling height of 45 ft.
(13,7 m).
Installation
The Model ESFR-1 Pendent Sprin-
klers are to be installed in accordance
with the following instructions:
NOTE
Damage to the fusible Link Assembly
during installation can be avoided by
handling the sprinkler by the frame
arms only (i.e., do not apply pressure
to the fusible Link Assembly), and by
using the appropriate sprinkler
wrench. Damaged sprinklers must be
replaced.
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). Higher
levels of torque may distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler.
Step 1. The ESFR-1 Sprinkler must be
installed in the pendent position.
Step 2. With pipe thread sealant ap-
plied, hand tighten the sprinkler into
the sprinkler fitting. Do not apply pres-
sure to the Link Assembly, and handle
the ESFR-1 Sprinkler by the Frame
arms only.
Step 3. Wrench tighten the ESFR-1
Sprinkler using only the W-Type 2
Sprinkler Wrench (Ref. Figure 2) and
by fully engaging (seating) the wrench
on the sprinkler wrench flats.
Step 4. After installation, inspect the
Link Assembly of each ESFR-1 Sprin-
kler for damage. In particular, verify
that the Link Assembly and Hook are
positioned as illustrated in Figure 1,
and that the Link Assembly has not
Page2of4 TFP318
1-Frame
2-Deflector
3-Compression Screw
4-Hook
5-Strut
6-Link Assembly
7-Button
8-Gasketed Spring Plate
9-Ejection Spring
FIGURE 1, MODEL ESFR-1 EARLY SUPPRESSION FAST RESPONSE PENDENT SPRINKLER
* Registered Trademark of DuPont
OBSOLETE
been bent, creased, or forced out of its
normal position in any way.
Damaged sprinklers must be replaced.
Care and
Maintenance
The Model ESFR-1 must be main-
tained and serviced in accordance
with the following instructions:
NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authori-
ties and all personnel who may be
affected by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
shipped or stored where their tempera-
ture will exceed 100°F/38°C and they
must never be painted, plated, coated,
or otherwise altered after leaving the
factory. Modified or over-heated sprin-
klers must be replaced.
Care must be exercised to avoid dam-
age - before, during, and after instal-
lation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage,
or the like, must be replaced.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES,ANDINNOEVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
TFP318 Page 3 of 4
FIGURE 2
W-TYPE 2
SPRINKLER WRENCH
"FITTING SIDE"
FITTING
TOWARDS SPRINKLER
RECESS
WRENCH
OBSOLETE
Ordering
Procedure
When placing an order, indicate the full
product name. Please specify the
Sprinkler Identification Number (SIN),
quantity, and temperature rating. Refer
to the Price List for complete listing of
Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (specify temperature rating),
natural brass, TY6226 Pendent Sprin-
kler, PSN (specify).
165°F/74°C . . . . . . . . . . . . . . . P/N 58-440-1-165
214°F/101°C . . . . . . . . . . . . . . P/N 58-440-1-214
Sprinkler Wrench
Specify: W-Type 2 Sprinkler Wrench,
P/N 56-872-1-001.
Page4of4 TFP318
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product Star StarMax S100 User manual

Tyco Fire Product

Tyco Fire Product Star StarMax S100 User manual

Tyco Fire Product Gem TY-B Series User manual

Tyco Fire Product

Tyco Fire Product Gem TY-B Series User manual

Tyco Fire Product Star S190 User manual

Tyco Fire Product

Tyco Fire Product Star S190 User manual

Tyco Fire Product CENTRAL 3 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL 3 User manual

Tyco Fire Product CENTRAL BV-QR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-QR User manual

Tyco Fire Product Star Stealth S112 User manual

Tyco Fire Product

Tyco Fire Product Star Stealth S112 User manual

Tyco Fire Product CENTRAL GB-LO 17/32 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL GB-LO 17/32 User manual

Tyco Fire Product CENTRAL BV-R1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-R1 User manual

Tyco Fire Product Gem F898 User manual

Tyco Fire Product

Tyco Fire Product Gem F898 User manual

Tyco Fire Product TY-B Series User manual

Tyco Fire Product

Tyco Fire Product TY-B Series User manual

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product SIN S3244 User manual

Tyco Fire Product

Tyco Fire Product SIN S3244 User manual

Tyco Fire Product Star PH-2 User manual

Tyco Fire Product

Tyco Fire Product Star PH-2 User manual

Tyco Fire Product Star Stealth S110 User manual

Tyco Fire Product

Tyco Fire Product Star Stealth S110 User manual

Tyco Fire Product Gem DS-1 User manual

Tyco Fire Product

Tyco Fire Product Gem DS-1 User manual

Tyco Fire Product RAPID RESPONSE LFII Series User manual

Tyco Fire Product

Tyco Fire Product RAPID RESPONSE LFII Series User manual

Tyco Fire Product Gem AQUARIUS F990 User manual

Tyco Fire Product

Tyco Fire Product Gem AQUARIUS F990 User manual

Tyco Fire Product Star LD-2 User manual

Tyco Fire Product

Tyco Fire Product Star LD-2 User manual

Tyco Fire Product Star E User manual

Tyco Fire Product

Tyco Fire Product Star E User manual

Tyco Fire Product Star Luminous S176 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S176 User manual

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product CENTRAL CC1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL CC1 User manual

Tyco Fire Product SIN S3230 User manual

Tyco Fire Product

Tyco Fire Product SIN S3230 User manual

Tyco Fire Product Gem F960/Q-48 User manual

Tyco Fire Product

Tyco Fire Product Gem F960/Q-48 User manual

Popular Irrigation System manuals by other brands

Toro 570Z PRX Series Specifications

Toro

Toro 570Z PRX Series Specifications

Tyco ESFR-22 quick start guide

Tyco

Tyco ESFR-22 quick start guide

DIG 12 Outlet Drip Manifold instruction manual

DIG

DIG 12 Outlet Drip Manifold instruction manual

Irritrol Platinum Sport Instruction guide

Irritrol

Irritrol Platinum Sport Instruction guide

Viking V-SD Technical data

Viking

Viking V-SD Technical data

Tyco Rapidresponse LFII Series manual

Tyco

Tyco Rapidresponse LFII Series manual

Toro FLX34 Series Installation and service instructions

Toro

Toro FLX34 Series Installation and service instructions

Seametrics EX90 quick start guide

Seametrics

Seametrics EX90 quick start guide

Viking FREEDOM VK460 Technical data

Viking

Viking FREEDOM VK460 Technical data

Viking FREEDOM VK466 Technical data

Viking

Viking FREEDOM VK466 Technical data

Fiskars 1023656 Original instructions

Fiskars

Fiskars 1023656 Original instructions

Eden 98063EDAMZ quick start guide

Eden

Eden 98063EDAMZ quick start guide

Coopers Pk 6 G346 Instructions for use

Coopers

Coopers Pk 6 G346 Instructions for use

Compacta International Smartenit RainBee8 5010Z quick start guide

Compacta International

Compacta International Smartenit RainBee8 5010Z quick start guide

Reliable XL Bulletin

Reliable

Reliable XL Bulletin

Johnson Controls tyco EC-8C Series manual

Johnson Controls

Johnson Controls tyco EC-8C Series manual

Senju Sprinkler RC-RES manual

Senju Sprinkler

Senju Sprinkler RC-RES manual

Tyco Ultra K17 quick start guide

Tyco

Tyco Ultra K17 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.