manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco Fire Product
  6. •
  7. Irrigation System
  8. •
  9. Tyco Fire Product Omega HEC-12 RES User manual

Tyco Fire Product Omega HEC-12 RES User manual

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product CENTRAL H User manual

Tyco Fire Product

Tyco Fire Product CENTRAL H User manual

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product CENTRAL Omega R-1M User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Omega R-1M User manual

Tyco Fire Product CENTRAL ELO-231TM User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231TM User manual

Tyco Fire Product CENTRAL DS-2 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL DS-2 User manual

Tyco Fire Product CENTRAL K11 ECOH User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K11 ECOH User manual

Tyco Fire Product CENTRAL BV4 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV4 User manual

Tyco Fire Product Star DS-1 Series User manual

Tyco Fire Product

Tyco Fire Product Star DS-1 Series User manual

Tyco Fire Product Gem F892X User manual

Tyco Fire Product

Tyco Fire Product Gem F892X User manual

Tyco Fire Product EC-HS User manual

Tyco Fire Product

Tyco Fire Product EC-HS User manual

Tyco Fire Product CENTRAL Omega Prohibitor QR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Omega Prohibitor QR User manual

Tyco Fire Product Gem F978 User manual

Tyco Fire Product

Tyco Fire Product Gem F978 User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product Gem TY-B User manual

Tyco Fire Product

Tyco Fire Product Gem TY-B User manual

Tyco Fire Product Star Celeste S140 User manual

Tyco Fire Product

Tyco Fire Product Star Celeste S140 User manual

Tyco Fire Product CENTRAL S176 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL S176 User manual

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product Gem G102 User manual

