HORIZONTAL SIDEWALL SPRINKLERS
MODEL FR-1 FAST RESPONSE
QR-EC/EC, SOLDER TYPE, 8.0 K-FACTOR, 3/4" NPT**
GENERAL DESCRIPTION
The 8.0 K-Factor (17/32 inch orifice),
Model FR-1 QR-EC/EC Horizontal
Sidewall Sprinklers (Ref. Figure A) are
automatic sprinklers of the “quick re-
sponse” fusible solder type. They are
“extended coverage spray sidewall
sprinklers” intended for use in fire
sprinkler systems designed in accord-
ance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on NFPA 13 require-
ments).
Extended coverage horizontal side-
wall sprinklers with coverage areas up
to 16 ft. x 24 ft. ( 4,9 m x 7,3 m) are
generally used in lieu of pendent and
upright sprinklers because of building
construction or installation economy
considerations. They are designed for
installation along a wall or the side of
a beam and just beneath a smooth and
level ceiling.
APPROVALS AND STANDARDS
Laboratory listings and approvals for
the 8.0 K-Factor Model FR-1 QR-
EC/EC Horizontal Sidewall Sprinklers
are given in Table A.
WARNING
The 8.0 K-Factor Model FR-1 QR-
EC/EC Horizontal Sidewall Sprin-
klers described herein must be in-
stalled and maintained in
compliance with this document, as
well as applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the integ-
rity of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. The installing contractor or
manufacturer should be contacted
relative to any questions.
Installation of the Model FR-1 QR-
EC/EC Horizontal Sidewall Sprin-
klers in recessed escutcheons will void
all sprinkler warranties, as well as
possibly void the sprinklers Approv-
als and/or Listings.
TECHNICAL DATA
The 8.0 K-Factor Model FR-1 QR-
EC/EC Horizontal Sidewall Sprinklers
are rated for use at a maximum service
pressure of 175 psi (12,1 bar) and they
are available in the temperature rat-
ings and finishes indicated in Table A.
The flow “Q” in GPM (LPM) is deter-
mined by the following formula:
where the nominal discharge coeffi-
cient “K” equals 8.0 (115,2) and “p”
equals the residual flowing pressure in
psi (bar).
The FR-1 utilizes a dezincification re-
sistant bronze alloy frame. The strut is
silicone bronze and the deflector is
brass. The Hook is phosphor bronze,
the two halves of the Link Assembly
are nickel, the Ejection Spring is In-
conel, the Button is brass, and the
Gasket is Teflon

.
QKp
=
Printed in U.S.A. 3-01 TD547M
FIGURE A
8.0 K-FACTOR (SIN G8170)
MODEL FR-1 QR-EC/EC HORIZONTAL SIDEWALL SPRINKLERS
*Temperature rating is indicated on the Deflector.
** Pipe thread connections per ISO 7/1 can be provided on special request.
1-Frame
2 - Strut
3 - Deflector
4 - Hook
5 - Link
Assembly
6 - Ejection
Spring
7 - Button
8 - Gasket
TYCO FIRE PRODUCTS, 7071 S. 13th Street, Suite 103 Oak Creek, WI 53154 — www.gemsprinkler.com
Customer Service/Sales: Tel: (877) 436-8926 / Fax: (877) 866-9250
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
OBSOLETE

