  9. Tyco Fire Product CENTRAL ELO-16 GB FR User manual

Tyco Fire Product CENTRAL ELO-16 GB FR User manual

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product Star E User manual

Tyco Fire Product

Tyco Fire Product Star E User manual

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product TY-B Series User manual

Tyco Fire Product

Tyco Fire Product TY-B Series User manual

Tyco Fire Product Gem TY-B User manual

Tyco Fire Product

Tyco Fire Product Gem TY-B User manual

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product SIN S3244 User manual

Tyco Fire Product

Tyco Fire Product SIN S3244 User manual

Tyco Fire Product CENTRAL Attic BB1-17/32 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Attic BB1-17/32 User manual

Tyco Fire Product Gem F978 User manual

Tyco Fire Product

Tyco Fire Product Gem F978 User manual

Tyco Fire Product Gem RFII Series User manual

Tyco Fire Product

Tyco Fire Product Gem RFII Series User manual

Tyco Fire Product STAR S160E User manual

Tyco Fire Product

Tyco Fire Product STAR S160E User manual

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product CENTRAL EC-25 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL EC-25 User manual

Tyco Fire Product Star PH-5 User manual

Tyco Fire Product

Tyco Fire Product Star PH-5 User manual

Tyco Fire Product Gem F938 User manual

Tyco Fire Product

Tyco Fire Product Gem F938 User manual

Tyco Fire Product RFII Series User manual

Tyco Fire Product

Tyco Fire Product RFII Series User manual

Tyco Fire Product Star Celeste S150 User manual

Tyco Fire Product

Tyco Fire Product Star Celeste S150 User manual

Tyco Fire Product CENTRAL ESFR-25 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-25 User manual

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product central bvr User manual

Tyco Fire Product

Tyco Fire Product central bvr User manual

Tyco Fire Product CENTRAL LF User manual

Tyco Fire Product

Tyco Fire Product CENTRAL LF User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product Gem F898 User manual

Tyco Fire Product

Tyco Fire Product Gem F898 User manual

Tyco Fire Product EC-17 User manual

Tyco Fire Product

Tyco Fire Product EC-17 User manual

Tyco Fire Product CENTRAL Omega EC-20A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Omega EC-20A User manual

