Series TY-B, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
Page 1 of 4 FEBRUARY 2014 TFP152
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cau-
tions with respect to handling and
installation of sprinkler systems and
components. Improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers described in this data sheet
are standard response, standard cover-
age, decorative 5 mm glass bulb type
spray sprinklers designed for use in
light, ordinary, or extra hazard, com-
mercial occupancies such as banks,
hotels, shopping malls, factories,
reneries, and chemical plants.
The recessed version of the Series
TY-B Pendent Sprinkler, where appli-
cable, is intended for use in areas with a
nished ceiling. This recessed pendent
sprinkler uses one of the following:
•
A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 inch (15,9 mm) from
the ush pendent position.
•
A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 inch (12,7 mm) from
the ush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the xed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-B Sprinklers are described in
Technical Data Sheet TFP352. Sprinkler
guards and shields are described in
Technical Data Sheet TFP780.
NOTICE
The Series TY-B Sprinklers described
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa-
tion, in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Numbers (SINs)
TY315 ......Upright 5.6K, 1/2˝ NPT
TY325 .....Pendent 5.6K, 1/2˝ NPT
Technical
Data
Approvals
UL and C-UL Listed
FM, LPCB, and VdS Approved
CE Certied
Sprinklers with Polyester Finish are
UL and C-UL Listed as Corrosion-
Resistant Sprinklers.
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
* The maximum working pressure of 250 psi
(17.2 bar) only applies to the listing by Un-
derwriters Laboratories, Inc. (UL).
Discharge Coefficient
K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
Temperature Ratings
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
360°F (182°C)†
† UL, C-UL, and VdS Approved only
Finishes
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame ................... Bronze
Button..............Brass/Copper
Sealing Assembly .........Stainless
Steel w/TEFLON
Bulb ......................Glass
Compression Screw. . . . . . . . Bronze
Deector................. Bronze
TFP152
Page 2 of 4
Operation
The glass bulb contains a uid which
expands when exposed to heat. When
the rated temperature is reached, the
uid expands sufciently to shatter the
glass bulb, allowing the sprinkler to
activate and water to ow.
Design
Criteria
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers are intended for re protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing
or Approval agency (e.g., UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of the FM Loss Preven-
tion Data Sheets). Only the Style 15
or Style 20 Recessed Escutcheon, as
applicable, is to be used for recessed
pendent installations.
Installation
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) to 3/32
inch (2,4 mm) for the 360°F (182°C)
temperature ratings.
A leak-tight 1/2 inch NPT sprinkler
joint should be obtained by applying a
minimum-to-maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Do not attempt to compensate for
insufcient adjustment in the escutch-
eon plate by under- or over-tightening
the sprinkler. Readjust the position of
the sprinkler tting to suit.
Upright and Pendent Sprinklers
The Series TY-B Upright and Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1. Install pendent sprinklers in
the pendent position; install upright
sprinklers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
tting.
Components:
1/2" NPT
1
5
2
3
4
2"
(50,8 mm)
Frame
Button
Sealing
Assembly
*
6
2
-
-
3
-
1
*
-
6 Deector
Compression
Screw
-
5
4-Bulb
2-7/8" (73,0 mm) DIA.
1-3/8"
(34,9 mm)
2"
(50,8 mm)
WRENCH
FLATS
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
STYLE 15 or 20
RECESSED
ESCUTCHEON
7/16" (11,1 mm)
NOMINAL MAKE-IN
Pipe thread connections per ISO 7-1
can be provided on special request.
** DEFLECTOR *
Temperature rating is
indicated on Deector.
DEFLECTOR *
*
ESCUTCHEON PLATE
SEATING SURFACE
**
**
1/2"
NPT
UPRIGHTCROSS SECTION PENDENT RECESSED PENDENT
WRENCH RECESS
(USE ONLY
END "A")
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 1
SERIES TY-B UPRIGHT (TY315) AND PENDENT (TY325) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
FIGURE 2
W-TYPE 6
SPRINKLER WRENCH
TFP152
Page 3 of 4
Step 3. Tighten the sprinkler into the
sprinkler tting using only the W-Type
6 Sprinkler Wrench (Figure 2). With
reference to Figure 1, apply the W-Type
6 Sprinkler Wrench to the wrench ats.
Torque sprinklers 7 to 14 ft.-lbs. (9,5 to
19,0 Nm).
Recessed Pendent Sprinklers
The Series TY-B Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15 or
Style 20 Mounting Plate, as applicable,
over the sprinkler threads and with
pipe-thread sealant applied to the pipe
threads, hand-tighten the sprinkler into
the sprinkler tting.
Step B. Tighten the sprinkler into the
sprinkler tting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench ats. Torque
sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0
Nm).
Step C. After the ceiling is installed or
the nish coat is applied, slide on the
Style 15 or Style 20 Closure over the
Series TY-B Sprinkler and push the
Closure over the Mounting Plate until
its ange contacts the ceiling.
Care and
Maintenance
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system
that it controls, obtain permission to
shut down the affected re protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a re situation.
The owner must assure that the
sprinklers are not used for hanging
any objects and that the sprinklers are
only cleaned by means of gently dust-
ing with a feather duster; otherwise,
non-operation in the event of a re or
inadvertent operation may result.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned by
wiping the sprinkler with a cloth or by
brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section.)
Thereafter, annual inspections per
NFPA 25 are required; however, instead
of inspecting from the oor level, a
random sampling of close-up visual
inspections should be made.
The owner is responsible for the
inspection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa
-
tion (e.g., NFPA 25), in addition to the
standards of any other authorities hav-
ing jurisdiction. Contact the installing
contractor or sprinkler manufacturer
regarding any questions.
Automatic sprinklers are recommended
to be inspected, tested, and maintained
by a qualied Inspection Service in
accordance with local requirements
and/or national codes.
MOUNTING
PLATE
MOUNTING
SURFACE
SERIES
TY-B
2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER
FITTING
2-1/4" DIA.
(57,2 mm)
1/8"
(3,2 mm)
CLOSURE
3/8±5/16"
(9,5±7,9 mm)
1-3/8" (34,9 mm)
5/8" (15,9 mm)
3/4" (19,1 mm)
FLUSH
MOUNTING
SURFACE
SERIES
TY-B
CLOSURE MOUNTING
PLATE
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
FACE OF
SPRINKLER
FITTING
1/8"
(3,2 mm)
5/16±1/4"
(7,9±6,4 mm)
1/2" (12,7 mm)
1-3/8" (34,9 mm)
FLUSH
7/8" (22,2 mm)
FIGURE 4
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY (TY325)
WITH TWO-PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
FIGURE 5
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY (TY325)
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
TFP152
Page 4 of 4
Copyright © 2014 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of The DuPont Corporation.
P/N* 77 – XXX – X – XXX
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-B Upright or Pen-
dent (specify) Sprinkler, SIN (specify),
K=5.6, Standard Response, (specify)
temperature rating, (specify) nish, P/N
(specify, refer to Table A)
Recessed Escutcheon
Specify: Style 15 Recessed Escutcheon
with (specify*) nish, P/N (specify*)
Specify: Style 20 Recessed Escutcheon
with (specify*) nish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
SIN
570 5.6K UPRIGHT (1/2˝ NPT) TY315
571 5.6K PENDENT (1/2˝ NPT) TY325
SPRINKLER
FINISH
1NATURAL BRASS
3PURE WHITE (RAL9010)**
POLYESTER
4SIGNAL WHITE (RAL9003)
POLYESTER
9CHROME PLATED
TEMPERATURE
RATINGS
135 135°F (57°C)
155 155°F (68°C)
175 175°F (79°C)
200 200°F (93°C)
286 286°F (141°C)
360 360°F (182°C)
000 OPEN***
*** OPEN indicates sprinkler
assembly without Glass Bulb,
Button, and Sealing Assembly
** Eastern Hemisphere sales only
* Use sufx “I” for ISO 7-1 connection;
for example, 77-570-4-175-I
TABLE A
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION

This manual suits for next models

2

Other Tyco Fire Protection Products Firefighting Equipment manuals

Tyco Fire Protection Products AM31 AQUAMIST Nozzle User manual

Tyco Fire Protection Products

Tyco Fire Protection Products AM31 AQUAMIST Nozzle User manual

Tyco Fire Protection Products ANSUL PS-150 User manual

Tyco Fire Protection Products

Tyco Fire Protection Products ANSUL PS-150 User manual

Tyco Fire Protection Products F3200 Instruction sheet

Tyco Fire Protection Products

Tyco Fire Protection Products F3200 Instruction sheet

Tyco Fire Protection Products ANSUL CHECKFIRE 210 User manual

Tyco Fire Protection Products

Tyco Fire Protection Products ANSUL CHECKFIRE 210 User manual

Popular Firefighting Equipment manuals by other brands

Waterous Advantus Foam Manager Operation and maintenance manual

Waterous

Waterous Advantus Foam Manager Operation and maintenance manual

POK Froggy user manual

POK

POK Froggy user manual

Hochiki FirePro Xtinguish Installation and operation manual

Hochiki

Hochiki FirePro Xtinguish Installation and operation manual

Shield Omega-X installation manual

Shield

Shield Omega-X installation manual

Meggitt F116 Series Maintenance manual

Meggitt

Meggitt F116 Series Maintenance manual

Tecnoalarm Tecnofire TFA1-298 Installation

Tecnoalarm

Tecnoalarm Tecnofire TFA1-298 Installation

Fike 403-0006 Installation and maintenance instructions

Fike

Fike 403-0006 Installation and maintenance instructions

Global Fire Equipment Valkyrie Vox C quick start guide

Global Fire Equipment

Global Fire Equipment Valkyrie Vox C quick start guide

Smoke Guard 200 quick start guide

Smoke Guard

Smoke Guard 200 quick start guide

Task Force Tips VORTEX 2 ER manual

Task Force Tips

Task Force Tips VORTEX 2 ER manual

ELKHART BRASS SFL-BG Operating and maintenance instructions

ELKHART BRASS

ELKHART BRASS SFL-BG Operating and maintenance instructions

STI EZ-Path 44+ Series installation instructions

STI

STI EZ-Path 44+ Series installation instructions

Security Brands S-1515 User & installation manual

Security Brands

Security Brands S-1515 User & installation manual

Global Fire Equipment ORION MINI-REP V2 Installation, operation & maintenance manual

Global Fire Equipment

Global Fire Equipment ORION MINI-REP V2 Installation, operation & maintenance manual

FireFlex Systems Inc. TOTALPAC 3 FIRECYCLE III Owner's operation and maintenance manual

FireFlex Systems Inc.

FireFlex Systems Inc. TOTALPAC 3 FIRECYCLE III Owner's operation and maintenance manual

Amerex 450 Owner's service manual

Amerex

Amerex 450 Owner's service manual

FireFlex 1230 Owner's operation and maintenance manual

FireFlex

FireFlex 1230 Owner's operation and maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.