DuPont Registered Trademark
TYPE TEMPERATURE
RATING
FRAME
COLOR
CODE
NATURAL
BRASS
CHROME
PLATED
SPRINKLER FINISH
NOTES:
1. Listed by Underwriters Laboratories, Inc. for Light Hazard Occupancies per Table B.
2. Listed by Underwriters’ Laboratories of Canada for Light Hazard Occupancies per Table B.
3. Approved by Factory Mutual Research Corporation for Light Hazard Occupancies per Table C.
4. Accepted by the City of New York under BSA 334-79-SA.
TABLE A
LABORATORY LISTINGS AND APPROVALS
EC HORIZONTAL SIDEWALL (SIN G8170)
165°F/74°C Unpainted 1, 2, 3, 4
140°F/60°C Unpainted 1, 2, 4
EC HORIZONTAL SIDEWALL (SIN G8170)
NOTES:
(a) For use in Light Hazard Occupancy automatic sprinkler system applications per NFPA 13
(QR-EC is quick response - extended coverage and EC is standard response - extended coverage).
(b) The centerline of the sprinkler waterway is located 7/16 inch (11,1mm) below the deflector (Ref. Figure A).
(c) Ceiling is to slope downwards from the wall on which the sprinkler is located.
TABLE B
UL AND ULC LISTING CRITERIA FOR INSTALLATION OF THE
8.0 K-FACTOR MODEL FR-1 QR-EC/EC
HORIZONTAL SIDEWALL SPRINKLERS
APPLICATION
COVERAGE AREA
WxL
FT. x FT. (m x m)
MINIMUM
FLOW
GPM (LPM)
MINIMUM
PRESSURE
PSI (BAR)
DEFLECTOR-TO-
CEILING DISTANCE
A(b)
INCHES (mm)
SPRINKLER
TEMP. RATING
°F
16 x 18 (4,9 x 5,5)
26 (98) 10.6 (0.73) 4 to 6 (100 to 150)
29 (110)
22.6 (1.56)
4 to 6 (100 to 150)
QR-EC(a)
16 x 16 (4,9 x 4,9)
16 x 18 (4,9 x 5,5) 38 (144)
13.1 (0.90)
4 to 18 (100 to 450)
140, 165
140, 165
140, 165
MAX.
CEILING
SLOPE
IN./FT.(c)
(mm/m)
2 (166)
2 (166)
2 (166)
16 x 20 (4,9 x 6,1) 34 (129) 18.1 (1,25) 4 to 6 (100 to 150) 140, 165 2 (166)
16 x 20 (4,9 x 6,1) 45 (170) 31.6 (2,18) 4 to 18 (100 to 450) 140 2 (166)
14 x 22 (4,3 x 6,7) 37 (140) 21.4 (1,48) 4 to 6 (100 to 150) 140, 165 2 (166)
16 x 22 (4,9 x 6,7) 37 (140) 21.4 (1,48) 4 to 6 (100 to 150) 140 2 (166)
16 x 24 (4,9 x 7,3) 44 (167) 30.3 (2,09) 4 to 6 (100 to 150) 140 2 (166)
18 x 16 (5,5 x 4,9) 31 (117) 15.0 (1,03) 4 to 6 (100 to 150) 140, 165 2 (166)
18 x 18 (5,5 x 5,5) 33 (125) 17.0 (1,17) 4 to 6 (100 to 150) 140, 165 2 (166)
20 x 16 (6,1 x 4,9) 35 (133) 19.1 (1,32) 4 to 6 (100 to 150) 140, 165 2 (166)
16 x 20 (4,9 x 6,1) 45 (170) 31.6 (2,18) 4 to 18 (100 to 450) 165 2 (166)
16 x 22 (4,9 x 6,7) 37 (140) 21.4 (1,48) 4 to 6 (100 to 150) 165 2 (166)
16 x 24 (4,9 x 7,3) 44 (167) 30.3 (2.09) 4 to 6 (100 to 150) 165 2 (166)
EC(a)
OBSOLETE
INSTALLATION
NOTE
A leak tight 3/4 inch NPT sprinkler
joint should be obtained with a torque
of 10 to 20 ft.lbs. (13,4 to 26,8 Nm). A
maximum of 30 ft. lbs. (40,7 Nm) of
torque may be used to install sprin-
klers with 3/4 NPT connections.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
The Model FR-1 QR-EC/EC Horizontal
Sidewall Sprinklers must be installed
in accordance with the following in-
structions.
1. Horizontal sidewall sprinklers are to
be installed with their centerline of
waterway perpendicular to the back-
wall and parallel to the ceiling. The
top of the deflector is to face towards
the ceiling. It is recommended that a
lightweight spirit level be used to
level the sprinkler fitting, as applica-
ble, and the deflector as shown in
Figure B.
2. With pipe thread sealant applied to
the pipe threads, hand tighten the
sprinkler into the sprinkler fitting.
3. Tighten the sprinkler into the sprin-
kler fitting using only the W-Type 11
Sprinkler Wrench (Ref. Figure C).
The wrench is to be applied to the
sprinkler wrenching area shown in
Figure A.
FIGURE B
LEVELING OF SPRINKLER
FITTING AND DEFLECTOR
NOTES:
(a) For use in Light Hazard Occupancy automatic sprinkler system applications per Factory Mutual Loss Prevention Data Sheet 2-8N
(QR-EC is quick response - extended coverage).
(b) The centerline of the sprinkler waterway is located 7/16 inch (11,1mm) below the deflector (Ref. Figure A).
(c) Ceiling is to slope downwards from the wall on which the sprinkler is located.
TABLE C
FM APPROVAL CRITERIA FOR INSTALLATION OF THE
8.0 K-FACTOR MODEL FR-1 QR-EC/EC
HORIZONTAL SIDEWALL SPRINKLERS
APPLICATION
COVERAGE AREA
WxL
FT. x FT. (m x m)
MINIMUM
FLOW
GPM (LPM)
MINIMUM
PRESSURE
PSI (BAR)
DEFLECTOR-TO-
CEILING DISTANCE
A(b)
INCHES (mm)
SPRINKLER
TEMP. RATING
°F
16 x 18 (4,9 x 5,5)
32 (121) 16 (1,10) 4 to 12 (100 to 300)
36 (136)
25 (1,72)
4 to 12 (100 to 300)
QR-EC(a)
16 x 16 (4,9 x 4,9)
16 x 20 (4,9 x 6,1) 40 (151)
20 (1,38)
4 to 12 (100 to 300)
165
165
165
MAX.
CEILING
SLOPE
IN./FT.(c)
(mm/m)
1 (83)
1 (83)
1 (83)
16 x 22 (4,9 x 6,7) 44 (167) 30 (2,06) 4 to 12 (100 to 300) 165 1 (83)
16 x 24 (4,9 x 7,3) 48 (182) 36 (2,48) 4 to 12 (100 to 300) 165 1 (83)
FIGURE C
W-TYPE 11 SPRINKLER WRENCH
OBSOLETE
CARE AND MAINTENANCE
Model FR-1 Sprinklers must be main-
tained and serviced in accordance
with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
which it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the proper
authorities and all personnel who
may be affected by this action must be
notified.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
shipped or stored where their tempera-
tures will exceed 100°F/38°C and they
must never be painted, plated, coated,
or otherwise altered after leaving the
factory. Modified or over-heated sprin-
klers must be replaced.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service. or over-heated
sprinklers must be replaced.
LIMITED WARRANTY
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL, INDI-
RECT, SPECIAL OR CONSEQUEN-
TIAL DAMAGES, INCLUDING BUT
NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS
OR IMPLIED, INCLUDING WARRAN-
TIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PUR-
POSE.
ORDERING PROCEDURE
A Product Symbol Number (PSN) is
not specified when ordering sprinklers
with thread connections per ISO 7/1.
Contact your local distributor for avail-
ability.
140°F Sprinkler Assemblies:
Specify: 8.0 K-Factor, 140F, Model
FR-1 QR-EC Horizontal Sidewall
Sprinkler with (specify type of finish),
PSN (specify from Table B).
165°F Sprinkler Assemblies:
Specify: 8.0 K-Factor, 165F, Model
FR-1 QR-EC/EC Horizontal Sidewall
Sprinkler with (specify type of finish),
PSN (specify from Table B).
“Special Order”
Sprinkler Assemblies with ISO 7/1
Thread Connections:
Specify: 8.0 K-Factor, (specify “140F
Model FR-1 QR-EC” or “165F Model
Fr-1 QR-EC/EC”) Horizontal Sidewall
Sprinkler with (specify type of finish)
and with thread connection per ISO
7/1.
Sprinkler Wrench:
Specify: W-Type 11 Sprinkler Wrench,
PSN 56-452-1-001.
PATENTS
The following patent is applicable to
the Model FR-1 QR-EC Horizontal
Sidewall Sprinkler:
U.S.A. . . . . . . . . . . . . . . . . . . 4,901,799
WEIGHT
The nominal weights are as follows.
8.0 K-Factor Model FR-1
QR-EC/EC HSW Sprinkler . . 3.7 ozs. (105 g)
W-Type 11
Sprinkler Wrench . . . . . . . . . 17.7 ozs. (500 g)
PSN 58 — XXX — X — XXX
140°F/60°C
(QR-EC)
140
TEMPERATURE
RATING
1
SPRINKLER
FINISH
TABLE B
PRODUCT SYMBOL NUMBER SELECTION FOR
8.0 K-FACTOR MODEL FR-1 QR-EC/EC
HORIZONTAL SIDEWALL SPRINKLERS
CHROME PLATED
NATURAL BRASS
9
TYPE
EC HORIZONTAL
SIDEWALL
170 165 165°F/74°C
(QR-EC/EC)
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product CENTRAL K25-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K25-1 User manual