Popular Irrigation System manuals by other brands

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Reliable RFC30 LL manual

Reliable

Reliable RFC30 LL manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model ELO-16 GB FR
11.2 K-factor
Quick Response - ECLH
Standard Response - ECOH
Flush, Recessed or Extended Dry Pendent Glass Bulb Automatic Sprinkler
No. 5-14.0
CENTRAL ELO-16 GB FR Dry Pendent 3-01
ELO-16 GB FR
Dry Pendent
Extended
Coverage
Sprinklers
I
M
A
O
P
T
systems designed in accordance with
the standard installation rules recog-
nized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on NFPA 13 requirements). They
produce a hemispherical water dis-
charge pattern below the deflector.
The Recessed, Flush, and Extended
Escutcheons for the ELO-16 GB FR Dry
Pendent Sprinklers are separable two-
piece designs which allow installation of
the sprinklers and pressure testing of
the fire protection system prior to
installation of a suspended ceiling. They
also permit removal of suspended
ceiling panels without having to first
shut down the fire protection system
and remove the sprinklers.
Operation: When the ELO-16 GB FR
Dry Pendent Sprinkler is in service,
water is prevented from entering the
assembly by the Plunger Assembly, a
Plug & O-ring in the Inlet (Spool) of the
Sprinkler. The glass Bulb contains a
fluid which expands when exposed to
heat. When the rated temperature is
reached, the fluid expands sufficiently to
shatter the glass Bulb, and the Bulb
Seat is released. The GuideTube drops,
allowing the Plug & O-ring to withdraw
from the Inlet, which then allows the
sprinkler to activate and flow water.
WARNING
The ELO-16 GB FR Dry Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authorities
having jurisdiction. Failure to do so may
impair the integrity of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
The ELO-16 GB FR Dry Pendent
Sprinklers must only be installed in
fittings that meet the requirements of
the Design Criteria section.
Product
Description
The Central Model ELO-16 GB FR, 11.2
K-factor Quick Response Extended
Coverage Light Hazard and Standard
Response Extended Coverage Ordinary
Hazard, Dry Pendent Sprinklers are
decorative glass bulb automatic
sprinklers designed for use
where pendent sprinklers are
required on dry pipe systems that are
exposed to freezing temperatures
(e.g. sprinkler drops from unheated
portions of buildings), or
where sprinklers and/or a portion of
the connecting piping may be
exposed to freezing temperatures
(e.g. sprinkler drops from wet
systems into freezers), or
where pendent sprinklers are used on
systems that are seasonably drained
to avoid freezing (e.g. vacation resort
areas).
The ELO-16 GB FR Dry Pendent
Sprinklers are available in a wide range
of operating temperatures and order
lengths.
The ELO-16 GB FR Dry Pendent
Sprinklers are listed for use in Light
Hazard occupancies, with a quick
response thermal sensitivity at spacings
up to 18' x 18' (5,5 x 5,5 m). When
used in light hazard occupancies, the
ELO-16 GB FR Dry Pendent Sprinklers
are limited to a type of unobstructed
constuction consisting of flat, smooth
ceilings.
The ELO-16 GB FR Dry Pendent
Sprinklers are listed for use in ordinary
hazard occupancies, with a standard
response thermal sensitivity at spacings
up to 16' x 16' (4,9 x 4,9 m). When
used in ordinary hazard occupancies,
the ELO-16 GB FR Dry Pendent
Sprinklers may be installed in unob-
structed and non-combustible ob-
structed construction.
The ELO Dry Pendent Sprinklers are
intended for use in fire sprinkler
OBSOLETE
The Model ELO-16 GB FR Dry Pendent
Sprinklers are UL and ULC Listed & NYC
Approved (MEA 120-97-E) as quick
response sprinklers for use in light hazard
occupancies, in accordance with current
NFPA standards & the design parameters
set forth in Table 1 of this Data Sheet.
The Model ELO-16 GB FR Dry Pendent
Sprinklers are UL and ULC Listed & NYC
Approved (MEA 120-97-E) as standard
response sprinklers for use in ordinary
hazard occupancies, in accordance with
current NFPA standards & the design
parameters set forth in Table 1 of this
Data Sheet.
The minimum lateral spacing between the
ELO-16 GB FR Dry Pendent Sprinkers, to
prevent cold soldering, is 12'-6" (3,81 m).
The ELO-16 GB Dry Pendent Sprinklers
are to be installed in the 1 inch NPT outlet
of a malleable iron threaded tee fitting per
ANSI B16.3 or cast iron threaded tee
fitting per ANSI B16.4 with the end
sprinkler fitting on a branch line to be
plugged as shown in Figure 3. Only use
maximum 2-1/2 inch size reducing tee's
for dry pipe sprinkler systems.
NOTES
Do not install the ELO-16 GB Dry Pendent
Sprinklers into any other type fitting
Design
Criteria
1" NPT
2-3/4"
(69,9 mm)
"A" Dimension
(order length)
FINISHED
CEILING
LINE
FACE OF
FITTING
ELEVATION VIEW
WRENCH
FLAT
9/16"
(14,3 mm)
MAKE-IN
Recessed -- 1-13/16"
(46,0 mm)
Ref.
Flush -- 2-7/16"
(61,9 mm)
Ref.
Figure 2 - ELO-16 GB FR Dry Pendent Sprinkler, Flush & Recessed
Figure 1 - ELO-16 GB FR Dry Pendent Sprinkler, Extended
Figure 3 - W-Type 8 (1068) Sprinkler Wrench
1" NPT
2-3/4"
(69,9 mm)
If "A" Dimension is < 3-1/4"
(82,6 mm)
,
Dimension is 3-3/4" 3/4"
(95,3 mm 19,1 mm)
If "A" Dimension is > 3-1/4"
(82,6 mm)
,
Dimension is 4-1/2" 1-1/2"
(114,3 mm 38,1 mm)
±
"A" Dimension
(order length)
FINISHED
CEILING
LINE
FACE OF
FITTING
ELEVATION VIEW
±
WRENCH
FLAT ±
±
9/16"
(14,3 mm)
MAKE-IN
Sprinkler Identification Number
SIN C5239
Approvals
UL and ULC Listed. NYC Approved.
(The approvals apply only to the service
conditions indicated in the Design Criteria
Section)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1 inch NPT
Discharge Coefficient
K = 11.2 GPM/psi1/2 (161,3 LPM/bar1/2)
Temperature Ratings
155o F/68oC, 200oF/93oC, 286°F/141°C
Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass
Physical Characteristics
The Model ELO-16 GB FR Dry Pendent
Sprinklers utilize a dezincification resistant
(DZR) bronze frame & a 3 mm bulb. The
Plug & Spool are brass & the O-ring is
silicone rubber. The Main Tube is carbon