Tyco Fire Product

Tyco Fire Product Gem G102 User manual

Tyco Fire Product TY-B Series User manual

Tyco Fire Product

Tyco Fire Product TY-B Series User manual

Tyco Fire Product Star SG300 User manual

Tyco Fire Product

Tyco Fire Product Star SG300 User manual

Tyco Fire Product Star E User manual

Tyco Fire Product

Tyco Fire Product Star E User manual

Tyco Fire Product Star Stealth S110 User manual

Tyco Fire Product

Tyco Fire Product Star Stealth S110 User manual

Tyco Fire Product S1810 User manual

Tyco Fire Product

Tyco Fire Product S1810 User manual

Popular Irrigation System manuals by other brands

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Reliable RFC30 LL manual

Reliable

Reliable RFC30 LL manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Product
Description
The Omega Model HEC-12 RES
Horizontal Sidewall Automatic
Sprinkler is an extremely versatile
horizontal sidewall sprinkler. It is a
low profile, aesthetically pleasing,
wall mounted sprinkler that operates
five to six times faster than a
standard sprinkler. It offers a high
degree of protection for human life
and features a spray pattern that has
been shown to be effective in the
control or extinguishment of fire.
The Model HEC-12 RES carries a
Listing* by Underwriters Laboratories
for use as a residential sprinkler that
is Listed for installation 4"-6" below
the ceiling in residential occupancies
in accordance with current NFPA 13,
NFPA 13D and NFPA 13R.
The Model HEC-12 RES is
available in three standard finishes,
chrome plated, brass plated and
white painted. Its mating escutcheon
plate is available in three standard
finishes, chrome plated, brass plated
and white painted, with additional
special finishes available upon
request.
Operation: A fusible alloy pellet is
compressed with a bearing disc into a
copper housing by a ball plunger.
Heat is absorbed by the heat
collecting fins and conducted to the
alloy pellet. At the rated temperature
the alloy melts, causing the ball
plunger to drop, freeing balls from
the retaining groove. This movement
allows system water pressure to
force the orifice sealing mechanism
and deflector assembly open. Water
is then discharged in a designed flow
pattern.
OmegaHEC-12 RES
* For specific listing requirements see the appropriate
information contained in this brochure.
HEC-12 RES
1⁄2"Orifice
Horizontal
Sidewall
Automatic
Sprinkler
Residential
HorizontalSidewallSprinkler
9-94
Model: HEC-12 RES
Style: Horizontal Sidewall
Wrench: Omega Sidewall Wrench
(Part #15932000)
Orifice Size: 1⁄2"
(12.7 mm)
K Factor: 5.6
(80.08)
Thread Size: 1⁄2"
(12.7 mm)
N.P.T.
Temperature Rating: 160°F/71°C
Approvals: U.L., U.L.C., M.E.A.
Maximum Working Pressure: 175 psi
Factory Hydro Test: 100% at 500 psi
Standard Finishes:
Sprinkler: chrome plated, brass
plated, white painted or
off-white
Escutcheon: chrome plated, brass
plated, white painted
or off-white
Length: 23⁄8"
(60.3 mm)
Width: 13⁄8"
(34.9 mm)
Weight: 4.5 oz.
(128 grams)
Technical
Data
No. 1-7.0
(375-75-SA)
OBSOLETE
2
Figure 1
Omega HEC-12 RES Horizontal Sidewall Automatic Sprinkler
1" Supply Pipe
5/8" ±1/8"
1/2"
Finished
Ceiling Line 1" x 1/2" Reducing
Coupling (N.P.T.)
Finished
Wall Line
1"±1/8"
4" to 6"
Note: Use this flange for field
installation. Use Central's Omega
Sidewall Sprinkler Wrench. DO
NOT “WRENCH” DEFLECTOR.
Escutcheon
Face of Coupling
2 1/4" Dia. Max.
2" Dia. Min.
Omega Sidewall Sprinkler Wrench
(Part #15932000)
OBSOLETE
3
Coverage Area Minimum Flow (Pressure) Req'd Temperature
Width (Ft.) Throw (Ft.) Single Sprinkler Two Sprinklers Rating
12 (or less) 12 (or less) 26 gpm (21.6 psi) 18 gpm (10.3 psi) 160oF/71oC
14 14 27 gpm (23.2 psi) 21 gpm (14.1 psi) 160oF/71oC
Design Requirements — Residential Applications
Design
Data
Installation Adjustments are made via the
adjustable sliding escutcheon plate to
compensate for variations in the
fittings.
The sprinkler will function properly,
only when the system piping is
anchored to the building structure.
Otherwise, reaction forces from
system initiation could alter the
sprinkler alignment and disrupt the
distribution pattern.
Step 3. Use only a non-hardening
pipe joint compound or Teflon* tape.
Apply to the male threads only.
Step 4. Hand tighten the sprinkler
into the fitting. Use an Omega
Sidewall Sprinkler Wrench to tighten
the assembly into the fitting. A leak
tight joint requires the application of
only 7-14 ft.-lbs. of torque. A
tangential force of 14-28 lbs.
delivered through a 6" long rachet
handle will deliver adequate torque.
Torque levels over 21 ft.-lbs may
distort the orifice seal, resulting in
leakage.
Step 5. To install the escutcheon
plate, align it with and press it over
the sprinkler body until the outer edge
of the escutcheon meets the
mounting surface.
Do not over or under tighten the
sprinkler to compensate for
inaccurate escutcheon plate
adjustment.
Model HEC-12 RES sprinklers must
be installed in accordance with
current NFPA 13, NFPA 13R or
NFPA 13D. Deviations from these
requirements and standards or any
alteration to the sprinkler itself will
void any warranty made by Central
Sprinkler Company. In addition,
installation must also meet local