Tyco Fire Product Star Pulsar ESFR-25 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar ESFR-25 User manual

Tyco Fire Product Gem F978 User manual

Tyco Fire Product

Tyco Fire Product Gem F978 User manual

Tyco Fire Product Gem F892X User manual

Tyco Fire Product

Tyco Fire Product Gem F892X User manual

Tyco Fire Product TY300-FRB User manual

Tyco Fire Product

Tyco Fire Product TY300-FRB User manual

Tyco Fire Product SIN S1800 User manual

Tyco Fire Product

Tyco Fire Product SIN S1800 User manual

Tyco Fire Product Star E User manual

Tyco Fire Product

Tyco Fire Product Star E User manual

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product Gem F960 User manual

Tyco Fire Product

Tyco Fire Product Gem F960 User manual

Tyco Fire Product Gem F685 User manual

Tyco Fire Product

Tyco Fire Product Gem F685 User manual

Tyco Fire Product SIN S3230 User manual

Tyco Fire Product

Tyco Fire Product SIN S3230 User manual

Tyco Fire Product Star Mizar S215 User manual

Tyco Fire Product

Tyco Fire Product Star Mizar S215 User manual

Tyco Fire Product Star SG300 User manual

Tyco Fire Product

Tyco Fire Product Star SG300 User manual

Tyco Fire Product CENTRAL GB User manual

Tyco Fire Product

Tyco Fire Product CENTRAL GB User manual

Tyco Fire Product CENTRAL H-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL H-1 User manual

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product Star SG-R User manual

Tyco Fire Product

Tyco Fire Product Star SG-R User manual

Tyco Fire Product Omega HEC-12 RES User manual

Tyco Fire Product

Tyco Fire Product Omega HEC-12 RES User manual

Tyco Fire Product CENTRAL ELO Optima User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO Optima User manual

Tyco Fire Product Star SG S180 User manual

Tyco Fire Product

Tyco Fire Product Star SG S180 User manual

Tyco Fire Product CENTRAL ELO-231 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 User manual

Tyco Fire Product Gem ISSUE D QUARTZOID User manual

Tyco Fire Product

Tyco Fire Product Gem ISSUE D QUARTZOID User manual

Tyco Fire Product EC-HS User manual

Tyco Fire Product

Tyco Fire Product EC-HS User manual

Tyco Fire Product RFII Series User manual

Tyco Fire Product

Tyco Fire Product RFII Series User manual

Popular Irrigation System manuals by other brands

Reliable F1-42 Series Bulletin

Reliable

Reliable F1-42 Series Bulletin

Reliable DH56 Dry quick start guide

Reliable

Reliable DH56 Dry quick start guide

Phytotronics WATER PRO manual

Phytotronics

Phytotronics WATER PRO manual

Viking M Technical data

Viking

Viking M Technical data

TOOLCRAFT 1561112 operating instructions

TOOLCRAFT

TOOLCRAFT 1561112 operating instructions

Tyco ESFR-22 manual

Tyco

Tyco ESFR-22 manual

Komet Pivot operating instructions

Komet

Komet Pivot operating instructions

Reliable F1FR quick start guide

Reliable

Reliable F1FR quick start guide

Gardena V1 operating instructions

Gardena

Gardena V1 operating instructions

Viking M Technical data

Viking

Viking M Technical data

Hunter Institutional Series quick start guide

Hunter

Hunter Institutional Series quick start guide

Sime MERCURY Operation, Installation, Maintenance, Spare Parts

Sime

Sime MERCURY Operation, Installation, Maintenance, Spare Parts

Toro DRIP ZONE VALVE KIT 53749 installation instructions

Toro

Toro DRIP ZONE VALVE KIT 53749 installation instructions

Westfalia Sun 91 98 04 Original instructions

Westfalia

Westfalia Sun 91 98 04 Original instructions

Senju Sprinkler CN-QR quick start guide

Senju Sprinkler

Senju Sprinkler CN-QR quick start guide

Viking MICROFAST VK352 Technical data

Viking

Viking MICROFAST VK352 Technical data

Eden 96998EDAMZ quick start guide

Eden

Eden 96998EDAMZ quick start guide

Cellfast MULTI TT IDEAL 52-065 user manual

Cellfast

Cellfast MULTI TT IDEAL 52-065 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.