steel. The Frame is bronze, the Deflector
is brass & the Compression Screw is
bronze. The Guide Tube & Bulb Seat are
brass. The two pieces of the three
available Escutcheons are low carbon
steel.
Technical
Data
WRENCH
RECESS PLUG
OBSOLETE
without first consulting the Technical
Services Department. Failure to use the
appropriate fitting may result in: failure of
the sprinkler to properly operate due to
formation of ice over the inlet Plug or
binding of the inlet Plug; or, insufficient
engagement of the inlet pipe threads with
consequent leakage.
In the case of a dry pipe sprinkler system
subject to freezing, the use of a fitting of
other than the types specified may result
in failure of the sprinkler to properly
operate due to the formation of ice over
the Inlet.
Branch, cross, and feed main piping
connected to Dry Sprinklers & subject to
freezing temperatures must be pitched for
drainage in accordance with the minimum
requirements of the National Fire
Protection Association for dry pipe
sprinkler systems.
When Dry Sprinklers are to be used in wet
pipe sprinkler systems protecting areas
subject to freezing temperatures (e.g.,
sprinkler drops into freezers), consider-
ation must be given to the appropriate
length of the sprinkler that will prevent
freezing of the water in the connecting
pipes due to conduction.
When Dry Sprinklers penetrate a ceiling
into an area subject to freezing, the
clearance space around the Main Tube
must be completely sealed in order to
prevent the leakage of moist air into the
freezing area which might result in the
formation of condensate around the
Frame, Deflector, Bulb Seat, or Bulb.
Failure to prevent the formation of
condensate could result in the build-up of
ice around the releasing components &
consequently, either an inadvertent
operation of the sprinkler or impaired
operation due to reduced thermal
sensitivity.
PLUNGER
ASSEMBLY
SPRINKLER
FRAME
COMPRESSION
SCREW
DEFLECTOR
GUIDE
TUBE
MAIN
TUBE
BULB
SEAT
GLASS BULB
OPERATING
ELEMENT
SPOOL
SUPPORT CUP
EXTENDED
SKIRT
ELO DP
RECESSED
ESCUTCHEON
VENT HOLE
Figure 4 - Cross Section, ELO-16 GB FR Dry Pendent
Refer to the Design Criteria section for
other important requirements regarding
piping design and sealing of the clearance
space around the Main Tube.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of liquid
from the bulb. With the sprinkler held
horizontally, a small air bubble should be
present. The diameter of the air bubble is
approximately 1/16 inch (1,6 mm) for the
155
°
F/68
°
C to 3/32 inch (2,4 mm) for the
286
°
F/141
°
C rating.
A leak tight 1 inch NPT sprinkler joint
should be obtained with a torque of 20 to
30 ft.lbs. (26,8 to 40,2 Nm). Higher levels
of torque may distort the 1 inch NPT
sprinkler inlet with consequent leakage or
impairment of the sprinkler.
OrderingLengthforDryPendentHeads
Flush — The “A” dimension is measured from the face of the tee to the finished ceiling. This is only approximately flush. Order to the
nearest 1/4" (6,4 mm). Minimum “A” dimension is 2" (50,8 mm).
Recessed — The “A” dimension is measured from the face of the tee to the finished ceiling. Minimum “A” dimension is 2-1/4"
(57,2 mm). Adjustment is ±3/8" (9,5 mm).
Extended — The “A” dimension is measured from the face of the tee to the finished ceiling. Follow one of these two options:
If this dimension is less than or equal to 3-1⁄4" (82,6 mm), total adjustment is 1-1⁄2" (38,1 mm) (from the mid point of the adjustment range
±3⁄4" (19,1 mm)). Order to the nearest 1⁄4" (6,4 mm). Minimum “A” dimension is 0".
If this dimension is greater than 3-1⁄4" (82,6 mm), the total adjustment is 3" (76,2 mm) (from the mid point of the adjustment range ±1-1⁄2"
(38,1 mm)). Order to the nearest 1⁄4" (6,4 mm). Minimum “A” dimension is 3-1⁄4" (82,6 mm).
Minimum Minimum Minimum
Spacing Flow/Pressure Flow/Pressure Flow/Pressure
Light Hazard Ordinary Hazard I Ordinary Hazard II
(0.1 gpm/sq. ft.) (0.15 gpm/sq. ft.) (0.20 gpm/sq. ft.)
14' x 14' 30.0 gpm / 7.2 psi 39.0 gpm / 12.1 psi
(4,9m x 4,9m)
--- 113,6 Lpm / 0,50 bar 147,6 Lpm / 0,83 bar
(Flush, Rec. & Ext.) (Flush, Rec. & Ext.)
16' x 16' 30.0 gpm / 7.2 psi 39.0 gpm / 12.1 psi 51.0 gpm / 20.7 psi
(4,9m x 4,9m)
113,6 Lpm / 0,50 bar 147 ,6 Lpm / 0,83 bar 193,1 Lpm / 1,43 bar
(Flush, Rec. & Ext.) (Flush, Rec. & Ext.) (Flush, Rec. & Ext.)
18' x 18' 33.0 gpm / 8.7 psi
(5,5m x 5,5m) 124,9 Lpm / 0,60 bar --- ---
(Flush & Extended)
Table 1 - UL and ULC Listing Criteria for the Installation of Model
ELO-16 GB FR Extended Coverage Dry Pendent Sprinklers
The ELO-16 GB FR Dry Pendent
Sprinkers must be installed in accordance
with the following instructions:
NOTES
The ELO-16 GB FR Dry Pendent
Sprinkers must only be installed in fittings
that meet the requirements of the Design
Criteria section.
Installation
Do not attempt to compensate for
insufficient adjustment in an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
Step 1. The sprinkler must be installed
only in the pendent position and with the
deflector parallel to the mounting surface.
Step 2. With pipe thread sealant applied
to the pipe threads, hand tighten the
sprinkler into the sprinkler fitting.
Step 3. Wrench tighten the sprinkler by
wrenching on the Main Tube with a pipe
wrench whenever the casing is readily
accessible. Otherwise, use a W-Type 8
Sprinkler Wrench (Ref. Figure 3). The
wrench recess of the W-Type 8 is to be
(Continued on Page 4)
OBSOLETE
Printed in U.S.A. 3-01
Ordering Information: When placing
an order, indicate the full product name.
Please specify the quantity, model,
style, orifice size, temperature rating,
type of finish or coating, and sprinkler
wrench. Refer to price list for complete
listing of Part Numbers.
Order dry pendents by “A” dimension to
the nearest 1⁄4" (6,4 mm).
Patents: U.S.A. Patent Number
5,366,022 is applicable to the Model
ELO-16 GB FR Dry Pendent Sprin-
klers. Other Patents are pending with
regard to other design features.
Teflon is a trademark of the DuPont Corp.
Ordering
Information
Flow Control
Tyco Fire