government provisions, codes, and
standards as applicable.
The system piping must be properly
sized to ensure the minimum required
flow rate from the sprinkler.
Prior to installation, check for
proper model, style, orifice size, and
temperature rating. Install sprinklers
after the piping is in place to avoid
mechanical damage; replace any
damaged unit. Wet pipe systems
must be protected from freezing.
Upon completion of the installation,
the system must be tested per
recognized standards.
In the event of a thread leak,
remove the unit, apply new pipe joint
compound or tape, and reinstall.
Installation Sequence
Step 1. The unit must be installed in
the horizontal position.
Step 2. The face of the sprinkler
fitting should be installed 1" (±1⁄8")
behind the finished wall line.
Caution: Special care must be
taken when installing with a CPVC
system. Sprinklers must be installed
after the CPVC manufacturer's
recommended setting time for the
primer and cement to ensure that
neither accumulate within the
sprinkler.
Special care must be taken when
installing with a copper system.
Sprinklers must be installed only after
the inside of the sprinkler nipple and
associated fittings have been wire
brushed to remove any flux. Residual
flux can cause corrosion and in
extreme cases can impair proper
sprinkler operation.
* Teflon is a trademark of the DuPont Corp.
Care &
Maintenance
Sprinklers must be handled
carefully. They must not be
transported or stored where ambient
temperatures may exceed 100oF/
38oC. For best results, store them in
a cool, dry location in the original
shipping package.
Do not install sprinklers that have
been dropped or visibly damaged.
Sprinklers must never be painted,
coated, plated, or altered in any other
way from manufactured condition or
they may not function properly. Any
sprinklers altered in such manner
must be replaced.
The owner is responsible for the
proper working condition of all fire
protection devices and accessories.
The NFPA Standard 25 entitled,
“Inspection, Testing and Maintenance
of Water-Based Fire Protection
Systems”
, contains guidelines and
minimum maintenance requirements.
Furthermore, the local
Authority
Having Jurisdiction
may have
additional regulations and
requirements for maintenance,
testing, and inspection that must be
obeyed.
It is advisable to have sprinkler
systems inspected regularly by a
qualified inspection service. Length
of time between such inspections can
vary due to accessibility, ambient
atmosphere, water supply, and site
In residential applications, the Model HEC-12 RES, 160
o
F rated sprinklers are
Listed for installation 4" to 6" below the ceiling.
OBSOLETE
©1994 Central Sprinkler Company
Printed in U.S.A.
Guarantee: Central Sprinkler
Company will repair and/or replace
any product found to be defective in
material or workmanship within a
period of one year from date of
shipment. Please refer to the current
Price List for further details of the
warranty.
Ordering
Information
Ordering Information: When
placing an order, indicate the full
product name. Specify the quantity,
model, style, orifice size, temperature
rating, type of finish, escutcheon plate
finish, and sprinkler wrench.
For special painted escutcheon
finishes, the customer must provide
paint in a quick-drying or lacquer-
base finish to insure proper color
duplication. Without such a guide,
Central Sprinkler Company cannot
be responsible for acceptable color
matching.
Availability and Service: Central
sprinklers, valves, accessories, and
other products are available
throughout the U.S. and Canada, and
internationally, through a network of
Central Sprinkler distribution centers.
You may write directly to Central
Sprinkler Company or call (215) 362-
0700 for the distributor nearest you.
Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 M
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 Kpa
= 0.0689 bar
= 0.0703 kg/cm2
1 U.S. gallon = 3.785 dm3
= 3.785 liters
Conversions are approximate.
activity.
Do not attempt to re-assemble or
otherwise reuse a sprinkler that has
operated. Replace any sprinkler
exhibiting corrosion or damage;
always use new sprinklers of the
same type and temperature rating as
replacements.
Because the discharge pattern is
critical to protection of life and
property, nothing should be hung or
attached to the sprinkler unit that
would disrupt the pattern. Such
obstructions must be removed. In the
event that construction has altered
the original configuration, additional
sprinklers may need to be installed to
maintain the protection level.
Do not attempt to replace sprinklers
without first removing the fire
protection system from service. Be
certain to secure permission from all
authorities having jurisdiction, and
notify all personnel who may be
affected during system shutdown. A
fire watch during maintenance
periods is a recommended
precaution.
To remove the system from service
mode, first refer to the system
operating guide and valve
instructions. Drain water and relieve
pressure in the pipes. Remove the
existing unit and install the
replacement, using only the
recommended sprinkler wrench. Be
certain to match model, style, orifice,
and temperature rating.
HEC-12RES.1