TFP443
Page 5 of 6
NOTICE
As long as the protective Cap remains
in place, the system is considered “Out
Of Service”.
Step 5. After the ceiling has been
completed with the 2-1/2 inch (63
mm) diameter hole and in preparation
for installing the Cover Plate/Retainer
Assembly, remove and discard the Pro-
tective Cap, and verify that the Deflec-
tor moves up and down freely.
If the sprinkler has been damaged and
the deflector does not move up and
down freely, replace the entire sprinkler
assembly. Do not attempt to modify or
repair a damaged sprinkler.
Step 6. Screw on the Cover Plate/
Retainer Assembly until its flange
contacts the ceiling. Do not continue
to screw on the Cover Plate/Retainer
Assembly such that it lifts a ceiling
panel out of its normal position.
If the Cover Plate/Retainer Assembly
cannot be engaged with the Mount-
ing Cup or the Cover Plate/Retainer
Assembly cannot be engaged suffi-
ciently to contact the ceiling, the Sprin-
kler Fitting must be repositioned.
Care and
Maintenance
The TYCO RAPID RESPONSE Series
LFII Residential Flat-Plate Concealed
Pendent Sprinkler (TY2524) must be
maintained and serviced in accordance
with this section:
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of a Cover Plate may delay the
sprinkler operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
When properly installed, there is a
nominal 1/8 inch (3,2 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 3. This
air gap is necessary for proper opera-
tion of the sprinkler by allowing heat
flow from a fire to pass below and
above the Cover Plate to help assure
appropriate release of the Cover Plate
in a fire situation. If the ceiling needs
repainting after sprinkler installation,
exercise care to ensure that the new
paint does not seal off any of the air
gap. Failure to do so may impair sprin-
kler operation.
Factory painted Cover Plates must not
be repainted. They should be replaced,
if necessary, by factory painted
units. Non-factory applied paint may
adversely delay or prevent sprinkler
operation in the event of a fire.
Do not pull the Cover Plate relative to
the Retainer. Separation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied or overheated sprinklers must be
replaced.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or sprinkler manufac-
turer regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product description and Part
Number (P/N).
Sprinkler/Support Cup Assembly
Specify: Series LFII (TY2524), K = 4.9
(70,6), Residential Flat-Plate Concealed
Pendent Sprinkler without Cover Plate/
Retainer Assembly, P/N 51-114-1-160
Cover Plate/Retainer Assembly
Specify: Series LFII (TY2524), K = 4.9
(70,6), Residential Flat-Plate Concealed
Pendent Sprinkler Cover Plate/Retainer
Assembly with (specify) finish, P/N
(specify):
Ivory (RAL 1015)...............56-202-0-135
Beige (RAL 1001) ..............56-202-2-135
Pure White(b) (RAL 9010) . . . . . . . . 56-202-3-135
Signal White(a) (RAL 9003) . . . . . . . 56-202-4-135
Grey White (RAL 9002) . . . . . . . . . 56-202- 5-135
Brown (RAL 8028) . . . . . . . . . . . . .56-202-6-135
Black (RAL 9005) ..............56-202-7-135
Brushed Brass ................56-202-8-135
Brushed Chrome ..............56-202-9-135
Custom Paint .................56-202-X-135
(a) Previously known as Bright White
(b) Eastern Hemisphere sales only
Note: All Custom Cover Plates are
painted using Sherwin Williams Interior
Latex Paint. Contact TYCO Customer
Service with any questions related to
custom orders.
Sprinkler Wrench
Specify: W-Type 18 Sprinkler Wrench,
P/N 56-000-1-265