Products
The ELO-16 GB FR Dry Pendent
Sprinklers
must be maintained and
serviced in accordance with the
following instructions.
NOTES
Absence of the outer piece of an
escutcheon, which is used to cover a
clearance hole, may delay the time to
sprinkler operation in a fire situation.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system which
it controls, permission to shut down the
affected fire protection systems must be
obtained from the proper authorities and
all personnel who may be affected by
this action must be notified.
It is recommended that the piping
connected to Dry Sprinklers be periodi-
cally checked to assure that proper
pitch and drainage is in accordance with
the minimum requirements of the
National Fire Protection Association if
the piping is subject to freezing tem-
peratures.
A Vent Hole is provided in the Bulb Seat
(Ref. Figure 4) to indicate if the Dry
Sprinkler is remaining dry. Evidence of
leakage from the Vent Hole is an
indication that there may be weepage
past the O-ring seal and, therefore, it is
an indication that the sprinkler needs to
be removed for determining the cause
of leakage (e.g. an improper installation
or an ice plug). The fire protection
system control valve must be closed
and the system drained before remov-
ing the sprinkler.
Sprinklers which are found to be leaking
or exibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
shipped or stored where their tempera-
tures will exceed 100°F/38°C and they
must never be painted, plated, coated
or otherwise altered after leaving the
factory. Modified sprinklers must be
replaced. Sprinklers that have been
exposed to corrosive products of
combustion, but have not operated,
Care &
Maintenance
should be replaced if they cannot be
completely cleaned by wiping the
sprinkler with a cloth or by brushing it
with a soft bristle brush.
Care must be exercised to avoid
damage - before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb (ref. Installation Section).
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(e.g., NFPA 25), in addition to the
standards of any other authorities
having jurisdiction. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspection
Service.
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed and
maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
Tyco Fire Products. No warranty is
given for products or components
manufactured by companies not
affiliated by ownership with Tyco Fire
Products or for products and compo-
nents which have been subject to
misuse, improper installation, corrosion,
or which have not been installed,
maintained, modified or repaired in
accordance with applicable Standards
of the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Materi-
als found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither
assumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL, INDI-
RECT, SPECIAL OR CONSEQUEN-
Limited
Warranty
Installation
(Cont.)
applied to the sprinkler wrench flats (Ref.
Figure 1 & 2).
Step 4. After a suspended ceiling has
been installed or the finish coat has been
applied to a fixed ceiling (as applicable),
slide on the outer piece of the Escutcheon
until it comes in contact with the ceiling.
Do not lift the ceiling panel out of its
normal position.
TIAL DAMAGES, INCLUDING BUT
NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS'
LIABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR
PURPOSE.
OBSOLETE